Title: The key to comfort and reduced fuel use for all heating systems
1The key to comfort and reduced fuel use for all
heating systems
Exquisite Heat
22
33
4Fixed
temperature
boiler
control
4
55
6High boiler output is only required on a few
coldest days of the heating season.Most days
even comfort could be provided with reduced
energy expense.
December 20, 2020
6
7Why are these high temps
- The fellow who set the boiler at service time,
did not want a low heat call on the coldest day
of the year. - Folks did not have a way of regulating boiler
temperatures. - Who cares what you spend, or how much you waste
to the atmosphere???? - Folks never complain if they are too warm.
8Hey Folks
- At Exquisite Heat we believe your heating system
should be comfortable first. - We believe you deserve good comfort at least
energy expense.
9Hey Folks !!!!!
- Can you see the problem here?
- ANYONE ??
- We are talking about 90 of buildings in the
world.
10Daily Heating Needs
December 20, 2020
10
11Fixed
temperature
boiler
control
December 20, 2020
11
12December 20, 2020
12
13Symptoms
- Uneven comfort ( too warm-too cool)
- Windows open - energy escape
- Folks complain about comfort
- Low humidity and dry skin
- We raise the heat to warm cool spaces.
- Excessive run times for boiler
- Basement too hot- waste of energy
- High Fuel bills
- WHY?
1414
1515
16Fixed
temperature
boiler
control
December 20, 2020
16
17December 20, 2020
17
18For every 2 degrees we reduce boiler temperatures
1 savings on your gas or oil bill.
19Desired Solutions
- Even out the comfort in all rooms
- Shut the windows in overheated rooms
- Keep complaints down
- Higher humidity levels, less dry skin
- Set the Thermostat lower for all rooms
- Reduced running of the boiler, saves fuel
- Get the heat out of the basement, and into the
rooms - Lets lower those fuel bills
20WASTED
- If your too hot or too cold, arent you wasting
the - money you are already spending on Fuel for
heating ?????
21The Main Goal
- Precise comfort replacement for
building heat loss.
December 20, 2020
21
22Daily Heating Needs
December 20, 2020
22
23Energy act 2007
- Manufacturers of hot water boilers must provide a
means to adjust boiler output to actual heat load
by 2012. - Exquisite Heat is the ideal indoor reset solution.
23
24Thats fine if your buying a new boiler. What
about the rest of us? Can we do anything to
improve economy and comfort with our current
boiler?SureInstall Exquisite Heat to all
boilers.
25Exquisite Heat
- Adjusts heating supply temperatures according to
Thermostat demand history (over time).
December 20, 2020
25
26Even Comfort
- Precise heating plant energy use allows for
even comfort to everyone in the space.
26
27December 20, 2020
27
28Temperature vs. Thermostat
- The lower the radiator temperature the longer
it will take the thermostat to sense the change. -
28
2929
30Daily Heating Needs
December 20, 2020
30
3131
3232
33What happened?
- A new heating philosophy for even comfort.
- To satisfy Ideal Comfort Delivery during changing
building heat loss conditions - Boiler supply is adjusted precisely every minute
of the hour. - Reduced energy use provides a before tax
return to the owner.
33
34Efficiency
- Reduced boiler piping standby heat loss for Hot
water and Steam boilers. - Cooler boiler operation
- Better air circulation at baseboard and radiators
that are heated evenly. - Precise soft Comfort in all areas of the building.
34
35We believe Exquisite Heat is the most precise
technology for reducing energy use, while
improving occupant comfort in homes and buildings
35
36Thermostat activity is the accurate means for
detecting heat loss and comfort needs.Precise
adjustment of hot air, steam or hot water supply
provides ideal comfort for all heating systems.
December 20, 2020
36
37Outdoor Reset Control
- Most Apt. buildings have some kind of outdoor
reset - Inaccurate weather, location, adjustment,
- No measure of indoor comfort.
- Most are misaligned with the building.
- Difficult to regulate.
- Poorly installed.
38Outdoor reset control
- Time lag from temp change to interior heat loss
- Sensor is subject to wet, wind, placement.
- Fixed curve assumption unrelated to building.
- Buildings react to a combination of heat loss
factors sunlight, wind, windows, insulation,
structure, occupancy thermostat setting. - Over and Under heating.
38
3939
40Exqheat Indoor Reste control
- Comfort based room indoor sensor
- Adjustable from central indoor thermostat.
- Takes the indoor data and interprets it in to
- High limit temperature for hot water boilers
- Burner fire time for steam boilers.
- Takes all environmental effects into immediate
consideration at the thermostat, and adjusts
heating supply to all rooms evenly.
41All Heating Systems
- Hydronic Radiant, Decentralized Steam
- Hot Air Systems, Humidification,
- Refrigeration, Steam Zone Valves,
- Steam to Hydronic Heat Exchangers, Geo-Thermal
Systems, Solar Hydronic Hybrid Heat, - Fresh Air IAQ, Process Control, Navigation,
41
42Thank you !!
- Exquisite Heat reg. trademark
- www.Exqheat.com
- 914-588-4791
- Rev 10-09-09
US Patent 6,402,043 10/18/01
42
4343
4444
45How Does It Work?
- Would you like to go into the technical side of
all this???
45
46Assumption 1
- Increased circulation delivers even comfort.
46
47Assumption 2.
- The closer the supply temperature is to the room
temperature, the more fuel efficient the system.
47
4848
4949
50Thermostat
- The thermostat takes all heat loss and heat gain
into consideration. - The customer can adjust thermostat for personal
comfort. - Thermostat activity can be used to adjust
boiler, HVAC output to satisfy the space with
ideal circulation. - The thermostat and energy source interact for
comfort and efficiency.
