Title: High Speed Digital Data Logging for OnLine Monitoring and Diagnostics in CANDU Nuclear Power Plants


1
High Speed Digital Data Logging for On-Line
Monitoring and Diagnostics in CANDU Nuclear Power
Plants
  • B. Sur, H. Storey, V.N.P. Anghel, H.W. Hinds
    (retired),
  • Information Control Systems Development
    Division,
  • D. Taylor, E. Young (retired),
  • Point Lepreau Generating Station,
  • O. Glockler,
  • International Atomic Energy Agency

2
Outline
  • CANDU Safety Instrumentation
  • High Speed (gt 10 Hz) digital data acquisition
    systems
  • Examples of High Speed Data and Analysis from
    Point Lepreaus HSDL
  • Lessons learned and issues for future permanently
    installed high-speed data acquisition systems

3
CANDU Core Instrumentation
Shut-off Mechanical Control Absorber Rods
SDS 1 (vertical) ICFDs
Liquid Zone Controllers
SDS 2 (horizontal)ICFDs
(Adjuster Rods)
Ion Chambers
Poison Injection Nozzles
Spatial Control Vanadium ICFDs
4
CANDU 6 Safety System Trips Instruments
5
CANDU 6 Safety System Trips Instruments cont.
Time constants from few ms to 10s of hours
6
Data Acquisition Systems - Standalone
Trip Comparator Buffer Amp
Dynamic Compensator
Up to 1 kHz
ADCs
Local Disc
ICFD
Adjustable Filter
Optical Iso- Amp
ICFD Amp
Installed as required
AECL / OPG s Noise Analysis System (NAS)
7
Data Acquisition Systems - Permanent
Plant Upset Trigger
20 ms data
ADCs
Plant Data LAN
FIFO Buffer
Trip Comparator Buffer Amp
ICFD Amp
ICFD
Dynamic Compensator
Normal
HSDL Iso- Amp
6 s data
Point Lepreaus High Speed Data Logging System
(HSDL)
Permanently Installed
8
Point Lepreaus permanently installed High Speed
Data Logger
9
HSDL Reactor Trip Data
10
HSDL Reactor Trip Data
11
HSDL Reactor Trip Data
12
HSDL Steady State Data for Detector 1D
Raw time sequence
Histogram
13
HSDL Steady State Data for Detector 1D
Power Spectrum
Gain, Phase, Coherence
14
Lessons learned Issues
  • Data quality
  • Dropped points and irrational data
  • Examine, filter, correct data before analysis
  • Data buffer and network limitations for long-term
    (hours) of steady state data
  • Anti-aliasing input filter is required for noise
    analysis
  • Ability to subtract dc would improve resolution
    for steady state data
  • Analysis software a must
  • But generally works as anticipated

15
Usefulness of Permanent HSDL
  • Any reactor trip becomes opportunity for safety
    system instrument verification
  • Readily available data for plant upset diagnosis
  • Steady State data available any time (eliminates
    temporary procedures)

16
Conclusions Permanent High Speed Data Logger
  • Necessary
  • For demonstrating compliance with safety analysis
    time constants
  • For effective sensor and system health monitoring
  • For diagnosis and resolution of problems
  • successfully implemented in Point Lepreau
  • should be retrofitted on existing plants
  • should be included in IC design of new plants