Study on the Performance of Ventiflex Ducting and Couplings PowerPoint PPT Presentation

presentation player overlay
1 / 15
About This Presentation
Transcript and Presenter's Notes

Title: Study on the Performance of Ventiflex Ducting and Couplings


1
Study on the Performance of Ventiflex Ducting and
Couplings
  • Göran Hansson and Lars Anisdahl (Protan)

2
Ventiflex for mine and tunnel ventilation on a
global scale
3
Objective with this study
  • To assess the friction loss factors, the shock
    loss factors and the leakage factors for
    Ventiflex ducting with couplings.
  • These factors are important design parameters for
    the whole ventilation system.
  • Correct assessment of these factors provides a
    better design basis for Ventiflex systems, and
    makes it easier to optimise both investment and
    operating costs for the whole ventilation system.

4
The Ventiflex coupling system
5
Couplings
Steel-ring
Velcro
Zip
6
Design parameters
  • Friction factor
  • This tells the magnitude of the friction loss
    between the flowing air and the inner duct wall.
  • Shock loss factor
  • This tells the magnitude of the sudden pressure
    drops at obstacles (bends, tees, contractions,
    diffusers, joints, etc.).
  • Leakage factor, f
  • This factor is the average area of leakages given
    in mm2 (in2) per m2 (ft2) duct wall.
  • The total pressure at the duct inlet and the air
    flow rate at the duct outlet are governed by
    these three factors.

7
The SIA norm (Swiss standard)
8
Experimental programme
  • Three straight ducts of length 400 m and diameter
    1200 mm.
  • One with no couplings.
  • One with Velcro couplings every 10 m.
  • One with Zip couplings every 10 m.
  • One duct length of 2720 m and diameter 1700 mm.
  • Steel-ring couplings for every 10 m.
  • Air flow rates and pressures were measured along
    the ducts.
  • Based on the measurements, friction factors,
    shock loss factors and leakage factors were
    calculated.

9
From the experiments
10
Results Friction factor (K-factor)
11
Results Shock loss factor
For comparison Shock loss factor for a bend or a
tee 0,2 1,0
12
Results Leakage factor (mm2/m2)
No leakages
13
Results
14
Duct design using VentiflexCalc
Friction factor input
Leakage factor input
Shock loss factor input
15
Summary
  • Friction factors, shock loss factors and leakage
    factors have been assessed for Ventiflex ducts
    comprising velcro, zip and steel-ring couplings.
  • The results confirm that the leakage is zero for
    correctly installed couplings in a well aligned
    duct, but it does not mean that there will be no
    leakages from any installed coupling.
  • The Ventiflex system easily complies to SIA class
    S, or better.
  • However, a Ventiflex system should always be
    designed according to the particular application.