Stability Issues in Entergy System Entergy Transmission Planning Summit New Orleans, LA July 10, 200 - PowerPoint PPT Presentation

1 / 31
About This Presentation
Title:

Stability Issues in Entergy System Entergy Transmission Planning Summit New Orleans, LA July 10, 200

Description:

PSS tuning mandatory in WOTAB and Southeast Louisiana ... New technologies (FACTS devices, e.g., SVC, STATCOM, D-SMES, UPFC, etc.) may be required. ... – PowerPoint PPT presentation

Number of Views:151
Avg rating:3.0/5.0
Slides: 32
Provided by: sman150
Category:

less

Transcript and Presenter's Notes

Title: Stability Issues in Entergy System Entergy Transmission Planning Summit New Orleans, LA July 10, 200


1
Stability Issues in Entergy System Entergy
Transmission Planning Summit New Orleans, LA
July 10, 2003
2
Classification of Power System Stability
  • Transient/Angle Stability
  • Voltage Stability
  • Small Signal/Oscillatory Stability

3
Static Voltage Stability Criteria
Limits Corresponding to Voltage Decline Criteria
Limits Corresponding to 5 margin from Nose Point
Nose Point ( point before voltage collapse)
4
Dynamic Voltage Stability Criteria
5
Damping Criteria 3
6
Areas of Stability Concern in 2002
I. Joint Stability Study between Entergy,
Southern, and TVA
North Arkansas
Northwest Quadrant
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
II. McKnight-Franklin Flow Limits
III. Stability problem in WOTAB Area
7
I. Joint Stability Study between Entergy,
Southern, and TVA
8
Results/Northwest Quadrant
  • New generation added without PSS severely
    deteriorated system damping.
  • The most limiting contingency from a damping
    standpoint was the Miller - Bellefonte 500 kV
    line.
  • The most limiting contingency from a voltage
    standpoint was the Farley - Mitchell 500 kV line.
  • With PSS on new generating units, the export
    limits were found to be 3,850 MW.
  • Current Status Problem doesnt exist any more
    due to cancellation of some IPP generation.

9
II. McKnight-Franklin Flow Limits
10
Problem Area
North Arkansas
Mississippi
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
11
Results/Southeast Louisiana
  • Angle Stability limits found to be slightly lower
    than voltage stability limits
  • Rating of the McKnight-Franklin 500kV line
    limited to 2,070 MVA due to unacceptable damping
  • With Webre-Richard out of service, the flow limit
    is 1,958 MVA
  • With Daniel-McKnight out of service, the flow
    limit is 1,522 MVA
  • No transient voltage security violations observed

12
III. Stability Problem in Entergys WOTAB
area
13
Problem Area
North Arkansas
Mississippi
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
14
Results/WOTAB
  • The limiting contingency is the Mt. Olive -
    Hartburg 500 kV line.
  • Without PSS, the limit is 2,700 MW based on
    damping criteria ( lt 3 damping).
  • With PSS on new generating units, the export
    limit was found to be 3300 MW based on voltage
    collapse criteria.
  • Limit based on voltage decline criteria (0.92 pu)
    is 2,100 MW.
  • Major transmission improvements may be required
    to increase export limits.

15
New Areas of Stability Concern
North Arkansas
Mississippi
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
V. Western Region Voltage Stability
IV. Amite South Stability
16
IV. Stability Problem in Entergys Amite
South Area
17
Problem Area
North Arkansas
Mississippi
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
Amite South Region
18
Background
  • Major Load Center
  • Large Concentration of Generation
  • Expected 2003 conditions
  • 6,280 MW of load (including CLECO LaGEN loads)
  • 8,400 MW of native and new generation

19
Background
  • 230 kV loop out of Waterford is critical
  • Approximately 3,100 MW generation in the loop
  • System stable for primary clearing faults
  • Additional generation can lead to instability for
    stuck breaker faults

20
Results
  • Under stuck breaker faults
  • Fault clearing time very important for the
    stability of the region
  • Units in Amite south region and close vicinity
    can separate from the rest of the system
  • Can lead to lines tripping

21
System Separation
22
Solutions Proposed
  • Faster fault clearing devices (relays, breakers)
  • Remedial action scheme to trip certain units to
    protect against stuck breaker fault conditions
  • Power system stabilizers on the new units
  • IPO breakers

23
V. Voltage Stability Problem in Entergys Western
Region
24
Areas of Stability Concern
North Arkansas
Mississippi
West of the Atchafalaya Basin (WOTAB)
Southeast Louisiana
Western Region
25
Background
  • Western Region load growth 5.1
  • Generation sources Two Lewis Creek units (226MW
    230MW, 150 MVAR each)
  • With one Lewis Creek unit out of service, certain
    line outages can cause low voltages leading to
    potential voltage collapse.
  • Critical tie lines are Grimes Crockett 345 kV
    and China Jacinto 230 kV.

26
Background
  • Currently, Under Voltage Load Shedding (UVLS)
    scheme is in place.
  • Voltage at critical buses below 0.92 pu
  • Loss of both Lewis Creek generators
  • Lewis Creek units go into over excitation mode
  • Series Compensation on China Jacinto 230 kV
    line
  • Static capacitors installed 770 MVAR
  • Two D-SMES units (8 MVA each) installed at New
    Caney and Metro in 2001

27
Power Voltage (P-V) CurveLoss of one Lewis
Creek unit and Grimes Crockett 345 kV line
28
Voltage Profile at Critical Buses
29
Results for 2005 Summer Peak
  • Voltage Instability
  • Slow voltage recovery
  • Several motor loads at risk
  • Depressed voltages can lead to UVLS operation

30
Possible Solutions
  • Static Devices MS Shunt Cap Banks
  • Series Compensation
  • New transmission facilities (for details, see
    EGSI-TXs area planning presentation)
  • Dynamic VAR support device (e.g., SVC, STATCOM,
    D-SMES)

31
System Stability Summary
  • PSS installation mandatory for all new generation
    locating on the Entergy system
  • PSS tuning mandatory in WOTAB and Southeast
    Louisiana
  • Traditional methods are needed to fix stability
    problems (alleviate thermal constraints,
    additional static reactive power support devices,
    series compensation)
  • New technologies (FACTS devices, e.g., SVC,
    STATCOM, D-SMES, UPFC, etc.) may be required.
Write a Comment
User Comments (0)
About PowerShow.com