Title: MODULAR DATA CENTER


1
MODULAR DATA CENTER
PUE 1.07
2
MODULAR DATA CENTER
Container Park with - EATON power infrastructure
(UPS electrical infrastructure) - AST
Containers and Modular Natural Free Cooling MNFC
technology
3
MODULAR DATA CENTER
About THOR
  • - Based in Reyjkavik (Iceland).
  • - Hosting and Cloud Storage provider
  • 100 Carbon Neutral Data Center (all power
    generation is geothermal and hydro).
  • Maximum resiliency Tier 3
  • 18 x IT Container 40 with 280 racks in total
    and 4MW IT power. Natural Free Cooling.
  • Ultra low TCO due to low PUE and very cheap
    kw/h ( 0,03), about 70 less than in continental
    Europe.
  • Redundant Fiber Optic link to continental Europe
    with 50ms latency.

4
Electrical consumption in Data Centers
Two areas to focus on savings
Energy costs grow between 10 to 25 annually
5
MODULAR DATA CENTER
  • The challenge of Free Cooling in Iceland
  • Ideal location for Free Cooling temp year round
    does not exceeds 24ºC.
  • However, very high content of sulphur in the
    ambience.
  • A study by IBM showed that direct air free
    cooling (even with EPA filter) damaged
    processors after 6 months.
  • Direct air intake in Iceland is not possible.
  • An alternative technology must be used.

6
MODULAR DATA CENTER
  • Natural Free Cooling not only in Iceland
  • MNFC can provide Free Cooling up to 24ºC.
  • 89 of hours in Madrid are below 24ºC (we can
    achieve PUE 1,11).
  • With std. Chiller Free Cooling (CW 7ºC/12ºC) we
    can only use 25 of the year-hours!
  • Savings in a 500KW IT load Data Center can be of
    up to 250k / year!
  • ROI is around 18 months!
  • The improvement is extraordinary even in
    non-nordic locations!

7
MODULAR DATA CENTER
Power room
8
MNFC System Main Advantatges
MODULAR DATA CENTER
  • No Cross Contamination
  • 80 efficiency
  • Low pressure drop
  • 100 Sensible cooling transfer
  • No moving parts
  • No energy required
  • No single points of failure
  • No Maintenance

Patent P201030478
9
Technology
MODULAR DATA CENTER
10
Cooling Operation
MODULAR DATA CENTER
11
Functioning Example
MODULAR DATA CENTER
12
Natural Free Cooling Operational Range
MODULAR DATA CENTER
  • External temperatures lt 19ºC ? temperature at the
    cold corridor is 24 ºC or lower with no support
    of traditional cooling
  • 19 ºC lt External temperatures lt 24 ºC ?
    temperature at the cold corridor is 24 ºC or
    lower WITH evaporative cooling
  • External temperatures gt 24ºC ? chilled water
    cooling

13
Hours Available
MODULAR DATA CENTER
14
PUE and Cooling Efficiency
MODULAR DATA CENTER
15
MODULAR DATA CENTER
  • PHASE 1 deployed
  • IT container
  • 17 racks _at_ 14kW/rack
  • NATURAL FREE COOLING container
  • SERVICES room
  • EATON UPS, model 9390M, 2 x 160 kVA (2n)
  • 2 x Genset 225 kVA (n1)
  • ATS, Main Switch Boards

16
SERVICES room
MODULAR DATA CENTER
  • EATON 9390M UPS Main advantages
  • Scalability and modular for future growth
  • Turn key solution, service and maintenance
  • ECONOMODE internal by-pass and 2 power loss

17
MODULAR DATA CENTER
18
MODULAR DATA CENTER
Scalable power infrastructure
PHASE 2
PHASE 1
19
MODULAR DATA CENTER
20
(No Transcript)
21
(No Transcript)
22
MODULAR DATA CENTER
Not just a sketch , but a reality.
23
MODULAR DATA CENTER
24
MODULAR DATA CENTER
25
MODULAR DATA CENTER
PMDC 40 Standard Servers Container configuration
26
PMDC 40 Compact Container configuration
MODULAR DATA CENTER
27
MODULAR DATA CENTER
Thank you Pablo Fernandez CentralEast Europe
Sales Director www.ast-global.com