CFBC BOILER DRIVE INTERLOCK - PowerPoint PPT Presentation

About This Presentation
Title:

CFBC BOILER DRIVE INTERLOCK

Description:

CFBC BOILER DRIVE START INTERLOCK,STOP INTERLOCK – PowerPoint PPT presentation

Number of Views:575

less

Transcript and Presenter's Notes

Title: CFBC BOILER DRIVE INTERLOCK


1
IR-CFBC BOILERDRIVE START/STOP LOGIC
  • ASHVANI SHUKLA
  • RELIANCE
  • CI

2
MAIN EQUIPMENT
  • I.D. FAN
  • P.A. FAN
  • S.A. FAN
  • COAL FEEDER
  • GRAVIMETRIC COAL FEEDER
  • BED MATERIAL RAV
  • LIME STONE RAV
  • HP DOSING PUMP
  • MDC RAV

3
I D FAN
  •  
  • START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • ID FAN INLET DAMPER IN CLOSE POSITION
  • ID FAN BEARING TEMPERATURE NORMAL
  • ID FAN MOTOR BEARING TEMPERATURE NORMAL
  • FURNACE PRESSURE NORMAL
  • FLUE GAS PATH SHOULD BE THROUGH

4
I D FAN
  • TRIP INTERLOCK
  • ID FAN BEARING TEMPERATURE VERY HIGH
  • ID FAN MOTOR BEARING TEMPERATURE VERY HIGH
  • ID FAN DE VIBRATION X-AXIS HIHI
  • ID FAN DE VIBRATION Y-AXIS HIHI
  • ID FAN NDE DE VIBRATION X-AXIS HIHI
  • ID FAN NDE VIBRATION Y-AXIS HIHI
  • ID FAN MOTOR DE VIBRATION X-AXIS HIHI
  • ID FAN MOTOR DE VIBRATION Y-AXIS HIHI
  • ID FAN MOTOR NDE DE VIBRATION X-AXIS HIHI
  • ID FAN MOTOR NDE VIBRATION Y-AXIS HIHI
  • FURNACE PRESSURE VERY LOW
  • OUT OF FIVE THREE TRANSFORMER TRIPPED FIELD-1
  • OUT OF FIVE THREE TRANSFORMER TRIPPED FIELD-

5
PA FAN
  • PA FAN START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • PA FAN INLET DAMPER IN CLOSE POSITION
  • PA FAN BEARING TEMPERATURE NORMAL
  • PA FAN MOTOR BEARING TEMPERATURE NORMAL
  • FURNACE PRESSURE NORMAL
  • WIND BOX PURGE COMPLETED OR PA FAN RUNING OR BED
    TEMPERATURElt200
  • ID FAN RUNNING
  • DRUM LEVEL NORMAL
  • PA FAN PRESSURE AFTER APH NORMAL

6
PA FAN
  • TRIP INTERLOCK
  • PA FAN BEARING TEMPERATURE VERY HIGH
  • PA FAN MOTOR BEARING TEMPERATURE VERY HIGH
  • PA FAN DE VIBRATION X-AXIS HIHI
  • PA FAN DE VIBRATION Y-AXIS HIHI
  • PA FAN NDE DE VIBRATION X-AXIS HIHI
  • PA FAN NDE VIBRATION Y-AXIS HIHI
  • PA FAN MOTOR DE VIBRATION X-AXIS HIHI
  • PA FAN MOTOR DE VIBRATION Y-AXIS HIHI
  • PA FAN MOTOR NDE DE VIBRATION X-AXIS HIHI
  • PA FAN MOTOR NDE VIBRATION Y-AXIS HIHI
  • FURNACE PRESSURE VERY HIGH
  • ID FAN NOT RUNNING
  • DRUM LEVEL VERY LOW
  • PA FAN PRESSURE AFTER APH VERY HIGH
  • EMERGENCY VENT VALVE OPEN

7
SA FAN
  • START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • SA FAN INLET DAMPER IN CLOSE POSITION
  • SA FAN BEARING TEMPERATURE NORMAL
  • SA FAN MOTOR BEARING TEMPERATURE NORMAL
  • FURNACE PRESSURE NORMAL
  • PA FAN RUNNING
  • SA FAN PRESSURE AFTER APH NORMAL

