Standards and procedures for pressure decay testing laboratories to ensure fire code compliance - PowerPoint PPT Presentation

1 / 44
About This Presentation
Title:

Standards and procedures for pressure decay testing laboratories to ensure fire code compliance

Description:

A lab work area is defined as a space within the lab unit for ... protection systems including: sprinkler, standpipe and hose, fixed water spray and foam water. ... – PowerPoint PPT presentation

Number of Views:749
Avg rating:3.0/5.0
Slides: 45
Provided by: aabc
Category:

less

Transcript and Presenter's Notes

Title: Standards and procedures for pressure decay testing laboratories to ensure fire code compliance


1
Standards and procedures for pressure decay
testing laboratories to ensure fire code
compliance
2
Definition of a laboratory unit
  • A laboratory unit (lab unit) is an enclosed space
    used for experiments and tests
  • A lab unit can include ancillary offices, toilet,
    etc. and contain one or more separate lab work
    areas
  • A lab work area is defined as a space within the
    lab unit for testing, analysis, research or
    similar activities that involve the use of
    chemicals

http//www.scdf.gov.sg
3
Lab unit 1
http//www.scdf.gov.sg
4
Lab unit 2
http//www.scdf.gov.sg
5
Lab unit 3
http//www.scdf.gov.sg
6
Defining lab units
1
2
All 3 lab unit layouts are the same - as defined
by the code.
3
http//www.scdf.gov.sg
7
Basic fire safety requirements for laboratories
  • NFPA 45, 2004

8
Basic fire safety requirements for laboratories
  • NFPA 45, 2004
  • The prevention and control of hazards such as
    fires explosions and exposure to toxic,
    corrosive, and other harmful chemicals.
  • The objectives of this code are
  • Limit injury to the occupants at the point of
    fire origin.
  • Limit injury to emergency response personnel.
  • Limit property loss to a maximum of a single
    Laboratory Unit.
  • States that all new labs must be protected with
    automatic extinguishing systems
  • It is not the objective of this standard to
    address financial losses or business
    interruptions or property loss.

9
Basic fire safety requirements for laboratories
  • NFPA 45, 2004 (cont)
  • Fire compartmentation
  • Fire fighting lobby
  • Automatic fire detection and extinguishing system
  • Caution label
  • Anteroom

10
(No Transcript)
11
Biosafety level laboratories
  • BSL-3, BSL-3 AG and BSL-4

12
Definition of BSL
  • Biosafety Level
  • the level of safety from exposure to
    infectious agents depends on work practices and
    safety equipment and facilities

http//wordnet.princeton.edu
13
Levels of BSL
  • There are 5 levels of BSL
  • BSL-1- exposure only to infectious agents that do
    not ordinarily cause human disease
  • BSL-2 - exposure to infectious agents that can
    cause disease in humans but whose potential for
    transmission is limited
  • BSL-3 - exposure to infectious agents that can be
    transmitted by the respiratory route and which
    can cause serious infection
  • BSL-3AG research involving certain biological
    agents in large animal species
  • BSL 4 - exposure to exotic infectious agents that
    pose a high risk of life-threatening disease and
    can be transmitted as an aerosol and for which
    there is no vaccine or therapy

14
Definition of BSL
  • BSL-3 and BSL-4
  • is defined as any enclosed room or space which
    is designed to comply with the WHO, (World Health
    Organization) and MOHs requirements for storing
    or handling of biological agents or toxins
  • BSL-3 AG
  • involves certain biological agents in large
    animal species

15
Guidelines for safety of BSL-3 BSL-4
  • To stipulate the safety requirements for
    biomedical facilities (Bio-Safety Level 3 and
    above) handling biological agents or toxins
  • Lab units or lab work areas shall be
    continuously maintained at a negative pressure
  • Pressure decay testing
  • Door fan testing

Not covered in NFPA 45
16
Typical BSL-3/4 containment lab
BOX IN A BOX
ANTE ROOMS
http//www.scdf.gov.sg
17
Fire Codes
  • Current resources for laboratories

18
Current resources for codes
  • Standard on Halon 1301 Fire Extinguishing
    Systems, (NFPA 12A), 2004
  • Standard for the Installation of Sprinkler
    Systems, (NFPA 13), 2005
  • Standard for the Inspection, Testing, and
    Maintenance of Water-Based Fire Protection
    Systems, (NFPA 25), 2002
  • Standard on Fire Protection for Laboratories
    Using Chemicals, (NFPA 45), 2004
  • Standard for Fire Doors and Other Opening
    Protectives, (NFPA 80) 2007
  • Installation of Air Conditioning and Ventilating
    Systems, (NFPA 90A),  2002

