Title: PREVENTIVE%20WARM-UP%20OF%20PHASE%20AND%20GROUND%20WIRES%20OF%20OVERHEAD%20POWER%20LINES%20BY%20LOADED%20DEVICES%20IN%20THE%20PERIOD%20OF%20GLAZE%20DANGER
1PREVENTIVE WARM-UP OF PHASE AND GROUND WIRES OF
OVERHEAD POWER LINES BY LOADED DEVICES IN THE
PERIOD OF GLAZE DANGER
- Y.R. HUNGER
- (ELSI GROUP),
- Ju.V. DEMIN,
- I.R. PIVCHIK, E.G. CHROMOV
- ("Sibenergosetproject JSC)
- Russia
2The damages of Odessaenergo power system
Lines switched off by means of electrical
protection
Damaged elements of overhead lines
3Icing prevention currents
4Variants of load implementation
- To switch on high voltage resistors.
- To switch on electroheaters.
- To switch on LV lines into short circuit.
- To use specially designed powerful ground
electrodes. - To switch on ground wires to 6-35 kV.
5Example of icing prevention
6Types of load-producing devices
10 kV module of 1,5 MW (BEL Co. Moscow, Russia)
Induction electroheaters Edison-500 (500 kW,
0,4 kV). ProducerSibtehnomach (Novosibirsk,
Russia)
7Some features of icing prevention
- 1. The duration of icing is short (2-5 days), and
its start can be forecasted meteorologically. - 2. The expected locations of icing are known.
- 3. The beginning of icing corresponds with the
time of minimum load of overhead lines. - 4. The networks disposable power is at its
maximum level during the period of icing.
8CONCLUSIONS
- The method of icing prevention
- newly developed
- allows to protect a whole group of lines with
various voltage - doesn't require expensive equipment
- allows to minimise additional energy losses.