50
51Constant
- Ideal Thermostat Demand Ratio gives us a constant
for comparison and adjustment.
51
52Actual Thermostat Demand Ratio
- The actual proportion of time a thermostat
calls for comfortable heat in a given period of
time. (60 minutes) - ADR
52
5353
54Actual Demand Ratio
- Control takes thermostat on/off status reading
every second. - 60 samples/minute x 60minutes
- 3600 samples per hour.
- If thermostat is on for 2520 times/3600 samples,
the actual demand ratio - 2520/3600 .70 70
54
55What information do we need?
- Previous hour adjusted High Limit Temperature
150 degrees F - Actual Demand Ratio.
- Period of analysis 60 minutes (5-90 min)
55
56Temperature change factor
- Ideal demand ratio .70
- Actual demand ratio .75
- ((ADR-IDR) x10) TCF
- ratio difference .75 - .70 .05
- Temperature Change Factor .05 x 10 .5
- Temperature change factor .5
57Temperature Change Increment
- Temp change increment is an arbitrary factor we
use to determine the degree of response we want
to make in the adjustment with the temperature
change factor. - 1 F x .5 .5 F
- 2 F x .5 1 F
- 3 F x .5 1.5 F
57
58New High Limit Temp calculation
- Current High Temp Limit 150 F
- ((.75 - .70) x 10) .5 x 3 F 1.5F
- 150 deg F 1.5F 151.5 F
- New High Temp Limit (Higher)
58
59Limit Settings
- 150 F 1.5F New High Temp Limit (Higher)
151.5 F - Differential of 10 F
- High Limit 151.5F
- Low limit of 141.5 F
59
60Temperature change factor -
Ideal demand ratio .70 Actual Demand ratio .55
- Temp. Change factor ((.55 - .70) x10) -1.5
- Temp Change increment 3 degrees F
- Current High Temp Limit HT 150 degrees F
- ((.55 - .70) x 10)) -1.5 x 3 degrees F -4.5F
- 150F 4.5F New High Temp Limit
- (Lower)145.5 degrees F
61All Variables are changeable
- Ideal ratio .5-.8
- Incremental temp change values (1-5F)
- Sample and cycle times 5-120 min
- Absolute High and Low limits for alarms and
reset 100, 120, 130 160, 190, 200 - Initial start up High Temp set 140 F-190F
- Temperature Differential 1-20 degrees
- Low limit High Temp limit Temp. Differential
6262
63Minute to Minute Comfort
- Between analysis within the hour, the thermostat
can increase the call for heat/cool, by running
more or less than the Ideal Demand ratio of 60 - If chillier, the thermostat can run up to 100.
- If warmer, the thermostat runs less than 70.
- The thermostat always responds to the call.
- We use TT information for analysis.
63
6464
65What has been done
- Changed the philosophy of boiler control.
- The new goal is to give heat to satisfy a fixed
Ideal Thermostat Demand ratio. - We adjust the boiler output to meet that Ideal
demand at the thermostat. - We provide a more comfortable and more efficient
method of heating interior space.
65
66A word about savings.
- Every building has a different relationship with
its heating plant. - Some waste a lot. Most waste a lot.
- Most have comfort problems.
- Savings on fuels can range from 5-30
- Exquisite Heat will run it more comfortably and
efficiently for sure.
66
67Domestic Hot Water
- A Second thermistor is provided to monitor
Domestic Hot Water. If the Thermostat does not
call for heat for one hour the second thermistor
is used to satisfy domestic hot water limit
temperatures. ( 120F-150F)
67
68Multi Zone Satisfaction
- Most cases are satisfied by attaching analysis
zone to average zone in system. The rest of the
zones will float with Thermostat call activity.
68
6969
7070
71Simple Attachment
- Two wire Thermostat parallel connection input.
- Attach thermistor to supply output.
- Connect low voltage control relay in series.
- Attach 24 Vlt Power from existing source.
- Program system variables.
- Revisit until satisfied with installation
settings.
71
72Steam Control
- Steam boilers can be made more precise with
Exquisite Heat burner cycle time Control. - Reduce overshoot in steam delivery.
- Temper supply to thermostat demand.
- Reduce discomfort and waste.
- Shut those open windows.
- Reduce complaints of discomfort.
72
7373
74Shut Down
- In the event of a control shut down
- Power failure
- Computer switches disconnect control relay on
to return HVAC to in series factory low voltage
control.
75Alarms
- Normally open or closed alarm relay is activated
upon shut down, or safety settings. - Trigger local alarm, communicator, internet
server or security system. - Alarm central or direct dialer to owner and/or
contractor. - Additional flood, heat, smoke detection available.
76(No Transcript)
77Cash Flow
- Day after day.
- Year after year. It more than pays for itself.
7815 fuel savings/4yr payback/800
78
79Improved Comfort
- The feature
- customers notice first
8080
81Reduction of chimney waste
- Air Pollutants CO2, NO, etc.
- Particulates heat
81
82Unconditional Guarantee
- Exquisite Heat will exchange failed equipment
for five years. Lease and rental replacement
will occur for the term of the agreement. - Equipment will be removed and full refund. (
Do it Right!!! ) - The goal is to refine comfort and efficiency.
82
83Manufacturers
- Now have the opportunity to develop efficient
boilers and deliver system efficiently to the
final comfort recipient.
83
84Heating Contractors
- have the opportunity to deliver unprecedented
comfort and efficiency to their customers. - Exquisite Heat offers the best in class for
controlling existing buildings without the need
for major renovation.
84
85Factory Settings
- Each control comes from the factory set up to
attach and run. - Advanced programming is available for those who
wish to adjust variables. - No computer knowledge is needed to install the
control.
85
86December 20, 2020
86
87Thank you !!