19
Current resources for codes
  • Standard for Exhaust Systems for Air Conveying of
    Vapors, Gases, Mists, and Non-combustible
    Particulate Solids, (NFPA 91), 2004
  • Standard for Smoke-Control Systems Utilizing
    Barriers and Pressure Differences, (NFPA 92A),
    2006
  • Life Safety Code, (NFPA 101), 2006
  • Standard on Clean Agent Fire Extinguishing
    Systems, (NFPA 2001), 2004
  • Standard System for the Identification of the
    Hazards of Materials for Emergency Response,
    (NFPA 704), 2007
  • The primary source for laboratories is NFPA 45
  • as it was removed from NFPA 101 in 1996.

20
NFPA 45
  • Chapter 1 Administration
  • Chapter 2 Referenced Publications
  • Chapter 3 Definitions
  • Chapter 4 Laboratory Unit Hazard Classifications
  • Chapter 5 Laboratory Unit Design and
    Construction
  • Chapter 6 Fire Protection
  • Chapter 7 Explosion Hazard Protection
  • Chapter 8 Laboratory Ventilating Systems and
    Hood Requirements
  • Chapter 9 Chemical Storage, Handling, and Waste
    Management
  • Chapter 10 Flammable and Combustible Liquids
  • Chapter 11 Compressed and Liquefied Gases
  • Chapter 12 Laboratory Operations Apparatus
  • Chapter 13 Hazard Identification

21
NFPA 45
  • Appendix A Explanatory Material
  • Appendix B Supplementary Definitions
  • Appendix C Supplementary Information on
    Explosion Hazards and Protection
  • Appendix D Supplementary Information on the
    Concept of the Laboratory Unit
  • Appendix E Flammable characteristics of Common
    Compressed and Liquefied Gases
  • Appendix F Safety Tips for Compressed Gas Users
  • Appendix G Informational References

22
Enclosure Integrity Procedure
  • NFPA 12A, 2004
  • Annex B, Door fan testing methods and formulas
    for calculating enclosure leakage
  • NFPA 2001, 2004
  • Annex C, Door fan testing methods and formulas
    for calculating enclosure leakage

23
Automatic extinguishing systems
  • NFPA 12, 2005
  • Standard on Carbon Dioxide Extinguishing Systems
  • NFPA 12A, 2004
  • Standard on Halon 1301 Fire Extinguishing
    Systems,
  • NFPA 13, 2005
  • Standard for the Installation of Sprinkler
    Systems
  • NFPA 2001, 2004
  • Standard on Clean Agent Fire Extinguishing
    Systems

24
Water-based fire protection systems
  • NFPA 25, 2002
  • Establishes the minimum requirements for the
    periodic inspection, testing, and maintenance of
    water-based fire protection systems including
    sprinkler, standpipe and hose, fixed water spray
    and foam water.
  • Fires must be contained in the room of origin
    within a single laboratory unit. Lab units shall
    be fire compartmented from each other and non-lab
    areas.
  • Does not cover other automatic extinguishing
    systems ie, Low, Medium and High-Expansion Foam
    CO2 Halon 1301 Water Spray Fixed Systems Dry
    Chemical Wet Chemical Explosion Prevention
    Mist and Clean Agent. (These are referenced in
    NFPA 45, 6.2.2)

25
Fire doors
  • NFPA 80, 2007
  • Defines all pertinent codes for doors and other
    opening protectives in laboratories

26
Air conditioning ventilating systems
  • NFPA 90A, 2002
  • Defines all pertinent codes for installation of
    air conditioning and ventilating systems based
    upon occupancies and hazardous materials

27
Exhaust systems
  • NFPA 91, 2004
  • Standards for exhaust systems for air conveying
    of vapors, gases, mists, and non-combustible
    particle solids

28
Smoke-control systems
  • NFPA 92 A, 2006
  • Standard for Smoke-Control Systems Utilizing
    Barriers and Pressure Differences

29
Emergency response
  • NFPA 704, 2007
  • Standard system for the identification of the
    hazards of materials for emergency response

