Vision Tekniks is one of the leading Consultants ; Manufacturers of LT & HT Electrical Control Panels & Turnkey Electrification Contractors. Major part in the design of APFC panels is the selection of step size of capacitor banks and number of steps. The right selection of step size and number of steps plays a significant role in the performance as well as cost of the APFC panel. – PowerPoint PPT presentation

Number of Views:171

less

Transcript and Presenter's Notes

Title: Automatic Power Factor Correction Panel


1
VisionTekniks Engineering Automation
  • Vision Tekniks

2
VisionTekniks Engineering Automation
Automatic Power Factor Correction Panel
  • Optimum step size selection guidelines in APFC
    panels
  • Major part in the design of APFC panels is the
    selection of step size of capacitor banks and
    number of steps.
  • The right selection of step size and number of
    steps plays a significant role in the performance
    as well as cost of the APFC panel.
  • This article focuses on the need and ways of good
    step size (maximum and minimum sizes) selection
    and number of steps.

3
VisionTekniks Engineering Automation
1. Maximum step size selection
  • The maximum capacitor rating in an APFC panel
    depends up on the following
  • Maximum amount of load variation that happens in
    the industry at a time Large load variations
    demand bigger capacitor steps so that target
    power factor is achieved in short time, by less
    number of switching operations.
  • Current and voltage transient withstand
    capabilities of the system
  • Current transients Switching of big capacitors
    (usually above 100 kVAr) introduces large
    magnitude of inrush current (current transients)
    for a small duration. This results in high
    thermal and electrical stress on capacitors,
    short circuit protection devices and mainly, the
    switching device. This may lead to their nuisance
    tripping and premature failures.

4
VisionTekniks Engineering Automation
1. Maximum step size selection -- Continued.
  • Voltage transients Switching of big capacitors
    may cause transient over voltages, which might
    result in failure of sensitive electronic
    devices.
  • Thus, the maximum size of the capacitor step is a
    trade-off between the points i and ii.
    Practically acceptable maximum possible rating in
    any APFC panel shall be 100 kVAr. If this 100
    kVAr rating capacitor is switched using power
    contactor, the peak inrush current may reach as
    high as 75 kA. Hence, the capacitors should be
    switched using either capacitor duty contactors
    or thyristor switching module.
  • However, thyristor switching module or capacitor
    duty contactor for 100 kVAr rating is not readily
    available. Hence, the best way to switch a 100
    kVAr bank is by connecting two 50 kVAr TSM /
    contactor in parallel, each with a separate
    physical 50 kVAr capacitor banks. The control
    supply to both the 50 kVAr TSM/contactors shall
    be common (one relay output of the controller),
    so that both of the devices are triggered at the
    same time. To achieve this, the common output of
    the APFC relay should be programmed as 100 kVAr.
    Hence, physically they are two separate 50 kVAr
    banks, whereas electrically they behave as a
    single 100 kVAr bank.

5
VisionTekniks Engineering Automation
2. Minimum step size selection
  • The minimum capacitor rating depends on how
    precise the power factor needs to be maintained.
    This minimum kVAr rating depends upon the minimum
    current sensitivity (typically around 2.5) of
    the APFC controller. However the change in PF due
    to these minimum selected kVAr rating would be
    usually in the 3rd or 4th decimal places
    (depending on panel size or kVAr requirement),
    whereas the electricity board is concerned only
    with the first two digits of PF (like 0.99).
  • Typically many industries want the desired target
    PF to be unity (exactly 1.00), in order to get
    incentives from some EBs. But practically, the
    optimum target PF has to be 0.96 to 0.99. These
    are healthy levels of power factor as it will
    have safety margin that avoids the leading power
    factor as well as any dangerous harmonic
    amplification (due to more capacitance in the
    system).
  • Hence, as a rule of thumb, the minimum kVAr
    rating in an APFC panel can be chosen to be 5-10
    of overall rating of APFC panel. For smaller
    rating APFC panels (up to 100 kVAr), the smallest
    step can be 5 kVAr and for bigger rating APFC
    panels (above 600 kVAr and up to 1000 kVAr) the
    minimum rating can be 25 kVAr.

6
VisionTekniks Engineering Automation
3. Number of steps / branches in APFC panels
  • Once the minimum and maximum kVAr rating of the
    APFC panel is selected, the number of branches
    can be decided upon based of the following
  • Technology of APFC controllers Latest APFC
    controllers like etaCON L Series employ self
    optimized intelligent switching where the
    controller calculates the exact kVAr requirement
    and switches ON / OFF the appropriate capacitors
    irrespective of the capacitors already in
    circuit. Traditional controllers employing linear
    or circular switching require more number of
    smaller steps (like 122) for effective power
    factor correction. Whereas the latest controllers
    like etaCON can have a mix of large and small
    steps reducing the number of steps in capacitor
    bank as well as the cost of associated
    switchgear.
  • Size cost of APFC panel More the number of
    steps more will be the cost of APFC panel, due to
    more number of switchgear, bigger size of panel
    and others.

7
VisionTekniks Engineering Automation
An APFC panel should have
  • a) Maximum number of electrical steps
    (combination of physical steps) to ensure more
    accurate and flexible power factor correction
  • b) Minimum number of physical steps to reduce the
    size and cost of the panel

8
VisionTekniks Engineering Automation
Summary
  • APFC panels with more number of steps (more than
    12) does not always mean better step resolution.
  • With the latest APFC controller technology, fewer
    steps are sufficient to achieve better step
    resolution and control of power factor
  • Hence, usually a combination of large, small and
    very small ratings is used in steps of capacitor
    banks, as given below
  • 1. Large rating capacitors (100 kVAr maximum)
    are required to PF compensation of base load and
    coarse power factor compensation
  • 2. Medium rating capacitors are meant for
    variable part of the reactive power
    compensation.
  • 3. Small rating capacitors (usually 5 to 10 of
    total kVAr or 25 kVAr for panels above 500 kVAr)
    are meant for fine tuning of the power factor.

9
VisionTekniks Engineering Automation
  • Please check if required kVAr of capacitors are
    installed.
  • Check the type of capacitor installed is suitable
    for application or the capacitors are de rated.
  • Check if the capacitors are permanently ON. The
    Capacitor are not switched off
  • When the load is not working, under such
    condition the average power factor is found to be
    lower side.
  • Check whether all the capacitors are operated in
    APFC depending upon the load operation.
  • Check whether the APFC installed in the
    installation is working or not. Check the CT
    connection is taken from the main incomer side of
    transformer, after the fix compensation of
    transformer.
  • Check if the load demand in the system is
    increased.
  • Check if power transformer compensation is
    provided.

Power Factor Improving
10
VisionTekniks Engineering Automation
  • Thumb Rule if HP is known.
  • The compensation for motor should be calculated
    taking the details from the rating plate of motor
    Or
  • the capacitor should be rated for 1/3 of HP
  • Kvar Required For Transformer Compensation
  • Transformer                                      
        Required Kva
  • lt 315 kVA  T.C                           
        5 of  KVA
  • 315kVA To 1000 kVA                        6
    of  KVA
  • gt 1000 kVA                                 
       8 of  KVA

11
VisionTekniks Engineering Automation
  • Thumb Rule if HP is known.
  • The compensation for motor should be calculated
    taking the details from the rating plate of motor
    Or
  • the capacitor should be rated for 1/3 of HP
  • Kvar Required For Transformer Compensation
  • Transformer                                      
        Required Kva
  • lt 315 kVA  T.C                           
        5 of  KVA
  • 315kVA To 1000 kVA                        6
    of  KVA
  • gt 1000 kVA                                 
       8 of  KVA