Title: Energy Savings Impacts of the Advanced Energy Design Guide: Small Office Buildings
1Energy Savings Impacts of the Advanced Energy
Design Guide Small Office Buildings
- Bing Liu, P.E.
- Research Engineer
- Pacific Northwest National Laboratory
- Tel (509) 375-3710
- Bing.liu_at_pnl.gov
2Energy Use Simulation Approach
- Scoping Study
- Baseline building Standard 90.1-1999
- Advanced building Off-the-Shelf technology
- Two Models 5,000 sf and 20,000 sf office
buildings - Use eQuest to test run in four climate locations
Miami, Phoenix, Seattle and Duluth - Full Study
- 15 representative locations in 8 DOE Climate
Zones - Use DOE-2.2 directly to make 60 parametric runs
for full study
35,000 ft² Office Prototype
- Square floor plan
- Single story
- Frame construction
- 20 window-to-wall ratio
- Single tenant
420,000 ft² Office Prototype
- Square floor plan
- 2-story
- Masonry construction
- 30 window-to-wall ratio
- 3 tenants
5What is in the Baseline Building?
- Comply with Standard 90.1-1999
- Insulation requirements for roofs, walls, floors
and slabs - U-Value and SHGC for window glazing
- U-Value for doors
- Interior lighting power density
- Mechanical equipment efficiency
- Economizer requirement
- And more
6What is in the Baseline Building?
- When not specified by 90.1-1999
- Room Thermostat
- Setpoint 75F cooling 70F heating
- Setback/Setup 80F cooling 65F heating
- Office Equipment Plug Load
- Schedules
- Energy Policy Act Standard analysis
- Recent research study and peer review comments
- Fan Static Pressure
7Plug Load Schedule - Weekday20,000 sf Office
Building
8(No Transcript)
9What is in the Advanced Building?
- Envelope
- Cool roofs
- Better insulations
- High performance windows and doors
- Overhangs for windows except facing north
- Interior Lighting
- Reduced installed lighting power density
- Daylighting harvest for WWR 25 or higher
- Daylighting dimming control on south and north
perimeter zones - Occupancy Sensor
10What is in the Advanced Building?
- Mechanical System
- Higher efficiency unitary equipment in some
climate zones - Motorized outside air damper control
- Demand Control Ventilation (DCV)
- Lower duct friction rate 0.08 in/100 ft vs. 0.10
in/100 ft of standard practice - Service Water Heater
- Higher thermal efficiency for gas-fired storage
water heater or - Gas-fired instantaneous water heater
11Energy Savings of Advanced vs. Base
Building (Without Plug Load)
12Energy Savings of Advanced vs. Base
Building (Including Plug Load)
13Energy Use Index 5,000 sf Office Building
14Energy Use Index 20,000 sf Office Building
15Comparison of Energy Savings 5,000 sf Office
Building
Average Savings of All the Climate Zones 38
49.1
36.4
35.6
16Comparison of Energy Savings 20,000 sf Office
Building
Average Savings of All the Climate Zones 38
43
38
35
17Advanced Simulation Challenges
- Real windows vs. DOE-2 window library
- Window Shading Coefficient Method
- Window Library Method
- Window Layers Method
18Advanced Simulation Challenges
- Occupancy sensor
- DOE-2 doesnt have occupancy sensor module
- Modify the lighting schedule to estimate the
potential energy savings from the occupancy
sensors
19(No Transcript)
20Advanced Simulation Challenges
- Demand ventilation control
- No CO2 sensor module in DOE-2
- Modify the outside air change rate to reflect the
average reduction of the outside intake using CO2
sensor 20
21Advanced Simulation Challenges
- Motorized outside air damper control
- Potentially saving cooling and heating energy
during nights by closing the OA damper when fans
cycle on to maintain space setback temperature - Hourly-based simulation may over-estimate the
energy savings from the motorized outside air
damper in the cold climates
22Questions?
- Bing Liu, P.E.
- Pacific Northwest National Laboratory
- Tel (509) 375-3710
- Bing.liu_at_pnl.gov