Title: High Speed Digital Data Logging for OnLine Monitoring and Diagnostics in CANDU Nuclear Power Plants
1High Speed Digital Data Logging for On-Line
Monitoring and Diagnostics in CANDU Nuclear Power
Plants
- B. Sur, H. Storey, V.N.P. Anghel, H.W. Hinds
(retired), - Information Control Systems Development
Division, - D. Taylor, E. Young (retired),
- Point Lepreau Generating Station,
- O. Glockler,
- International Atomic Energy Agency
2Outline
- CANDU Safety Instrumentation
- High Speed (gt 10 Hz) digital data acquisition
systems - Examples of High Speed Data and Analysis from
Point Lepreaus HSDL - Lessons learned and issues for future permanently
installed high-speed data acquisition systems
3CANDU Core Instrumentation
Shut-off Mechanical Control Absorber Rods
SDS 1 (vertical) ICFDs
Liquid Zone Controllers
SDS 2 (horizontal)ICFDs
(Adjuster Rods)
Ion Chambers
Poison Injection Nozzles
Spatial Control Vanadium ICFDs
4CANDU 6 Safety System Trips Instruments
5CANDU 6 Safety System Trips Instruments cont.
Time constants from few ms to 10s of hours
6Data Acquisition Systems - Standalone
Trip Comparator Buffer Amp
Dynamic Compensator
Up to 1 kHz
ADCs
Local Disc
ICFD
Adjustable Filter
Optical Iso- Amp
ICFD Amp
Installed as required
AECL / OPG s Noise Analysis System (NAS)
7Data Acquisition Systems - Permanent
Plant Upset Trigger
20 ms data
ADCs
Plant Data LAN
FIFO Buffer
Trip Comparator Buffer Amp
ICFD Amp
ICFD
Dynamic Compensator
Normal
HSDL Iso- Amp
6 s data
Point Lepreaus High Speed Data Logging System
(HSDL)
Permanently Installed
8Point Lepreaus permanently installed High Speed
Data Logger
9HSDL Reactor Trip Data
10HSDL Reactor Trip Data
11HSDL Reactor Trip Data
12HSDL Steady State Data for Detector 1D
Raw time sequence
Histogram
13HSDL Steady State Data for Detector 1D
Power Spectrum
Gain, Phase, Coherence
14Lessons learned Issues
- Data quality
- Dropped points and irrational data
- Examine, filter, correct data before analysis
- Data buffer and network limitations for long-term
(hours) of steady state data - Anti-aliasing input filter is required for noise
analysis - Ability to subtract dc would improve resolution
for steady state data - Analysis software a must
- But generally works as anticipated
15Usefulness of Permanent HSDL
- Any reactor trip becomes opportunity for safety
system instrument verification - Readily available data for plant upset diagnosis
- Steady State data available any time (eliminates
temporary procedures)
16Conclusions Permanent High Speed Data Logger
- Necessary
- For demonstrating compliance with safety analysis
time constants - For effective sensor and system health monitoring
- For diagnosis and resolution of problems
- successfully implemented in Point Lepreau
- should be retrofitted on existing plants
- should be included in IC design of new plants