Title: DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER PROTECTION USING WALSH SERIES AND LEAST SQUARES ESTIMATORS
1DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER
PROTECTION USING WALSH SERIES AND LEAST SQUARES
ESTIMATORS
- Ali Reza FEREIDUNIAN,
- Mansooreh ZANGIABADI,
- Majid SANAYE-PASAND,
- Gholam POURNAGHI
- ECE Dep., Faculty of Engg., University of
Tehran,Tehran, IRAN - Kerman Regional Electric Company (KREC),
Kerman, IRAN
2Differential Protection
- The fundamental principle of differential
protection sum of the currents entering a device
through normal paths should be zero Kirchhoff's
Current Law (KCL). - If the currents enter (or leave) through abnormal
paths, namely fault paths, then the sum of the
currents through normal paths will not be zero.
3Differential Protection Illustration
4Problems in transformer differential protection
- inrush current,
- CT inaccuracy,
- CT saturation,
- over-excitation.
- These problems produce fault trips (fault alarm
when there isnt any trip) or no alarm when there
is a trip in transformer protection function
5DIFFERENTIAL RELAY IMPLEMENTATION
- Current Sensor (CT) converts large amounts of
current to small amounts - Data Acquisition System gathering data
- Filter anti aliasing
- Pre-processor scaling and so on
- Estimator estimating peak phase
- Decision Maker (Classifier) fault/no fault
6Effect of CT Saturation on a Sinusoidal Current
7WE HAVE USED TWO METHODS
- FOR ESTIMATING PEAK AND PHASE OF INPUT WAVE.
8Walsh coefficients
9Walsh Series (Ctd)
- WA F
- FA-1W
where - F F0 F1 F2 F3 F4 F5 F6 F7 F8
- A-1AT
-
10Least Squares
- AX B
- E AX B
- LPI(A) B
- LPI(A)
11Sampling
- 12 point window (for half cycle estimation) or
- 24 points (for full cycle estimation)
- with
- 24 sample/cycle sampling system
12Least square frequncy response for fundamental
frequency
13The Decision Space
14Inrush Pattern Recognition
- A significant second harmonic
- Inrush Current Pattern Recognition
15A CASE STUDY
- Real recorded data
- Transformer internal fault,
- Transformer external fault,
- Transformer inrush current
16High and Low Voltage Side Currents for External
Fault
17High and Low Voltage Side Currents for Internal
Fault
18High and Low Voltage Side Currents for Inrush
Current
19Three Phases Differential Currents in External
Fault
20. Three Phases Differential Currents in Internal
Fault
21Three Phases Differential Currents in Inrush
Current
22Decision Space in External Fault for three Phases
23Decision Space in Internal Fault for Three Phases
24Decision Space in Inrush Current for Three Phases
25Second/Fundamental Harmonic Ratio for External
Fault
26Second/Fundamental Harmonic Ratio for Internal
Fault
27Second/Fundamental Harmonic Ratio for Inrush
Current
28General Trip Alarm for External Fault
29General Trip Alarm for Internal Fault
30General Trip Alarm for Inrush Current
31Summary
- A digital differential relay for transformer
protection was presented. - Two estimator systems Walsh series and least
squares algorithms were formulated and designed. - The differential protection decision maker
subsystem was introduced. - Current signals harmonic components and second
harmonic restraint concept were utilized in
decision maker subsystem.
32Conclusion
- In a practical case study, the designed relay
performance was tested under three real
circumstances external fault, internal fault and
inrush current. - It was shown -using graphs and illustrations-
that the presented relay issues trip alarm for
transformer internal fault, and does not issue
trip alarm for external fault and inrush current
situations.
33Conclusion (Ctd)
- It were seen that both estimation algorithms
perform their job correctly. - Walsh series acts better than least squares
algorithm, especially on second harmonic
estimation. - An anti alias filter (for example a Butterworth
one) will improve response of the estimator.