ANY PIPE CONNECTION TO THE TURBINE IS A POTENTIAL SOURCE OF WATER EITHER BY INDUCTION FROM EXTERNAL EQUIPMENT OR BY ACCUMULATION OF CONDENSED STEAM - PowerPoint PPT Presentation

1 / 49
About This Presentation
Title:

ANY PIPE CONNECTION TO THE TURBINE IS A POTENTIAL SOURCE OF WATER EITHER BY INDUCTION FROM EXTERNAL EQUIPMENT OR BY ACCUMULATION OF CONDENSED STEAM

Description:

design basis design criteria main steam piping main steam piping main steam piping start-up drain upstream of boiler stop valve main steam line drains (typical for ... – PowerPoint PPT presentation

Number of Views:447
Avg rating:3.0/5.0
Slides: 50
Provided by: 3060
Category:

less

Transcript and Presenter's Notes

Title: ANY PIPE CONNECTION TO THE TURBINE IS A POTENTIAL SOURCE OF WATER EITHER BY INDUCTION FROM EXTERNAL EQUIPMENT OR BY ACCUMULATION OF CONDENSED STEAM


1
(No Transcript)
2
ANY PIPE CONNECTION TO THE TURBINE IS A
POTENTIAL SOURCE OF WATER EITHER BY INDUCTION
FROM EXTERNAL EQUIPMENT OR BY ACCUMULATION OF
CONDENSED STEAM
3
DESIGN BASIS
  • ASME TDP 1
  • RECORD NOTES OF DISCUSSION HELD AT TS-HQ,
  • N.DELHI ON 12.09.91 REGARDING DRAINS SYSTEM
  • SPECIFIC CUSTOMER REQUIREMENTS

4
DESIGN CRITERIA
  • DETECTION OF THE PRESENCE OF WATER
  • ISOLATION OF THE WATER BY MANUAL OR PREFERABLY
    AUTOMATIC MEANS
  •  
  • DISPOSAL OF THE WATER BY MANUAL OR PREFERABLY
    AUTOMATIC MEANS
  •  
  • NO SINGLE FAILURE OF EQUIPMENT SHOULD RESULT IN
    WATER ENTERING THE TURBINE

5
MAIN STEAM PIPING
6
MAIN STEAM PIPING
  • MS PIPING DRAINS UPTO TURBINE VALVES ARE LED TO
    ATMOSPHERE
  • DRAINS DOWNSTREAM OF TURBINE STOP VALVES ARE
    LED TO CONDENSER
  •  
  • START-UP DRAIN IS PROVIDED AT THE UPSTREAM OF
    BOILER STOP VALVE
  •  
  • MS STRAINER IS THE LOWEST POINT AND FORMS THE
    DRAIN POINT
  •  
  • BEFORE SEAT DRAIN IS CASCADED BACK TO THE MAIN
    STEAM LINE
  •  
  • DURING START-UP MS STRAINER / LINE DRAINS ARE
    OPEN TO ATMOSPHERE
  •   CONTD.

7
MAIN STEAM PIPING
  •  
  • AUTOMATIC CLOSURE OF MS STRAINER LINE DRAINS
  •  
  • SEPARATE ATMOSPHERIC FLASH TANK (UFT) IS
    PROVIDED IN TG AREA TO RECEIVE MS DRAINS / HP
    BYPASS DRAINS TO MINIMIZE ROUTING PROBLEM
  •  
  • DRAINAGE SYSTEM AS DESCRIBED HAS BEEN ADOPTED
    IN VARIOUS 210 MW / 250 MW / 500 MW PROJECTS LIKE
    DADRI, UNCHAHAR, BAKRESWAR, DAHANU, SURATGARH,
    KOTHAGUDEM, SIMHADRI ETC.

8
START-UP DRAIN UPSTREAM OF BOILER STOP VALVE
9
MAIN STEAM LINE DRAINS(TYPICAL FOR ONE LEG)
10
MAIN STEAM STRAINER DRAIN
11
HOT REHEAT PIPING
12
HOT REHEAT PIPING
  • DRAINAGE SYSTEM IS SIMILAR TO THAT OF MAIN
    STEAM EXCEPT THAT PRIOR TO STARTING THE TURBINE
    THE HOT REHEAT PIPING WILL BE AT CONDENSER
    PRESSURE, HENCE HOT REHEAT PIPING DRAINS ARE TO
    BE LED TO CONDENSER
  • HRH DRAIN VALVES ARE OPEN BEFORE START OF
    VACUUM PULLING
  • AUTOMATIC CLOSURE OF HRH STRAINER LINE
    DRAINS
  • ADDITIONALLY MANUAL DRAIN IS PROVIDED AT THE
    UPSTREAM OF RH ISOLATING DEVICE TO FACILITATE
    DRAINING OF PIPING AFTER HYDRO TEST OF RH
    SECTIONS

