Seat Cushion Testing Methods Fire Test FAA Hand Book Regulation Lab A Lab F Lab B Lab G Lab C Lab D Lab E - PowerPoint PPT Presentation

About This Presentation
Title:

Seat Cushion Testing Methods Fire Test FAA Hand Book Regulation Lab A Lab F Lab B Lab G Lab C Lab D Lab E

Description:

Is Chair Frame. Affixed to Scale? Lab A - Yes. Lab B - Yes. Lab C - Yes. Lab D - Yes. Lab E - Yes ... Lab F - Remove Cushions and place on scale. Lab G ... – PowerPoint PPT presentation

Number of Views:190
Avg rating:3.0/5.0
Slides: 35
Provided by: edaw5
Category:

less

Transcript and Presenter's Notes

Title: Seat Cushion Testing Methods Fire Test FAA Hand Book Regulation Lab A Lab F Lab B Lab G Lab C Lab D Lab E


1
Seat Cushion Testing MethodsFire Test FAA
Hand Book RegulationLab A Lab FLab
B Lab GLab CLab DLab E

2
All labs participating are using Park Oil Burner
Model D. P. L.
3
Modification to BurnerLab A -Tabs, Anemometer
_at_ Airflow inletLab B - Tabs, Flow MeterLab C
- Adjustable Air InletLab D - Tabs, Static
DiskLab E - Tabs, AnemometerLab F - Tabs,
Fuel Filter Flow meter Lab G - Static Disk
4
Method of Rotating BurnerLab A - Mechanical
Lab B - MechanicalLab C - Electrical Motor
ActuatorLab D - MechanicalLab E -
MechanicalLab F - ManualLab G - Electrical
Motor Actuator
5
Method of Placing Temperature Measuring
Instruments in FlameManual Mechanical Lab
A Lab BLab F Lab C Lab
D Lab E Lab G
6
Fuel Lab A - No. 2 Grade Diesel Fuel
OilLab B - ASTM D2 Number 2 Lab C - Jet A
FuelLab D - No. 2 Home Heating OilLab E -
JP8Lab F - No. 2 DieselLab G - Jet A Fuel
7
Method for Measuring Fuel FlowLab A -
Nozzle Fuel PressureLab B - Flow MeterLab C
- Graduated Cylinder and StopwatchLab D -
Collection MethodLab E - Graduated Cylinder
Lab F - Flow MeterLab G - Timed Collection
Method
8
Intermittent Replacement of NozzleLab A
- YesLab B - No Lab C - YesLab D - NoLab
E - Yes, not oftenLab F - YesLab G - Yes
9
Distance of the stabilizer from end of the draft
tubeLab A - 4Lab B - 4.9 Lab C -
2.72Lab D - 4Lab E - 3 13/16Lab
F - 4Lab G - 3 ½
10
Distance of the stabilizer from end of the
draft tubeLab A - 10.16cmLab B -
12.5cmLab C - 6.91cmLab D - 10.16cmLab
E - 8.10cmLab F - 10.16cmLab G -
8.89cm
11
NozzleLab A - Monarch 2.0 80 CCLab
B - Monarch 2.25 80 AR Lab C -
Monarch 2.25 80 ARLab D - Monarch 80
CCLab E - Monarch 80 CCLab F - Hago
80 2.25Lab G - Monarch 2.25 80 R
12
Orientation of IgnitersLab A - 1000
1100Lab B - 600 Lab C - 1000Lab D
- 630Lab E - 1000 700 Lab F -
1200Lab G - 900 600
13
Dimensions of TabsLab A - 2.5 X .75Lab B
- 1.5 x .5 Lab C G - N/ALab D - 1 X
1Lab E - 1/16 thick 1 6/16 X ¾ X ¾ Lab F
- 2 thin steel Trapezoid, 2" long, measuring
2.25" at outer end 1.5" at inner end and 2
rectangles 2" long X 1" wide
14
Dimensions of TabsLab A - 63.5mm X
.19.05mmLab B 38.1mm x 12.7mm Lab C G -
N/ALab D 25.4mm X 25.4mmLab E 1.59mm
thick 34.93mm X 19.05mm X 19.05mm Lab F - 2
thin steel Trapezoid, 50.8mm long, measuring
2.25" at outer end 38.1mm at inner end and
2 rectangles 0.8mm" long X 5.4mm wide
15
Static DiskLab A - N/ALab B - N/A
Lab C - N/ALab D - Located 3.5 (8.89
cm) Behind StabilizerLab E - N/ALab
F - N/ALab G - Located directly behind
Stabilizer
16
Heat Flux GaugeLab A - Medtherm -
H-201Lab B - Vatell - 1000-1ALab C -
Hycal - C-1300-A-15-072-X2 Vatell -
1000-1 / S1K Amplifier Medtherm -
64-15-20KLab D - Vatell - 1000-1ALab E -
Vatell -Lab F - Vatell - 1000-1Lab G -
Medtherm - 64-20-20
17
Heat Flux Gauge Date of Last
CalibrationLab A - 7/11/2003Lab B -
10/8/2002Lab C - Annually or sooner if
necessaryLab D -12/4/2003Lab E - 6 months ago
Lab F -12/3/2001Lab G -3/7/2003 Annually or
sooner if necessary

