Prisma Plus the tested switchboard, complying with standard IEC 60 439-1 - PowerPoint PPT Presentation

About This Presentation
Title:

Prisma Plus the tested switchboard, complying with standard IEC 60 439-1

Description:

the tested switchboard, complying with standard IEC 60 439-1 Contents The low voltage switchboard A vital link for electrical distribution The low voltage electrical ... – PowerPoint PPT presentation

Number of Views:50
Avg rating:3.0/5.0
Slides: 27
Provided by: HeadL8
Category:

less

Transcript and Presenter's Notes

Title: Prisma Plus the tested switchboard, complying with standard IEC 60 439-1


1
Prisma Plus the tested switchboard,complyin
g with standard IEC 60 439-1
2
Contents
  • The low voltage electrical switchboard
  • The functions of an electrical switchboard
  • The IEC 60439-1standard
  • Prisma Plus a structured switchboard based on
    functional units
  • Forms partitioning
  • Forms separations within an assembly
  • The minimum requirements to guarantee the safety
    of a LV switchboard
  • The tests of standard IEC 60439-1
  • 7 type tests performed by the manufacturer
  • 3 routine tests performed by the panelbuilder
  • Switchboard builders and manufacturer, together
    for the safety challenge IEC 60439-1
  • Prisma Plus and the IEC 60439-1 standard an
    international influence

3
The low voltage switchboard
  • A vital link for electrical distribution
  • To satisfy the increasing needs of safety of
    people and equipment and availability of
    electrical power its realization is not
    improvised

Safety
Reliability
Availability
Maintenability
  • and to provide a continual balance between
  • the needs of safety and availability
  • and the constraints of reliability and
    maintenability of the installation.

Contents
Definitions
4
The low voltage electrical switchboard
  • Definitions
  • The safety is the aptitude of a system not to put
    the people in danger .
  • Availibilty is the percentage of time during
    which the system functions correctly. MTBF (Mean
    Time Between Failure) average time between two
    failures of a reparable system is a means of
    characterizing the availibility.
  • Reliability is the aptitude of a system to
    function correctly as long as possible. MTTF
    (Mean Time To Failure) average time of good
    working before the first failure is a means of
    characterizing the reliability.
  • Maintainability is the aptitude of a system for
    being repaired quickly.La maintenabilité est
    l'aptitude d'un système à être réparé rapidement.
    MTTR (Mean Time To Repair) the average duration
    of repair is a means of characterizing
    maintainability.

Back
5
The functions of an electrical switchboard
  • To group and protect against external influences
    the protection and control devices and all their
    electrical and mechanical connections.
  • To inform the end-user on the state of his
    installation
  • To protect the switchboard user against the risk
    of accidents (direct and indirect contact).
  • To evolve with the activity.

Contents
Definitions
Cubicles up to 3200 A
Wall-mount and floor standing enclosures up to
630 A
6
The functions of an electrical switchboard
  • Definitions
  • Some of the components or specificities of the
    switchboard realize and/or guarantee its
    finalities,
  • in functional term
  • The architecture of LV network in centralized
    distribution
  • It results in a cutting into various switchboard,
    wall-mount enclosures... Distributed
    geographically, which
  • carry out the installation drawing.
  • Then various areas are defined within the
    switchboard
  • equipment
  • busbar
  • connection
  • auxiliary
  • The distances from minimal insulation and safety
    must already be respected.
  • The functional units
  • allow to realize the electrical functions
    correspondint to the user s
  • each unit is intended to cover a function, for
    example
  • - the incoming of current in the switchboard
  • - the protection of a feeder or a feeders
    whole- the motor control...
  • The enclosure
  • It materializes electric volume and ensures
    simultaneously
  • the protection of electrical materials which it
    contains against the external influences
  • the protection of people against electrical
    shocks (direct and indirect contacts).

