Title: ABB CM-UFD Solar Relay & ComAp MainsPro Solar Protection Relay | MainsPro


1
ABB CM-UFD.M33 ComAp MainsProSolar Protection
Relay
  • BCJ Controls

2
ABB CM-UFD.M33
  • The ABB CM-UFD.M33 is a multifunctioning grid
    feeding monitoring relay. It trips the section
    switch that is connected between the distributed
    generation and the public grid allowing the
    distributed generation to disconnect in case of
    problems (e.g. unstable grid), faults, or grid
    maintenance. The device provides different
    monitoring services to detect 10-minutes average
    overvoltage, real time over- and under-voltage as
    well as over- and under-frequency. Additionally,
    monitoring of vector shift and ROCOF (rate of
    change of frequency) can be configured to trip
    the generation in a case of loss of mains.

3
ABB CM-UFD.M33 Characteristics
  • Monitoring of voltage and frequency in
    single-phase and three-phase mains (2-wire,
    3-wire or 4-wire AC systems)
  • Over- and under-voltage, 10-minutes average
    value as well as over- and under-frequency
    monitoring
  • Two-level threshold settings for
    over-/under-voltage and over-/under-frequency
  • ROCOF monitoring and vector shift detection are
    configurable
  • Interrupted neutral detection
  • Default settings in accordance with Great
    Britain Engineering Recommendations G59/3 and
    G83/2

4
ABB CM-UFD.M33 Characteristics
  • True RMS measuring principle
  • All threshold values and tripping delays are
    adjustable
  • Error memory for up to 99 entries (incl. cause
    of error, measured value, relative timestamp)
  • Password setting protection
  • 3 control inputs (e.g. for feedback signal,
    remote trip)
  • 3 c/o (SPDT) contacts
  • Multiline, backlit LCD display

5
ABB CM-UFD.M33 Application
  • The ABB CM-UFD.M33 is a grid feeding monitoring
    relay that monitors the voltage and the frequency
    of the public low or medium voltage grid.
    Whenever measured values are not within the range
    of adjusted threshold values, the ABB CM-UFD.M33
    causes the section switch to trip (consisting of
    1 or 2 switching devices according to the
    applicable standard). This tripping disconnects
    the power generation of systems such as
    photovoltaic systems, wind turbines, and
    block-type thermal power stations from the grid.
    The fault is indicated by a LED and the
    corresponding plain text failure message is
    displayed.

6
ComAp MainsPro 
  • The ComAp MainsPro solar protection relay is used
    for grid-tie applications, and provides
    anti-islanding protection as required by
    Distribution Network Service Providers for solar
    over 30 kW. It can be used with any embedded
    generator systems such as gen sets,
    co-generation, or renewable energy sources
    including photovoltaic plants or wind turbines.
    The ComAp MainsPro grants adjustable voltage,
    frequency, and loss of mains functions to
    safeguard the distribution network and the
    generators.
  • With ComAp MainsPro, no special knowledge is
    needed for the installation process and no
    additional units are required. This makes it an
    optimal solution for both untrained personnel and
    professionals. The unit is designed to comply
    completely with Utilities connection
    requirements and statutory codes, offering a high
    level of protection and safety when working in
    parallel to the mains.

7
ComAp MainsPro Product Features
  • Flexible supply voltage and measurement range
  • Suited for standard DIN rail installation or
    door-mount
  • User friendly interface with easy setting (no
    software tools needed)
  • Simple wiring with removable connectors
  • Remote binary communication
  • Compact design for installation in restricted
    spaces

8
ComAp MainsPro Product Features
  • Lost of Mains function and history track
    function (Last 5 events history log)
  • Integrated mechanical lock to secure your
    settings
  • Breaker failure protection
  • Watchdog relay output
  • Increased resolution of frequency protection
    settings
  • Resistance to frequency jumping

9
Technical Information
  • True RMS measurements for more accurate,
    reliable evaluation of failures
  • Vector Shift and Rate of change of
    frequency protections are available in a single
    unit to allow for the best fit for each site
  • Symmetrical components allow for better
    detection of voltage asymmetry failures
  • Two stage settings of voltage and frequency
    safeguards cover short and long term disturbances
    with fitting priority
  • Free assignment of five relay outputs allows for
    a large range of signaling and trip methods
  • Four binary switches to remotely alter unit
    operation

10
Technical Information
  • Adjustable time delay of Automatic fault
    reset to avoid need for personnel on-site
  • Universal power supply of 8 40 VDC, 85 265
    VAC, and 110 370 VDC
  • Unit is independent on application due to the
    optional voltage range of 120/230/400 VAC with
    over-range to 156/290/520 VAC
  • Supports three-phase and one-phase applications
  • Last trip is recorded to provide evidence of
    trip cause

11
At BCJ Controls we produce Secondary Protection
Switchboards with solar protection relays for
Commercial Solar over 30kW grid connections. BCJ
Controls - commercial solar network protection
unit - switchboard manufacturing including
protection relay anti-islanding and zero export
devices. BCJ Controls is a solar technology
company set up by ex-utility industrial sparkies.