13
HRH RH ISOLATING DEVICE
14
HRH LINE DRAINS (TYPICAL FOR ONE LEG )
15
HRH DRAIN BETWEEN IPT VALVE
16
HRH STRAINER DRAIN
17
COLD REHEAT PIPING
18
COLD REHEAT PIPING
  • THE POTENTIAL SOURCE OF WATER INGRESS INTO CRH
    PIPE ARE
  • REHEATER SPRAY
  • HP BYPASS SPRAY
  • TOP HEATER EXTRACTION PIPING FROM HP EXHAUST
  • DESIGN OF DRAINAGE SYSTEM TO REMOVE THE ENTIRE
    WATER THAT CAN ENTER INTO CRH LINE IS
    IMPRACTICAL
  • SYSTEM IS DESIGNED TO PROVIDE SIGNAL TO ENABLE
    OPERATOR TO TAKE CORRECTIVE ACTION TO PREVENT
    WATER INFLOW
  • CRH PIPING DRAINS ARE LED TO CONDENSER AS IT
    COMES UNDER VACUUM DURING START-UP
  • CONTD.

19
COLD REHEAT PIPING
  • PIPING DOWNSTREAM OF CRH NRV FORMS LOWEST POINT
    IN THE CRH LINE
  • ADDITIONALLY DRAIN IS PROVIDED BETWEEN HP
    TURBINE EXHAUST CRH NRV
  • A MANUAL DRAIN IS ALSO PROVIDED AT THE
    DOWNSTREAM OF RH ISOLATING DEVICE TO FACILITATE
    DRAINING OF PIPING AFTER HYDRO TEST OF RH
    SECTIONS

20
CRH RH ISOLATING DEVICE
21
COLD REHEAT LINE DRAINS
22
CRH PIPING DRAIN BETWEEN HPT EXHAUST NRV
23
CRH PIPING DRAINS
24
CRH PIPING DRAIN POT
  • DRAIN POT OF 6 INCH DIA IS PROVIDED IN 210 MW /
    250 MW 12 INCH DIA IN 500 MW AT THE EACH LOW
    POINT
  • TWO LEVEL SWITCHES ARE INSTALLED ON THE DRAIN
    POT FOR SENSING OF PRESENCE OF CONDENSATE IN THE
    DRAIN POT AND EFFICIENT EVACUATION OF THE SAME
  • LEVEL SWITCH AT HIGH LEVEL SHALL INITIATE FULL
    OPENING OF THE DRAIN VALVE AS WELL AS PROVIDE AN
    ALARM IN CONTROL ROOM
  • LEVEL SWITCH AT HIGH HIGH LEVEL SHALL INITIATE
    AN ALARM AND REPEAT COMMAND FOR OPENING DRAIN
    VALVE
  • CONTD.

25
CRH PIPING DRAIN POT
  • HIGH HIGH LEVEL IS A WARNING TO THE OPERATOR TO
    INVESTIGATE ISOLATE THE SOURCE OF WATER INGRESS
  • BEFORE START OF VACUUM PULLING CRH DRAINS ARE
    OPEN TO CONDENSER AND OPERATOR TO ENSURE NO ALARM
    CONDITION ( CW PUMP CEP ARE RUNNING)
  • SPRAY IS ENVISAGED IN FLASH TANK TO COOL DRAINS
  • CLOSING OF CRH DRAIN VALVE IS REMOTE MANUAL

26
CRH DRAIN POT ARRANGEMENT
27
HP BYPASS PIPING
28
HP BYPASS PIPING
  • HP BYPASS WARM-UP DRAIN ARRANGEMENT HAS BEEN
    ADOPTED IN LINE WITH DELIBERATIONS DTD. 20-21ST
    FEB. 1998 AT TRICHY
  • HP BYPASS PIPING LAYOUT IS SUCH THAT ENTIRE
    PIPING IS SELF DRAINABLE TOWARDS MAIN STEAM /
    COLD REHEAT PIPING
  • WARM-UP TAPPING IS PROVIDED CLOSE TO THE BYPASS
    VALVE FROM BOTTOM OF THE PIPING
  • WARMING-UP LINE IS CONNECTED TO CRH LINE MINIMUM
    5M AWAY FROM TEMPERATURE TAPPING POINTS
  • START-UP DRAIN IS PROVIDED ON THE WARM-UP LINE
    AND IS LED TO ATMOSPHERE CONTD.

