Title: EZ Speed with SINAMICS S120 Basic Starter Offline Commissioning


1
EZ Speed with SINAMICS S120Basic Starter
Offline Commissioning
2
Open Starter Program Go Offline
  • Open Starter by Motor Icon for Sinamics

Go Offline with Starter Use
3
Open DDS (Drive Data Set)
  • From the Drive to be Commissioned Choose
  • Configuration
  • Choose Configure DDS
  • Offline Configuration Wizard is Opened

4
Control Structure Setup - Servo
  • Select Speed Control with Encoder
  • Use Function Modules when Needed
  • For the Servo Extended Setpoint Channel is
    needed
  • Next, Select Continue

5
Power Unit Configuration
  • Power Unit Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • Confirm Device type is Correct via Part label
  • Select Continue for next Configuration Screen

6
Motor Configuration
  • Motor Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • If Motor is a Drive-CLIQ Motor
  • Non Drive-CLIQ Motors can be Selected from List
  • Third Party Motors can have data entered

7
Motor Configuration
  • For Third Party Motors Select Complete Motor ID
  • Motor ID will be Completed on First Start Command
  • Motor may rotate back and forth slightly on Demo
  • Insure motor is braked for actual application if
    needed

8
Holding Brake Configuration
  • Motor Data Up-read in Auto Configuration
    (Drive-CLIQ)
  • If Motor is a Drive-CLIQ Motor
  • Non Drive-CLIQ Motors Check Motor Name Plate
  • DEMO drives do not Use Holding Brakes

9
Encoder Configuration
  • Choose Encoder Data for Non Drive CLIQ Encoder
  • Siemens and Third Party Encoders can be
    Parameterized
  • Choose 1024 HTL for the DEMO Induction Motor
  • Note Encoder 1 is from Motor Encoder

10
Technology Type
  • Choose Standard Technological Application
  • Other Option is for Fans Pumps
  • Note the Motor ID Parameter is set

11
Profibus Telegram type
  • Choose Free Telegram with BICO
  • The Profibus Telegram will be Configured Later
  • Free Telegram allows Custom Telegrams
  • Script Files will be used to Setup Telegram
    Mapping

12
Summary Data Acceptance
  • Review data and Click Finish if Complete
  • After Completing DDS Wizard Save and Compile
  • DDS Wizard Data is now Complete

13
Profibus Telegram Configuration
  • From the Drive to be Commissioned Choose
  • Configuration
  • Use Up Down Buttons to Move Drive Objects
  • CU is 1st and Drive (S) should be in Preceding
    Order
  • S7 Hardware Configuration Should be Closed!

14
Profibus Telegram Configuration
  • Select Word Length For Telegrams
  • CU Telegram not needed for Demo
  • Word Length For Telegrams
  • EZ_EPOS uses 10 words IN and 10 Words Out
  • EZ_APC_SPEED uses 10 Words IN and 10 Words Out
  • EZ_Basic_SPEED uses 6 Words IN and 6 Words Out

15
Profibus Telegram Configuration
  • Select Transfer to HW Config
  • CU Telegram will be sent to the S7 Hardware
    Config.
  • Select Yes to transfer

16
Profibus Telegram Configuration
  • Telegram has Successfully been Transferred
  • Note Blue Check Boxes
  • Save and Compile Program before Proceeding
  • Save and Compile Using Starter