Back
7
The IEC 60439-1 standard
  • The IEC 60439-1 standard gives general rules for
    switchboards construction to meet with safety
    and availability needs required by the
    application
  • guarantees the minimum level of safety of people
    and equipment
  • concerns the low-voltage switchgear and
    controlgear assemblies for the power
    distribution and control.
  • states
  • - the service conditions (temperature...)
  • - the construction requirements (IP, IK,
    forms,...)
  • - the tests requirements
  • So conformity to the standard is, for the end
    user, an insurance on switchboard realization
    quality.

Contents
8
Prisma Plus a structured switchboard based on
functional units
  • This modular design brings much clearness to the
    switchboard
  • incoming unit
  • current distribution units
  • feeder units
  • distribution units
  • connection units
  • communication units

Contents
Definitions
9
IEC 60439-1 Standard and Prisma Plus a
structured switchboard based on functional units
Definitions
  • Incoming units incoming circuit breaker
    (Masterpact, Compact NS, Interpact INS...).
  • Current distribution units busbars (Linergy,
    flat bars, Powerclip...).
  • Feeder units feeders circuit-breaker and
    contactors (Compact NS, Interpact INS, switch
    INV, modulars devices...).
  • Each device is part of a functional unit
    comprising
  • a dedicated mounting plate for device
    installation
  • a front plate to block direct access to live
    parts
  • prefabricated busbar connections
  • systems for on-site connections
  • running of cables and auxiliary wires
  • Connection units insulated flexible bars,
    prefabricated junction
  • Distribution units distribution block
    (Polypact, Polybloc, Multiclip, terminal
    block...).
  • Communication units measurement devices, BP,
    Powerlogic, Digipact (Human/swichboard Interface).

Back
10
Forms partitioning
  • In most installations, Prisma Plus cubicles do
    not require partitioning, Schneider Electric
    offering options and features that go well
    beyond the recommendations of the standard
  • front plates requiring a tool to be removed
  • doors providing access to live parts are
    keylocked
  • systematic installation of terminal shields on
    Compact NS circuit breakers and Interpact INS and
    INV switch-disconnectors
  • upstream and downstream terminals on the incoming
    device are covered
  • The protection of people and equipment is ensured
    on origin
  • However, Prisma Plus offers different levels of
    partitioning to create separations inside the
    cubicles and thus create Form 2,3 and 4, as
    defined by the standard.

Contents
11
Forms separations within an assembly
Prisma Plus
  • Form 1
  • Form 2a
  • Form 3a
  • Form 4a

Prisma Plus
Prisma Plus
Prisma Plus
  • Form 4b
  • Form 2b

Contents
  • Form 3b

Definitions
12
Forms separations within an assembly
Definitions
  • Form 1 no separation within the enclosure.
  • Form 2a the functional units are separated from
    busbars, but not the terminals
  • Form 2b the functional units and terminals are
    separated from the busbars. The terminals are not
    separated from each other.
  • Form 3a the functional units are separated from
    each other and from the busbars , but not the
    terminals.
  • Form 3b the functional units are separated from
    each other and from the busbars. Terminals are
    separated from busbars, but are not separated
    from each other
  • Form 4a the functional units are separated from
    each other and from the busbars . Terminals which
    are in the same compartment as the associated
    functional unit are separated from each other
  • Form 4b the functional units are separated from
    each other and from the busbars. Terminals are
    separated from each other and from the
    functional units.

Back
13
The minimum requirements to guarantee the
reliability of a LV switchboard
  • First of all, it must comply with standards
  • Switchboard construction standard
  • IEC 60439-1 low voltage switchgear assemblies.
  • Structural standards for incorporated switchgear
  • IEC 60947-1 general provisions
  • IEC 60947-2/3 circuit-breakers/switches
  • IEC 60269-1 low voltage fuses.
  • Installation standards
  • IEC 60364 buildings electrical installation
  • specific standards and rules to each country.

Contents
14
The tests of standard IEC 60439-1
They guarantee that the switchboard complies with
standard and confirm its characteristics
  • 7 type tests
  • n1 - temperature rise limits
  • n2 - dielectric properties
  • n3 - short-circuit withstand
  • n4 - protective circuit effectiveness
  • n5 - clearances and creepage distances
  • n6 - mechanical operation
  • n7 - degree of protection
  • 3 routine tests
  • n8 - overall inspection cabling, electrical
    operation
  • n9 - insulation/dielectric test
  • n10 - protection measures .