8
SA FAN
  • TRIP INTERLOCK
  • SA FAN BEARING TEMPERATURE VERY HIGH
  • SA FAN MOTOR BEARING TEMPERATURE VERY HIGH
  • SA FAN DE VIBRATION X-AXIS HIHI
  • SA FAN DE VIBRATION Y-AXIS HIHI
  • SA FAN NDE DE VIBRATION X-AXIS HIHI
  • SA FAN NDE VIBRATION Y-AXIS HIHI
  • SA FAN MOTOR DE VIBRATION X-AXIS HIHI
  • SA FAN MOTOR DE VIBRATION Y-AXIS HIHI
  • SA FAN MOTOR NDE DE VIBRATION X-AXIS HIHI
  • SA FAN MOTOR NDE VIBRATION Y-AXIS HIHI
  • FURNACE PRESSURE VERY HIGH
  • PA FAN NOT RUNNING
  • DRUM LEVEL VERY LOW
  • SA FAN PRESSURE AFTER APH VERY HIGH

9
DRAG CHAIN FEEDER
  •  
  • START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • SILO LEVEL NORMAL
  • ZERO SPEED SWITCH ACTIVATED
  • BED TEMPERATURE gt MINIMUM IGNITION TEMPERATURE OF
    COAL
  • MFT NOT ACTIVATED
  • BED TEMPERATURE gt 760 Deg C OR FURNACE PURGE
    COMPLETED
  • DCF DISCHARGE VALVE OPEN
  • SEAL AIR PRESSURE AT DCF INLET NORMAL
  • SA FAN RUNNING

10
DRAG CHAIN FEEDER
  • TRIP INTERLOCK
  • U-BEAM TEMPERATURE VERY HIGH
  • BED TEMPERATURE VERY HIGH
  • BED TEMPERATURE VERY LOW
  • SEAL AIR PRESSURE VERY LOW
  • SILO LEVEL VERY LOW
  • MFT ACTIVATED
  • DCF DISCHARGE VALVE OPEN

11
GRAVIMATRIC FEEDER
  • START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • SILO LEVEL NORMAL
  • ZERO SPEED SWITCH ACTIVATED
  • BED TEMPERATURE gt MINIMUM IGNITION TEMPERATURE OF
    COAL
  • MFT NOT ACTIVATED
  • BED TEMPERATURE gt 760 Deg C OR FURNACE PURGE
    COMPLETED
  • GMF SUCTION SLIDE GATE VALVE OPEN
  • SEAL AIR PRESSURE AT GMF INLET NORMAL
  • SA FAN RUNNIN

12
GRAVIMATRIC FEEDER
  • TRIP INTERLOCK
  • U-BEAM TEMPERATURE VERY HIGH
  • BED TEMPERATURE VERY HIGH
  • BED TEMPERATURE VERY LOW
  • SEAL AIR PRESSURE VERY LOW
  • SILO LEVEL VERY LOW
  • MFT ACTIVATED
  • GMF SUCTION SLIDE GATE VALVE OPEN

13
LIME STONE RAV
  • START PERMISSIVE 
  • DRIVE AVAILABLE FOR DCS CONTROL
  • LIME STONE BUNKER LEVEL NORMAL DCF FAN RUNNING
  •  
  • TRIP INTERLOCK
  • LIME STONE BUNKER LEVEL VERY LOW

14
BED MATERIAL RAV
  •  
  • START PERMISSIV 
  • DRIVE AVAILABLE FOR DCS CONTROL
  • LIME STONE BUNKER LEVEL NORMAL
  •  
  • TRIP INTERLOCK
  • LIME STONE BUNKER LEVEL VERY LOW

15
MDC RAV
  • START PERMISSIVE
  • DRIVE AVAILABLE FOR DCS CONTROL
  • TRIP INTERLOCK
  • MDC HOPPER LEVEL VERY LOW
Write a Comment
User Comments (0)
About PowerShow.com