29
HP BYPASS PIPING
  • START-UP DRAIN OPENS PRIOR TO STARTING THE UNIT
    AND CLOSES WHEN HP BYPASS VALVE IS TAKEN INTO
    SERVICE
  • TEMPERATURE MEASUREMENT SHALL BE PROVIDED AT HP
    BYPASS VALVE INLET
  • HP BYPASS VALVE TO BE LOCATED ABOVE THE MAIN
    STEAM CRH PIPING
  • WARMING-UP LINE TO DOWNSTREAM OF MS STRAINER IS
    NOT PREFERRED AT IT WOULD LEAD TO UNSTRAINED
    STEAM TO TURBINE

30
HP BYPASS WARMING-UP SCHEME
31
HP BYPASS WARM-UP PIPING
32
LP BYPASS PIPING
33
LP BYPASS WARM-UP PIPING
34
LP BYPASS WARM UP PIPING
35
LP BYPASS PIPING
  • IN EARLIER 210MW SETS AN ISOLATING VALVE WAS
    ENVISAGED IN LP BYPASS WARM-UP SCHEME
  • THE PURPOSE OF ISOLATING VALVE IS TO ISOLATE
    WARM-UP LINE DURING INITIAL COLD START-UP
  • THIS VALVE HAS TO BE KEPT OPEN IN ALL OTHER
    MODES OF OPERATION
  • BASED ON THE SITE FEEDBACK AN ANALYSIS WAS DONE
    IT WAS OBSERVED THAT OPERATION OF ISOLATING
    VALVE WAS NOT PROPER AND WAS USUALLY LEFT CLOSED
    WHICH LEAD TO PROBLEMS WITH LP BYPASS SYSTEM
  • FROM DADRI 210MW TPS ONWARDS THIS ISOLATING
    VALVE HAS BEEN DISPENSED WITH CONTD.

36
LP BYPASS PIPING
  • IN 500MW PROJECTS ALSO THERE IS NO ISOLATING
    VALVE IN THE WARM-UP LINE
  • THIS HAS ENHANCED THE SYSTEM RELIABILITY AND
    EASE IN OPERATION
  • LP BYPASS LOOP PIPING DRAINS CAN BE CASCADED
    BACK TO HRH PIPING (BETWEEN TURBINE STRAINER)
    AT AN LOWER ELEVATION OTHERWISE DRAIN CAN BE LED
    TO CONDENSER
  • DRAIN ON WARMUP LINE IS PROVIDED CLOSE TO VALVE
    TO ENSURE WARMING UP
  • CONTD.

37
LP BYPASS PIPING
  • BEFORE PULLING VACUUM IN THE CONDENSER OPEN
    ABOVE DRAINS TO CONDENSER
  • ONCE LP BYPASS VALVE IS TAKEN INTO OPERATION
    THESE DRAIN VALVES CAN BE CLOSED

38
LP BYPASS WARMING UP SCHEME FOR 210 MW UNITS
39
LP BYPASS WARMING UP SCHEME FOR 500 MW UNITS
40
OPERATING MODES
  • COLD START-UP
  • ØDRAINS SHALL BE OPERATED AS DESCRIBED EARLIER
  • HOT START-UP
  • ØDURING TURBINE TRIPPED / BOILER TRIPPED
    CONDITION, OPEN AND CLOSE DRAINS AS IN
    COLD START-UP. MS STRAINER DRAINS ARE TO BE
    CLOSED AS SOON AS 50COF SUPERHEAT IS ACHIEVED
    AND BYPASS IS ESTABLISHED.
  • ØDURING TURBINE TRIPPED / BOILER IN SERVICE WITH
    HP/LP BYPASS CONDITION NO DRAINS TO BE OPENED

41
NTPC SPECIFIC REQUIREMENTS
  • FOLLOWING ARE ADDITIONAL FEATURES PROVIDED IN
    NTPC PROJECTS AS PER THE CONTRACTUAL REQUIREMENT
  • ANGLE VALVES INSTEAD OF GLOBE VALVES IN DRAIN
    LINES
  • NTPC SPECN. CALLS FOR TWO DRAINS FOR EACH DRAIN
    POINT I.E. ONE AS NORMAL DRAIN TO DRAIN FLASH
    TANK AND THE OTHER AS ALTERNATE DRAIN TO
    ATMOSPHERIC FLASH TANK. AFTER DELIBERATIONS
    ALTERNATE PATH ARE PROVIDED FOR MAIN STEAM DRAINS
    HOT REHEAT DRAINS ONLY
  • CLEAN OUT VALVES FOR DRIP POTS

