DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER PROTECTION USING WALSH SERIES AND LEAST SQUARES ESTIMATORS - PowerPoint PPT Presentation

About This Presentation
Title:

DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER PROTECTION USING WALSH SERIES AND LEAST SQUARES ESTIMATORS

Description:

digital differential relays for transformer protection using walsh series and least squares estimators ali reza fereidunian*, mansooreh zangiabadi*, – PowerPoint PPT presentation

Number of Views:505
Avg rating:3.0/5.0
Slides: 34
Provided by: Fereid
Category:

less

Transcript and Presenter's Notes

Title: DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER PROTECTION USING WALSH SERIES AND LEAST SQUARES ESTIMATORS


1
DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER
PROTECTION USING WALSH SERIES AND LEAST SQUARES
ESTIMATORS
  • Ali Reza FEREIDUNIAN,
  • Mansooreh ZANGIABADI,
  • Majid SANAYE-PASAND,
  • Gholam POURNAGHI
  • ECE Dep., Faculty of Engg., University of
    Tehran,Tehran, IRAN
  • Kerman Regional Electric Company (KREC),
    Kerman, IRAN

2
Differential Protection
  • The fundamental principle of differential
    protection sum of the currents entering a device
    through normal paths should be zero Kirchhoff's
    Current Law (KCL).
  • If the currents enter (or leave) through abnormal
    paths, namely fault paths, then the sum of the
    currents through normal paths will not be zero.

3
Differential Protection Illustration
4
Problems in transformer differential protection
  • inrush current,
  • CT inaccuracy,
  • CT saturation,
  • over-excitation.
  • These problems produce fault trips (fault alarm
    when there isnt any trip) or no alarm when there
    is a trip in transformer protection function

5
DIFFERENTIAL RELAY IMPLEMENTATION
  • Current Sensor (CT) converts large amounts of
    current to small amounts
  • Data Acquisition System gathering data
  • Filter anti aliasing
  • Pre-processor scaling and so on
  • Estimator estimating peak phase
  • Decision Maker (Classifier) fault/no fault

6
Effect of CT Saturation on a Sinusoidal Current
7
WE HAVE USED TWO METHODS
  • FOR ESTIMATING PEAK AND PHASE OF INPUT WAVE.

8
Walsh coefficients

9
Walsh Series (Ctd)
  • WA F
  • FA-1W
    where
  • F F0 F1 F2 F3 F4 F5 F6 F7 F8
  • A-1AT

10
Least Squares
  • AX B
  • E AX B
  • LPI(A) B
  • LPI(A)

11
Sampling
  • 12 point window (for half cycle estimation) or
  • 24 points (for full cycle estimation)
  • with
  • 24 sample/cycle sampling system

12
Least square frequncy response for fundamental
frequency
13
The Decision Space
14
Inrush Pattern Recognition
  • A significant second harmonic
  • Inrush Current Pattern Recognition

15
A CASE STUDY
  • Real recorded data
  • Transformer internal fault,
  • Transformer external fault,
  • Transformer inrush current

16
High and Low Voltage Side Currents for External
Fault
17
High and Low Voltage Side Currents for Internal
Fault
18
High and Low Voltage Side Currents for Inrush
Current
19
Three Phases Differential Currents in External
Fault
20
. Three Phases Differential Currents in Internal
Fault
21
Three Phases Differential Currents in Inrush
Current
22
Decision Space in External Fault for three Phases
23
Decision Space in Internal Fault for Three Phases
24
Decision Space in Inrush Current for Three Phases
25
Second/Fundamental Harmonic Ratio for External
Fault
26
Second/Fundamental Harmonic Ratio for Internal
Fault
27
Second/Fundamental Harmonic Ratio for Inrush
Current
28
General Trip Alarm for External Fault
29
General Trip Alarm for Internal Fault
30
General Trip Alarm for Inrush Current
31
Summary
  • A digital differential relay for transformer
    protection was presented.
  • Two estimator systems Walsh series and least
    squares algorithms were formulated and designed.
  • The differential protection decision maker
    subsystem was introduced.
  • Current signals harmonic components and second
    harmonic restraint concept were utilized in
    decision maker subsystem.

32
Conclusion
  • In a practical case study, the designed relay
    performance was tested under three real
    circumstances external fault, internal fault and
    inrush current.
  • It was shown -using graphs and illustrations-
    that the presented relay issues trip alarm for
    transformer internal fault, and does not issue
    trip alarm for external fault and inrush current
    situations.

33
Conclusion (Ctd)
  • It were seen that both estimation algorithms
    perform their job correctly.
  • Walsh series acts better than least squares
    algorithm, especially on second harmonic
    estimation.
  • An anti alias filter (for example a Butterworth
    one) will improve response of the estimator.
Write a Comment
User Comments (0)
About PowerShow.com