18
In Cool Weather Is Heat Flux Cooled With Warm
Water to Avoid Condensation on the Surface During
Cold Weather?
  • Lab A - No Ambient Temp. 70 FLab B
    - No Lab C - Yes, Maintained _at_ 68 FLab D
    - NoLab E - No Lab F - NoLab G - No

19
ThermocoupleLab A - Type K 1/16" gageLab
B - Left Blank Lab C - Type K 1/16"
gageLab D - Type K-inc.-G-T4-12.00Lab E
- Type K 1/16" gageLab F - Type K 1/16"
gageLab G - Type K 1/16" gage
20
Thermocouple Flame TimeLab A - 5
HoursLab B - 1-3 minutes per calibration
Lab C - Variable - Replaced PeriodicallyLab
D - No time keptLab E - 45 Seconds Lab
F - Less than 30 HoursLab G - 3 Hours, 22
min.
21
Fuel Pressure GaugeLab A - 100 PSILab B
- Not reportedLab C - 85 PSILab D - 93
PSILab E - 100-105 PSILab F - 85 PSILab G
- 85 PSI
22
Last Calibration of Fuel GaugeLab A
- 1/30/2004Lab B - 1/2004Lab C - 1995Lab
D - 2 years agoLab E - UnknownLab F
- 5/16/2002Lab G - Replaced Annually

23
Wires Used to Secure Fabric Test SpecimenLab
A - 1 on BackLab B - 1 on Back Lab C
- None Binder Clips Lab D - 1 on BackLab
E - 1 on BackLab F - 1 on BackLab G - 1
on Back
24
Wires Used to Secure Leather Test SpecimenLab
A - 1 on Back 2 on BottomLab B - 3 on Back
3 on BottomLab C - No Reply Lab D - 1
on Back 2 on BottomLab E - Not reportedLab
F - 2 on BackLab G - 3 on Back 3 on
Bottom
25
Is Chair Frame Affixed to Scale?Lab A
- YesLab B - Yes Lab C - Yes Lab D
- YesLab E - YesLab F - NoLab G
- Yes
26
Method of Weighing PosttestLab A -
Continuous Reader Manual CalculateLab B -
Continuous Reader Manual Calculate Lab C -
Continuous Reader Manual CalculateLab D -
Continuous Reader Manual Calculate Lab E -
Continuous Reader Manual Calculate Lab F -
Remove Cushions and place on scaleLab
G - Computer displays calculates wt./
wt. Loss continuously
27
Air Velocity TransducerLab A - Extech Ins.
Model 44104 Date Cal. 1/12/2004Lab B - Omega
Model HH30A Date Cal. 1/20/2003Lab C - Kurz
Model 441S Date Cal. 1/27/2004Lab D - Dwyer
Ins. Model 641-6 Date Cal 11/20/2003Lab E -
Omega Model HH30A Date Cal. NewLab F -
Airflow Ins. Model TA400 Date Cal.
6/5/2002Lab G - Omega Model HHF618 Date Cal.
12/9/2003
28
Variance in Pre-post Test
CalibrationLab A - NoLab B - No Lab
C - Seldom Lab D - NoLab E -
Generally post test is close to per-testLab
F - Not ObservedLab G - Yes, Heat Flux is
cooler Thermocouples are warmer still in
spec
29
Dimensions of Burn ChamberLab A - 10
X 9 X 8Lab B - 18 x 11.5 x 13.1 Lab
C - 25 X 13 X 14Lab D - 16 X 13 X
14Lab E - Left BlankLab F - 12 X
10 X 8Lab G - 12 X 12 X 8 10 Shed
roof
30
Dimensions of Burn ChamberLab A -
3.m X 2.74m X 2.44mLab B - 5.5m x 3.5m x 4m
Lab C - 7.62m X 4m X 4.27mLab D -
4.88m X 4m X 4.27mLab E - Left BlankLab
F - 3.66m X 3.m X 2.44mLab G - 3.66m X
3.66m X 2.44m 3.m Shed roof
31
How Is Air Replenished to Burn ChamberLab
A - High Temperature VentilatorLab B -
Left Blank Lab C - Rooftop Plenum for
minimal cell VentilationLab D - Outside
air through wall ventsLab E - No forced air
into room Lab F - 7 X 3 door with access
holes in walls for instrumentationLab G -
Adjustable vents every two foot at base top
of walls
32
Is the Anemometer Permanently
Installed?Lab A - Yes Calibration Date
1/12/2004Lab B - No Calibration Date
1/20/2003Lab C - No Calibration Date
1/27/2004Lab D - Yes Calibration Date
8/20/2003Lab E - Yes Calibration Date
NewLab F G - FAR Test Method N/A
33
ScalesLab A - Weighmaster Model
1300Lab B - Busch 332 Lab C - Toledo
Scale 2095Lab D - Rice Lake 1040Lab E -
Not ReportedLab F - Penn Scale Model
17300Lab G - Advanced Weight Tech. BM
2424- 100 IQ510-2A
34
Scale CalibrationLab A - 7/7/2003Lab B
- 3/16/2003 Lab C - 1/30/2004Lab D
- 1/9/2004Lab E - Has Not Been
Calibrated by Mfg.Lab F - 6/2/2002Lab G
- 5/6/2003