30
Testing design standards
  • Current resources for laboratories

31
Current resources for testing design standards
  • Agricultural Research Service (ARS) Facilities
    Design Standards, (242.1M-ARS), 2006
  • American National Standards Institute (ANSI),
    General Room Exhaust of (ANSI/AIHA Z9.5),
    Laboratory Ventilation, 2002
  • Standard Test Method for Water Penetration of
    Windows, Curtain Walls and Doors Using Dynamic
    Pressure, (AAMA 501.1-05), 2005
  • Standard Test Method for Determining Rate of Air
    Leakage Through Exterior Windows, Curtain Walls,
    and Doors Under Specified Pressure Differences
    Across the Specimen, (ASTM E 283-04)

32
Current resources for testing design standards
  • Standard Test Method for Structural Performance
    of Exterior Windows, Doors, Skylights and Curtain
    Walls by Uniform Static Air Pressure Difference,
    (ASTM E 330-02) and (ASTM E 331-00)
  • World Health Organization (WHO)
  • Department of Health and Human Services, Centers
    for Disease Control (CDC)
  • Association for Assessment and Accreditation of
    Laboratory Animal Care (AAALAC International)

33
Testing certification of a containment room
  • The purpose of testing is to determine if the
    walls, floors, ceilings, penetrations, and other
    containment barrier features have adequate
    integrity to prevent leakage of air from the
    containment space

34
Testing certification of a containment room
  • Testing will involve 3 steps
  • Pre-testing for gross leaks
  • Soap bubble pre-testing
  • Pressure decay testing

35
Testing for gross leaks
  • Raising and lowering containment space air
    pressure to about .5 W.C. (125 Pascal)
  • Look and listen for leaks

36
Soap bubble pre-testing
  • Performed after gross leaks have been identified
    and repaired
  • Typically performed under negative pressure when
    soap bubbles are readily visible on the inside
    surface of the containment barrier
  • Slowly load building to maintain 2 W.C. (500
    Pascal), then apply a low surface tension liquid
    detergent to find any sources of air leakage

37
Door fan testing
  • Measures the size of the holes in an enclosure
    and the pressure that exists across the holes
  • Pressurization should be gradual (to not damage
    the structure)

38
Door fan testing
  • Steps involved
  • Door fan is temporarily installed from the
    protected space to a large open area or outdoors
  • Blow air out of the room (Depressurization)
  • Blow air into the room (Pressurization)
  • These readings are averaged to reduce errors due
    to HVAC operation, wind and faulty gauge zeroing

39
Pressure decay testing
  • How retention time is calculated
  • The testing agent is heavier than air which
    presses down on the air in the room, so the flow
    develops whenever the holes have pressure across
    them, thus creating a negative pressure across
    the top (the descending interface case). This
    pulls a similar volume into the room as was exited

40
Pressure decay testing
  • Most specifications call for a ten minute
    retention time

41
Pressure decay testing
  • Typically the containment zone will be
    depressurized to 2 W.C. below adjacent areas.
    The differential pressure will then be recorded
    each minute for 20 minutes
  • A 20 minute wait period is required then the test
    is repeated
  • Acceptance criterion would be 2 consecutive tests
    demonstrating 1 W.C. negative differential
    pressure remaining after 20 minutes with an
    initial pressure of 2 W.C. negative pressure

42
Pressure decay testing reports
  • Each decay test report shall include
  • Start time and date
  • Start and end room temperature
  • Monometer data (brand, model, serial number, date
    of last calibration, full scale reading and
    smallest scale unit)
  • Description of fan blower unit and control means
  • Tabulation of pressure differential reading for
    each test minute
  • A graphical plot of the test data
  • A floor plan illustrating the containment
    envelope and the location of the fan/blower unit
  • A description of the test including seals and
    block outs
  • Signature and date by the person completing the
    test

43
Conclusion
  • The base code for labs is NFPA 45
  • NFPA 45 DOES NOT include door fan testing and
    pressure decay testing (refer to NFPA 12 A, Annex
    B and NFPA 2001, Annex C)

44
References
  • In addition to the codes listed
  • Diagrams Technical guidelines and fire safety
    requirements for laboratories handling chemicals.
    Singapore civil defense force http//www.scdf.gov
    .sg
  • Some definitions Wordnet a lexical database
    for the English language. Princeton university
    http//wordnet.princeton.edu
Write a Comment
User Comments (0)
About PowerShow.com