Title: Standards and procedures for pressure decay testing laboratories to ensure fire code compliance
1Standards and procedures for pressure decay
testing laboratories to ensure fire code
compliance
2Definition of a laboratory unit
- A laboratory unit (lab unit) is an enclosed space
used for experiments and tests - A lab unit can include ancillary offices, toilet,
etc. and contain one or more separate lab work
areas - A lab work area is defined as a space within the
lab unit for testing, analysis, research or
similar activities that involve the use of
chemicals
http//www.scdf.gov.sg
3Lab unit 1
http//www.scdf.gov.sg
4Lab unit 2
http//www.scdf.gov.sg
5Lab unit 3
http//www.scdf.gov.sg
6Defining lab units
1
2
All 3 lab unit layouts are the same - as defined
by the code.
3
http//www.scdf.gov.sg
7Basic fire safety requirements for laboratories
8Basic fire safety requirements for laboratories
- NFPA 45, 2004
- The prevention and control of hazards such as
fires explosions and exposure to toxic,
corrosive, and other harmful chemicals. - The objectives of this code are
- Limit injury to the occupants at the point of
fire origin. - Limit injury to emergency response personnel.
- Limit property loss to a maximum of a single
Laboratory Unit. - States that all new labs must be protected with
automatic extinguishing systems - It is not the objective of this standard to
address financial losses or business
interruptions or property loss.
9Basic fire safety requirements for laboratories
- NFPA 45, 2004 (cont)
- Fire compartmentation
- Fire fighting lobby
- Automatic fire detection and extinguishing system
- Caution label
- Anteroom
10(No Transcript)
11Biosafety level laboratories
- BSL-3, BSL-3 AG and BSL-4
12Definition of BSL
- Biosafety Level
- the level of safety from exposure to
infectious agents depends on work practices and
safety equipment and facilities
http//wordnet.princeton.edu
13Levels of BSL
- There are 5 levels of BSL
- BSL-1- exposure only to infectious agents that do
not ordinarily cause human disease - BSL-2 - exposure to infectious agents that can
cause disease in humans but whose potential for
transmission is limited - BSL-3 - exposure to infectious agents that can be
transmitted by the respiratory route and which
can cause serious infection - BSL-3AG research involving certain biological
agents in large animal species - BSL 4 - exposure to exotic infectious agents that
pose a high risk of life-threatening disease and
can be transmitted as an aerosol and for which
there is no vaccine or therapy
14Definition of BSL
- BSL-3 and BSL-4
- is defined as any enclosed room or space which
is designed to comply with the WHO, (World Health
Organization) and MOHs requirements for storing
or handling of biological agents or toxins - BSL-3 AG
- involves certain biological agents in large
animal species
15Guidelines for safety of BSL-3 BSL-4
- To stipulate the safety requirements for
biomedical facilities (Bio-Safety Level 3 and
above) handling biological agents or toxins - Lab units or lab work areas shall be
continuously maintained at a negative pressure - Pressure decay testing
- Door fan testing
Not covered in NFPA 45
16Typical BSL-3/4 containment lab
BOX IN A BOX
ANTE ROOMS
http//www.scdf.gov.sg
17Fire Codes
- Current resources for laboratories
18Current resources for codes
- Standard on Halon 1301 Fire Extinguishing
Systems, (NFPA 12A), 2004 - Standard for the Installation of Sprinkler
Systems, (NFPA 13), 2005 - Standard for the Inspection, Testing, and
Maintenance of Water-Based Fire Protection
Systems, (NFPA 25), 2002 - Standard on Fire Protection for Laboratories
Using Chemicals, (NFPA 45), 2004 - Standard for Fire Doors and Other Opening
Protectives, (NFPA 80) 2007 - Installation of Air Conditioning and Ventilating
Systems, (NFPA 90A), 2002
19Current resources for codes
- Standard for Exhaust Systems for Air Conveying of
Vapors, Gases, Mists, and Non-combustible
Particulate Solids, (NFPA 91), 2004 - Standard for Smoke-Control Systems Utilizing
Barriers and Pressure Differences, (NFPA 92A),
2006 - Life Safety Code, (NFPA 101), 2006
- Standard on Clean Agent Fire Extinguishing
Systems, (NFPA 2001), 2004 - Standard System for the Identification of the
Hazards of Materials for Emergency Response,
(NFPA 704), 2007
- The primary source for laboratories is NFPA 45
- as it was removed from NFPA 101 in 1996.