Contents
15
7 type tests performed by the manufacturer
  • The aim of these tests is to confirm the
    switchboard characteristics.
  • The 7 type tests are carried out on most
    difficult and unfavourable system Prisma Plus
    configurations. The assembled and cabled
    switchboards are made up of their usual
    components, connection system, equipped with
    Merlin Gerin and Telemecanique switchgear and
    assemblied and installed according to inductrial
    standards
  • The tests are conducted either in approved
    laboratories (Asefa, Kema, Lcie,), or in
    Schneider Electric ones

Contents
16
Test n1(8-2-1) Temperature rise limits
  • Guarantees the safety and reliability of the
    switchboard, by avoiding problems such as
  • connection damages
  • reduction in insulation performances
  • risk of burn for maintenance operators
  • electronic components damages
  • faulty operation of the devices inopportune
    release

Conditions
Contents
Results
17
Test n1(8-2-1) Temperature rise limits
  • Conditions
  • Tests progress
  • several switchboard configurations
  • equipped with Merlin Gerin and Telemecanique
    switchgear
  • 10 Clt ambient air temperaturelt40 C
  • switchgear loaded to its rated current,
    multiplied by the rated diversity factor
  • Complying limits (temperature rise limits)
  • when the temperature has stabilised, the
    temperature rise should not exceed limits
    admitted by materials or cause any burn
  • 70 C for terminal for external insulated
    conductors
  • 15 C or 25 C , according to material type , for
    manual operating means
  • 30 C or 40 C for accessible external enclosures
    and covers

Back
18
Test n1(8-2-1) Temperature rise limits
  • Results
  • The tests conducted with Prisma Plus have
    recorded temperature rises less than or equal to
    those stipulated by the standard.

Back
19
Test n2 (8-2-2) dielectric properties
  • Guarantees the switchboard safety and
    reliability , to avoid problems such as
  • electrical arc generation
  • insulation performance decreasing
  • connection damages

Conditions
Contents
Results
20
Test n2 (8-2-2) dielectric properties
Conditions
  • Tests progress
  • the test voltage is applied between all live
    parts and interconnected exposed conductive parts
    (frame), as well as between each pole and all the
    other connected poles
  • dielectric test voltage
  • - 3500 V for a rated insulation voltage 1000
    V for busbars in cubicle and rear busbars in
    enclosures
  • - 750 V for a rated insulation voltage 3000 V
    according to the type of busbars in enclosure
  • - 500 V for a rated insulation voltage 2500 V
    according to the type of busbars in enclosure
  • test duration 1 minute.
  • Complying limits
  • No arc flash-over or insulator perforation are
    observed.

Back
21
Test n2 (8-2-2) dielectric properties
  • Results
  • No arc flashover or insulator perforation for
    the test voltage following the rated voltage of
    busbars

Back
22
Test n3 (8-2-3) short-circuit withstand
  • This test simulates an incident which could occur
    on site
  • Withstanding the short-circuit currents is
  • to avoid danger (rupture and projections of
    components, arc generation and propagation
    outside the switchboard,...)
  • it also means the installation can be quickly put
    back into operation after the incident

Conditions
Contents
Results
23
Test n3 (8-2-3) short-circuit withstand
Conditions
  • Tests progress
  • the short-circuit tests are carried out by using
    bolted connections at the ends of the main or
    secondary busbars
  • 25 kA rms/1 sec. for Prisma Plus System G
  • 85 kA rms/1 sec. for Prisma Plus System P
  • Complying limits
  • the main conductors and the insulating parts must
    retain their insulation and mechanical withstand
    characteristics (lenght, cross-section,
    dielectric properties,).

