Connecting to the Grid: Active Network Management on Orkney - PowerPoint PPT Presentation

1 / 7
About This Presentation
Title:

Connecting to the Grid: Active Network Management on Orkney

Description:

CIRED Paper 0421. Connecting to the Grid: Active Network Management ... and remote lockout/enable), PLC capability, interoperability and communications solution ... – PowerPoint PPT presentation

Number of Views:41
Avg rating:3.0/5.0
Slides: 8
Provided by: scott616
Category:

less

Transcript and Presenter's Notes

Title: Connecting to the Grid: Active Network Management on Orkney


1
Connecting to the Grid Active Network Management
on Orkney
  • Graham Ault and Robert Currie
  • Advanced Electrical Systems Research Group
  • University of Strathclyde

2
Orkney Electrical System
  • 6 miles off North-Scotland
  • 11,500 customers
  • Min/Max demand 8/31MW
  • 33kV submarine cables 2 x 20MW import/export
  • Existing generation a mix of wind, wave and gas.
  • Firm Generation (FG) allocated
  • Non-Firm Generation (NFG) allocated
  • Generation fully committed
  • Reactive compensation equipment installed
    (including DVAR)

3
Orkney Active Network Management Scheme
  • Reactive compensation equipment solves almost all
    voltage problems
  • Each zone has a thermal limitation on generation
    output at any given time
  • Whole Orkney system has a further thermal limit
    on generation output
  • Real time control of wind and marine generating
    units based on measurements and control logic.

4
Economics of ANM on Orkney
5
ANM Trial November 2006
  • Closed loop control trial to test communications
    and control logic on PLCs
  • PLCs operational at Scorradale and existing Wind
    Farm
  • Trial outcomes
  • Integration of ANM scheme with WT/WF controllers
  • Verification of logic control (output regulation,
    loss of comms., local and remote lockout/enable),
    PLC capability, interoperability and
    communications solution
  • Measurement of communications and control system
    and generation response times
  • Control codes for full ANM scheme in development

6
Orkney ANM Trial - Results
  • Output of wind farm regulated below issued
    set-point
  • Results of trial feeding directly into the design
    of the full ANM scheme
  • Response of Wind Farm observed
  • Closed-loop control achieved
  • Communications and control logic proven

7
Questions?
Does this demonstration encapsulate the sort of
active management scheme envisaged for future
distribution networks?What are the major
barriers to further exploitation of such schemes?