42
ANGLE VALVE DRAIN ARRANGEMENT
43
FLASH TANKS SPRAY SYSTEM
  • FOR COOLING OF INCOMING HOT DRAINS FOLLOWING
    SPRAYS ARE ENVISAGED IN THE FLASH TANKS
  • CONDENSATE SPRAY FROM CEP DISCHARGE TO CONDENSER
    FLASH TANK THROUGH TEMPERATURE REGULATED ON /
    OFF TYPE CONTROL VALVE
  • CONTINUOUS SPRAY THROUGH A MANUAL REGULATING
    VALVE RESTRICTION ORIFICE FROM SERVICE WATER
    SYSTEM TO UNIT FLASH TANK
  • CONTINUOUS SPRAY THROUGH A RESTRICTION ORIFICE
    FROM CEP DISCHARGE VALVE GLAND SEALING HEADER TO
    HP DRAIN FLASH TANK

44
UNIT FLASH TANK ARRANGEMENT (TYP)
45
GENERAL RECOMMENDATIONS
  • DESIGN , CONTROL AND OPERATION OF ALL SYSTEM
    THAT HAVE A POTENTIAL FOR ALLOWING WATER TO THE
    TURBINE SHALL PREVENT ANY UNUSUAL ACCUMULATION
  • DRAINS SHALL BE INSTALLED AT EVERY LOW POINT
    WITH ADEQUATE MEANS (MANUAL / AUTOMATIC) TO
    DISPOSE OFF THE CONDENSATE COLLECTED
  • DRAIN LINE SIZE SHALL BE SUFFICIENT TO PREVENT
    RISK OF PLUGGING BY FOREIGN MATERIAL. NORMALLY
    DRAIN LINE SIZE IS 2 INCH
  • ALL DRAIN LINES SHALL PREFERABLY BE RUN
    INDIVIDUALLY AND HAVE CONTINUOUS SLOPE TOWARDS
    THE DISPOSAL POINT
  • CONTD.

46
GENERAL RECOMMENDATIONS
  • HIGH PRESSURE DRAINS SHALL BE PROVIDED WITH TWO
    VALVES IN SERIES , UPSTREAM LOCKED OPEN VALVE
    DOWNSTREAM MOTORIZED VALVE. LOW PRESSURE DRAINS
    SHALL BE PROVIDED WITH MOTORIZED VALVE
  • ALL MOTORIZED DRAINS SHALL HAVE FACILITY TO
    OPERATE FROM UNIT CONTROL ROOM WITH OPEN / CLOSE
    POSITION INDICATION
  • OPERATOR TO ENSURE THAT ALL THE MOTORISED DRAIN
    VALVES SHALL BE CLOSED IMMEDIATELY ON ATTAINMENT
    OF 10 BLOCK LOAD ON TURBINE
  • INSTALLATION LEVELS OF MS STRAINER. HRH
    STRAINER , CRH NRV ETC SHALL BE SUCH THAT DRAIN
    CAN BE LED WITH CONTINUOUS PROPER SLOPE TO THE
    TERMINAL POINT
  • CONTD.

47
GENERAL RECOMMENDATIONS
  • ALTERNATE PATH SHOULD BE AVOIDED AS IT BECOMES
    SOURCE OF AIR INGRESS. ALSO AT SOME SITES ITS
    MAL-OPERATION RESULTED SUCKING OF WATER FROM
    ATMOSPHERIC TANK INTO THE MAIN PIPING LEADING TO
    SEVERE PROBLEMS
  • DRAINS TO MANIFOLD SHALL BE GROUPED IN
    APPROXIMATELY SAME PRESSURE RANGES OTHERWISE
    DRAINS SHALL BE ARRANGED IN A DECREASING ORDER OF
    THE PRESSURE
  • DRAIN LINES TO THE MANIFOLD SHALL BE MOUNTED AT
    450 TO THE MANIFOLD AXIAL CENTRE LINE WITH THE
    DRAIN LINE DISCHARGE POINTING TOWARDS THE
    DISPOSAL POINT
  • CONTD.

48
GENERAL RECOMMENDATIONS
  • DRAIN SHALL BE PREFERABLY TAPPED THROUGH A DRIP
    POT
  • LOOPS REQUIRED FOR FLEXIBILITY SHALL BE IN THE
    PLANE OF THE SLOPE
  • LOOP DRAINS CAN BE CASCADED BACK TO THE MAIN
    PIPING BY GRAVITY AT A LOWER ELEVATION
  • OPERATION OF DRAIN VALVE, PLUGGING OF DRAIN
    LINES AND HEALTHINESS OF INSTRUMENTS SHALL BE
    PERIODICALLY CHECKED
  • LEVEL ACTUATED MECHANISM SHALL BE TESTED AT
    INTERVALS TO ENSURE THEIR PROPER FUNCTIONING
  • DRIP POTS, TRAPS ORIFICES FOR ALL DRAIN LINES
    SHALL BE REGULARLY CLEANED

49
THANK YOU
Write a Comment
User Comments (0)
About PowerShow.com