Back
24
Test n3 (8-2-3) short-circuit withstand
  • Results
  • After a short-circuit test, the Prisma Plus main
    conductors and the insulating parts keep on their
    insulation and mechanical withstand
    characteristics
  • maximum rated short-time currents on busbars
  • Prisma Plus System G Icw 25 kA rms/1 s
  • Prisma Plus System P Icw 85 kA rms/1 s.
  • the installation can be quickly put back into
    operation after a simple inspection

Back
25
Test n4 (8-2-4) effectiveness of the
protective circuit
  • The effectiveness of the protective circuit is
    verified by two tests
  • resistance measurement of the connection between
    the exposed conductive parts and the protective
    circuits
  • short-circuit withstand performed between the
    protective conductor and the nearest phase
    conductor.

Conditions
Contents
Results
26
Test n4 (8-2-4) effectiveness of the
protective circuit
Conditions
  • Tests progress
  • the short-circuit tests are carried out by using
    bolted connections at the ends of the main or
    secondary busbars
  • 15 kA rms/1sec. for Prisma Plus System G
  • 51 kA rms/1sec. for Prisma Plus System P.
  • Complying limits
  • the main conductors and the insulating parts must
    retain their insulation and mechanical withstand
    characteristics (lenght, cross-section,
    dielectric properties,).

Back
27
Test n4 (8-2-4) effectiveness of the
protective circuit
  • Results
  • After the test, continuity and short-circuit
    withstand of the protective circuit, whether it
    consists of a separate conductor or frame, is not
    significantly impaired
  • Continuity and short-circuit withstand of the
    Prisma Plus protective circuit comply with the
    standard.

Back
28
Test n5 (8-2-5) clearance and creepage
distances
  • Clearance control shortest distance between
    two conductive parts.
  • Creepage distance control shortest distance
    along the surface of an insulating material
    between two conductive parts.

Conditions
Contents
Results
29
Test n5 (8-2-5) clearance and creepage
distances
Conditions
  • The values given in the standard apply to bare
    live conductors and the switchgear.
  • The minimum clearance in air depends on the rated
    impulse withstand voltage and the degree of
    pollution in the switchboard.
  • The minimum creepage distance depends on the
    rated insulation voltage, the degree of pollution
    and the insulating material group separating live
    parts.

Back
30
Test n5 (8-2-5) clearance and creepage
distances
  • Results
  • The tests carried out on typical Prisma Plus
    configurations, equipped with standard main
    busbars, validate compliance with minimum
    clearances and creepage distances for a voltage
    of 1000V, degree of pollotion 3, IIIa material
    group.
  • minimum clearance 14 mm
  • minimum creepage distance 16 mm.

Back
31
Test n6 (8-2-6) mechanical operation
  • Endurance of material, guaranteeing the longevity
    of the various mechanisms.

Conditions
Contents
Results
32
Test n6 (8-2-6) mechanical operation
Conditions
  • The mechanical operation test is carried out on
    an assemblied switchboard.
  • The standard requires that 50 operating cycles be
    carried out.
  • Verification of locking mechanisms are included
    in this range of tests.

Back
33
Test n6 (8-2-6) mechanical operation
  • Results
  • After 50 operating cycles, the interlocking
    mechanisms and other moving parts of the
    switchboard preserve their initial properties
    - operation, - operating force.
  • Some more solicited moving parts of Prisma Plus
    have passed until 10000 operating cycles (door
    handles, hinges).

Back
34
Test n7 (8-2-7) degree of protection
  • The tests carried out define the capacity of an
    equipped switchboard to
  • protect persons against contact with live parts
  • protect equipment against penetration of solid
    objects and liquids
  • protect equipment against external influences
    such as impacts (shocks).

Conditions
Contents
Results
35
Test n7 (8-2-7) degree of protection
Conditions
  • Tests for solid objects penetration (test
    finger, stem and wire).
  • Tests for water ingress (jets of water, drop
    vaps).