20NFPA 45
- Chapter 1 Administration
- Chapter 2 Referenced Publications
- Chapter 3 Definitions
- Chapter 4 Laboratory Unit Hazard Classifications
- Chapter 5 Laboratory Unit Design and
Construction - Chapter 6 Fire Protection
- Chapter 7 Explosion Hazard Protection
- Chapter 8 Laboratory Ventilating Systems and
Hood Requirements - Chapter 9 Chemical Storage, Handling, and Waste
Management - Chapter 10 Flammable and Combustible Liquids
- Chapter 11 Compressed and Liquefied Gases
- Chapter 12 Laboratory Operations Apparatus
- Chapter 13 Hazard Identification
21NFPA 45
- Appendix A Explanatory Material
- Appendix B Supplementary Definitions
- Appendix C Supplementary Information on
Explosion Hazards and Protection - Appendix D Supplementary Information on the
Concept of the Laboratory Unit - Appendix E Flammable characteristics of Common
Compressed and Liquefied Gases - Appendix F Safety Tips for Compressed Gas Users
- Appendix G Informational References
22Enclosure Integrity Procedure
- NFPA 12A, 2004
- Annex B, Door fan testing methods and formulas
for calculating enclosure leakage - NFPA 2001, 2004
- Annex C, Door fan testing methods and formulas
for calculating enclosure leakage
23Automatic extinguishing systems
- NFPA 12, 2005
- Standard on Carbon Dioxide Extinguishing Systems
- NFPA 12A, 2004
- Standard on Halon 1301 Fire Extinguishing
Systems, - NFPA 13, 2005
- Standard for the Installation of Sprinkler
Systems - NFPA 2001, 2004
- Standard on Clean Agent Fire Extinguishing
Systems
24Water-based fire protection systems
- NFPA 25, 2002
- Establishes the minimum requirements for the
periodic inspection, testing, and maintenance of
water-based fire protection systems including
sprinkler, standpipe and hose, fixed water spray
and foam water. - Fires must be contained in the room of origin
within a single laboratory unit. Lab units shall
be fire compartmented from each other and non-lab
areas. - Does not cover other automatic extinguishing
systems ie, Low, Medium and High-Expansion Foam
CO2 Halon 1301 Water Spray Fixed Systems Dry
Chemical Wet Chemical Explosion Prevention
Mist and Clean Agent. (These are referenced in
NFPA 45, 6.2.2)
25Fire doors
- NFPA 80, 2007
- Defines all pertinent codes for doors and other
opening protectives in laboratories
26Air conditioning ventilating systems
- NFPA 90A, 2002
- Defines all pertinent codes for installation of
air conditioning and ventilating systems based
upon occupancies and hazardous materials
27Exhaust systems
- NFPA 91, 2004
- Standards for exhaust systems for air conveying
of vapors, gases, mists, and non-combustible
particle solids
28Smoke-control systems
- NFPA 92 A, 2006
- Standard for Smoke-Control Systems Utilizing
Barriers and Pressure Differences
29Emergency response
- NFPA 704, 2007
- Standard system for the identification of the
hazards of materials for emergency response
30Testing design standards
- Current resources for laboratories
31Current resources for testing design standards
- Agricultural Research Service (ARS) Facilities
Design Standards, (242.1M-ARS), 2006 - American National Standards Institute (ANSI),
General Room Exhaust of (ANSI/AIHA Z9.5),
Laboratory Ventilation, 2002 - Standard Test Method for Water Penetration of
Windows, Curtain Walls and Doors Using Dynamic
Pressure, (AAMA 501.1-05), 2005 - Standard Test Method for Determining Rate of Air
Leakage Through Exterior Windows, Curtain Walls,
and Doors Under Specified Pressure Differences
Across the Specimen, (ASTM E 283-04)
32Current resources for testing design standards
- Standard Test Method for Structural Performance
of Exterior Windows, Doors, Skylights and Curtain
Walls by Uniform Static Air Pressure Difference,
(ASTM E 330-02) and (ASTM E 331-00) - World Health Organization (WHO)
- Department of Health and Human Services, Centers
for Disease Control (CDC) - Association for Assessment and Accreditation of
Laboratory Animal Care (AAALAC International)
33Testing certification of a containment room
- The purpose of testing is to determine if the
walls, floors, ceilings, penetrations, and other
containment barrier features have adequate
integrity to prevent leakage of air from the
containment space
34Testing certification of a containment room
- Testing will involve 3 steps
- Pre-testing for gross leaks
- Soap bubble pre-testing
- Pressure decay testing
35Testing for gross leaks
- Raising and lowering containment space air
pressure to about .5 W.C. (125 Pascal) - Look and listen for leaks
36Soap bubble pre-testing
- Performed after gross leaks have been identified
and repaired - Typically performed under negative pressure when
soap bubbles are readily visible on the inside
surface of the containment barrier - Slowly load building to maintain 2 W.C. (500
Pascal), then apply a low surface tension liquid
detergent to find any sources of air leakage
37Door fan testing
- Measures the size of the holes in an enclosure
and the pressure that exists across the holes - Pressurization should be gradual (to not damage
the structure)
38Door fan testing
- Steps involved
- Door fan is temporarily installed from the
protected space to a large open area or outdoors - Blow air out of the room (Depressurization)
- Blow air into the room (Pressurization)
- These readings are averaged to reduce errors due
to HVAC operation, wind and faulty gauge zeroing
39Pressure decay testing
- How retention time is calculated
- The testing agent is heavier than air which
presses down on the air in the room, so the flow
develops whenever the holes have pressure across
them, thus creating a negative pressure across
the top (the descending interface case). This
pulls a similar volume into the room as was exited
40Pressure decay testing
- Most specifications call for a ten minute
retention time
41Pressure decay testing
- Typically the containment zone will be
depressurized to 2 W.C. below adjacent areas.
The differential pressure will then be recorded
each minute for 20 minutes - A 20 minute wait period is required then the test
is repeated - Acceptance criterion would be 2 consecutive tests
demonstrating 1 W.C. negative differential
pressure remaining after 20 minutes with an
initial pressure of 2 W.C. negative pressure
42Pressure decay testing reports
- Each decay test report shall include
- Start time and date
- Start and end room temperature
- Monometer data (brand, model, serial number, date
of last calibration, full scale reading and
smallest scale unit) - Description of fan blower unit and control means
- Tabulation of pressure differential reading for
each test minute - A graphical plot of the test data
- A floor plan illustrating the containment
envelope and the location of the fan/blower unit - A description of the test including seals and
block outs - Signature and date by the person completing the
test
43Conclusion
- The base code for labs is NFPA 45
- NFPA 45 DOES NOT include door fan testing and
pressure decay testing (refer to NFPA 12 A, Annex
B and NFPA 2001, Annex C)
44References
- In addition to the codes listed
- Diagrams Technical guidelines and fire safety
requirements for laboratories handling chemicals.
Singapore civil defense force http//www.scdf.gov
.sg - Some definitions Wordnet a lexical database
for the English language. Princeton university
http//wordnet.princeton.edu