Back
36
Test n7 (8-2-7) degree of protection
  • Results
  • Results of tests confirm the characteristics of
    Prisma Plus switchboard IP30 to IP55 and IK7 to
    IK10 according to the different configurations.
  • Prisma Plus system P - IP30/31/55- IK07 with
    fixed panelling frame- IK08 with door IP30-
    IK10 with door IP55.
  • Prisma Plus system G
  • enclosure - IP30/31/43- IK07 without door -
    IK08 with door
  • IP55 enclosure IK10
  • Pack enclosure- IP30- IK07 without door -
    IK08 with door.

Back
37
The IP degrees of protection (IEC 60529/EN
60529)
  • 1st digit
  • protection of persons
  • protection against solids.
  • 2nd digit
  • protection against liquids.
  • Additional letter (optional) protection of
    persons against contact with live parts
  • A protect againts access of the back of the
    hand
  • B protect against access of fingers Ø 12 mm
  • C protect against access of a tool diameter 2.5
    mm
  • D protect against access of a tool diameter 0.1
    mm

Contents
Definitions
38
Degree of protection
Definitions
  • The IEC 60529 standard (02/ 2001) gives , by the
    IP code, the different degrees of protection
    provided by an electrical enclosure.
  • The IP code is described by 2 specific digits
    an additional letter , in option, can complete
    the IP code when the real protection of persons
    against contact with live parts is better than
    the protection given by the first digit
  • the 1st digit gives the level of protection of
    equipment against penetration of solid objects
    and protection of persons
  • the 2nd digit gives the level of protection of
    equipment against penetration of liquids.
  • Additional letter
  • it is used only when the effective protection of
    persons is better than the one given bythe
    first IP digit
  • in case of only protection of persons is needed,
    the 2 IP digits are replaced by x.
  • Example IPxxB.

Back
39
Degree of protection IK (IEC 62262)
  • IK code 2 digits giving the level of shock
    energy, in Joules
  • IK 01 0,14
  • IK 02 0,2
  • IK 03 0,35
  • IK 04 0,5
  • IK 05 0,7
  • IK 06 1
  • IK 07 2
  • IK 08 5
  • IK 09 10
  • IK 10 20.
  • The IEC 62262 standard defines a IK code which
    gives the equipment capacity to resist to
    mechanical impacts , on all the enclosure
    surfaces.

Contents
40
3 routine tests performed by the panelbuilder
  • The 3 routine tests, easily and rapidly
    performed, must be carried out by the
    panelbuilder.
  • overall inspection according to the mounting
    instructions and technical documents (right
    device ratings, tightening torques)
  • insulation checking by a dielectric test
  • checking of protective measures and of the
    electrical continuity of the protective circuits.
  • They complete the 7 manufacturer type tests and
    guarantee professionnalism and responsability of
    panelbuilder.
  • Schneider Electric supplies a full range of tools
    for assistance
  • Quality inspection guide
  • switchboard assembly and installation guide
  • Prisma Plus System P and G assembly guides

Contents
41
Test n8 (8-3-1) cabling, electrical operation
  • Check of mechanical actuating elements,
    interlocks, ... effectiveness
  • Check of proper laying of conductors and cables
    and proper mounting of device
  • Check of connections adequate contact, especially
    screwed and bolted connections.

Conditions
Contents
Results
42
Test n8 (8-3-1) cabling, electrical operation
Conditions
  • Check of conformity with
  • drawings, circuit and wiring diagrams
  • cabling (power and auxiliary connection)
  • cabling quality (cross-section, crimping...)
  • information and marking (cables and devices).
  • Visual inspection
  • degree of protection, creepage distances and
    clearancess
  • technical data document (diagrams,
    characteristics...).
  • Mechanical and electrical functioning test
  • check of cabling and most sensitive parts of the
    switchboard (mechanical control
    facilities,interlocks...).

Back
43
Test n8 (8-3-1) cabling, electrical operation
  • Results
  • The design of the switchboard , a structure based
    on functional units, insures conformity to this
    test.
  • Schneider Electric gives the basic rules of
    assembly and installation in its documentation
    for assistance

Back
44
Test n9 (8-3-4) insulation resistance /
(8-3-2) dielectric test
  • No arc flash-over or insulator perforation must
    be observed between the live parts each other and
    between the live parts and the conductive
    structural parts.

Conditions
Contents
Results
45
Test n9 (8-3-4) insulation resistance /
(8-3-2) dielectric test
Conditions
  • 2 possibilities of test depending on the
    panelbuilder s means
  • either insulation measuring (8-3-4)
  • or dielectric test (8-3-2).
  • all electrical equipment shall be connected for
    the test, except those apparatus which are
    designed for a lower test voltage
  • the test voltage is applied
  • - between each pole and interconnected exposed
    conductive parts - between each pole of main
    circuit and the other poles
  • - between each auxiliary control circuit and
    main circuit and exposed conductive parts
  • - between supply and withdrawable part of a
    switchgear .
  • Insulation test (8-3-4)
  • insulation measurement using an insulation
    measuring device at a voltage of at least 500V.
  • Dielectric test (8-3-2)
  • for a rated operational voltage of 240/400 V, the
    dielectric test voltage of 2500 V must be applied
    during 1 s.

Back
46
Test n9 (8-3-4) insulation resistance /
(8-3-2) dielectric test
  • Results
  • Verification of insulation resistance (8-3-4)
  • The test is passed if there is no perforation or
    flashover between the different tested parts
  • Dielectric test (8-3-2)
  • The test is passed if the insulation resistance
    between circuits and exposed conductive parts is
    at least 1000 Ohms/V..
  • The standardization of the distribution and
    conenctions is the best guarantee.

Back
47
Test n10 (8-3-3) protective measures
  • Checking of protective measures and of the
    electrical continuity of the protective circuits
    for metallic assemblies

Conditions
Contents
Results
48
Test n10 (8-3-3) protective measures
Conditions
  • Visual inspection
  • Checking of protective measures against direct
    and indirect contacts
  • Checking of the electrical continuity of the
    protective circuits for metallic assemblies
    (screwed and bolted connections shall be checked
    for adequate contact) possibly by random tests.

Back
49
Test n10 (8-3-3) protective measures
  • Results
  • Compliance of mechanical and electrical assembly
    instructions guarantees good electrical
    continuity of protection circuits.

Back
50
Panelbuilder and manufacturer, together to offer
maximum safety and realibility
  • Manufacturer
  • products tested in real configurations
  • detailed instructions for fautless construction.
  • Installer
  • it has to its disposal informations, by means of
    tools of switchboard assembly and installation
    guide (catalogs, internet)
  • confidence in products and swichboards systems,
    the result of many years of experience
  • A shared success
  • this complementarity must fall under the duration
    to consolidate our professionalism.

Contents
Customers advantages
51
Panelbuilder and manufacturer, together to offer
maximum safety and realibility
Customers advantages
  • Panelbuilders (and installators workshops)
  • they complete a work of quality, simply
  • they minimize the risk related to their
    responsibility for realization of a switchboard
    of which they know and ensure the level of safety
  • they carry out very simply the conformity to the
    standard, therefore CE marking
  • they develop their professionalism by making
    known it
  • they are different from the other panelbuilders
  • they profit from the transfer of Schneider
    Electric s experiment and tools
  • Installators
  • for them, a certified switchboard is the
    guarantee of the safety of installation and the
    good completion of work
  • it is also the certainty to fulfill the user s
    requirements
  • they minimize the risk related to their
    responsibility for installation
  • they show professionalism.
  • Users
  • They have the certainty to have a switchboard
    ensuring
  • - the safety and whose the quality is proven
  • - maintenance and evolutivity easy thanks to the
    prefabrication and the standardization of the
    components
  • They are ensured of the equipment and components
    perennity.
  • They minimize the risks related to their
    responsibility for exploitation
  • Specifiers/consultants
  • For them it is the certainty to prescribe a
    switchboard which ensures the level of safety
    required by the user.

Back
52
Prisma Plus and IEC 60439-1 standard an
international influence
  • IEC 60439-1 the same standard for all the
    professionals of switchboards

IEC
UL
IEC
IEC
IEC
IEC
Contents
Write a Comment
User Comments (0)
About PowerShow.com