Fire Alarm Systems, 1999 NFPA 72 The Standard and Their Impact with Current Codes - PowerPoint PPT Presentation

1 / 150
About This Presentation
Title:

Fire Alarm Systems, 1999 NFPA 72 The Standard and Their Impact with Current Codes

Description:

( This definition includes fire alarm systems whose sole purpose is to provide ... all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes. ... – PowerPoint PPT presentation

Number of Views:1616
Avg rating:3.0/5.0
Slides: 151
Provided by: dav5208
Category:

less

Transcript and Presenter's Notes

Title: Fire Alarm Systems, 1999 NFPA 72 The Standard and Their Impact with Current Codes


1
Fire Alarm Systems, 1999 NFPA 72The
StandardandTheir Impact with Current Codes
  • Presented by
  • Dave Miller, S.E.T.
  • Miller Consulting Group, LLC

2
What We Will Discuss Today
  • NFPA 72
  • Chapter 1
  • 1-4 Definitions
  • 1-5 Fundementals
  • 1-6 Documentation
  • Chapter 2
  • Various Sub Chapters
  • Chapters 3 5
  • A quick and brief review

3
What We Will Discuss Today
  • Chapter 4
  • Chapter 7

4
Definitions
Control Unit A system component that monitors
inputs and outputs through various types of
circuits. Fire Alarm System A systemthat
consist of components and circuits arranged to
monitor and annunciate the status of fire alarm
or supervisory signal-initiating devices and to
initiate the appropriate responses to those
signals. (This definition includes fire alarm
systems whose sole purpose is to provide
sprinkler supervisory service.)
5
Definitions
Signals Alarm Signal A signal indicating an
emergency that requires a immediate action, such
as a signal indicative of fire. Supervisory
Signal A signal indicating the need for action
in connection with the supervision of , the fire
suppression systems or equipment, or the
maintenance features of related systems. Trouble
Signal A signal initiated by the fire alarm
system or device indicative of a fault in
monitored circuit or component.
6
Definitions
Actions Acknowledge To confirm that a message or
signal has been received, such as by the pressing
of a button or the selection of a software
command. Silence Action by which predetermined
audio/visual devices and the panel audible no
longer sound or flash. Reset A control function
that attempts to return a system or device to its
normal, non-alarm state.
7
Definitions
Circuits Signaling Line Circuit A circuit or
path between any combination of circuit
interfaces, control units, or transmitters over
which multiple system inputs signals or output
signals, or both are carried. Comments SLCs
are typically configured as Style 4 (Class B)
or Style 7 (Class A) Campus High Rise
Networks use or are required to be Style
7 Devices use Style 4 typically
8
Definitions
Circuits Initiating Device Circuit a circuit to
which automatic or manual initiating devices are
connected where the signal received does not
identify the individual device operated. Comments
IDCs are typically configured as Style B
(Class B) or Style D (Class A) Monitor
Modules on SLCs will have IDCs associated with
them.
9
Definitions
Circuits Notification Appliance Circuit A
circuit or path directly connected to a
notification appliance(s). Comments NACs are
typically configured as Style Y (Class B) or
Style Z (Class A) Many devices are
synchronized via the NACs.
10
Definitions
Industry Definitions Addressable A fire alarm
system component with discrete identification
that can have its status individually identified
or that is used to individually control other
functions. Ability to collect information, and
control/program logic functions varies amongst
various system manufacturers. Peer-to-Peer Two
or more fully functional fire alarm systems
communicating via a SLC. Each system typically
has full standalone capability if network
communication is lost. Master-Slave A fully
functional fire alarm system with transponders
networked via SLCs. Transponders typically have
limited standalone capability if network
communication is lost. Indicates NFPA 72
Definition
11
Definitions
Industry Definitions Conventional/Hardwired Fire
alarm systems utilizing a zoned system of
non-addressable devices. IDCs are typical wired
with like devices on the same IDC. Combination
System A fire alarm system in which components
are used, in whole or part, in common with a
non-fire signaling system. Best example is a
burglar alarm system UL Listed for commercial
fire applications. Hybrid System A fire alarm
system were an SLC is used as data backbone for
interface modules and non-addressable smoke
detectors are then monitored from those modules.
Essentially a distributed, zoned
system. Indicates NFPA 72 Definition
12
1-5 Fundamentals
  • 1-5.1.3 System Design
  • plans and specifications by persons who are
    experienced in the proper design, application,
    installation, and testing of fire alarm systems.
  • The system designer shall be identified on the
    system design documents
  • Evidence of qualifications shall be provided when
    requested by the authority having jurisdiction.
  • PE Stamp
  • NICET Statement

13
NICET Statement
These plans have been designed and reviewed
by David C. Miller, Jr., S.E.T. Mr. Miller holds
a National Institute for Certification in
Engineering Technologies Level IV Fire Alarm
Systems, Certificate 96867. ___________________
_____ ___________ Signature


Date
  • These plans have been designed and reviewed
  • David C. Miller, Jr., S.E.T. Mr. Miller holds a
    National Institute for Certification in
    Engineering Technologies Level IV Fire Alarm
    Systems, Certificate 96867.
  • ________________________ ___________
  • Signature

    Date

14
1-5 Fundamentals
  • 1-5.2 Power Supplies
  • 1-5.2.2 All power supplies shall be installed
    in compliance with NFPA 70.
  • 1-5.2.3 Fire alarm systems shall be provided
    with
  • One primary
  • One secondary (standby)

15
1-5 Fundamentals
  • 1-5.2 Power Supplies
  • 1-5.2.4 Primary Supply
  • - shall have a high degree of reliability
  • - shall have adequate capacity for the intended
    service
  • - and shall consist of one of the following
  • (1) Light and power service
  • (2) Engine driven generator, manned 24/7
  • 1-5.2.5.2 Dedicated Branch Circuit

16
1-5 Fundamentals
  • 1-5.2.5.2 Dedicated Branch Circuit
  • circuits shall be mechanically protected
  • connections shall be mechanically protected
  • circuit disconnects shall have red marking
  • accessible only to authorized personnel
  • identified as FIRE ALARM CIRCUIT CONTROL
  • location of circuit disconnect shall be
    permanently identified in the FACP
  • 1-5.2.5.2 Overcurrent Protection
  • overcurrent device shall be located immediately
    adjacent to the connection to light and power
    connections
  • circuit breaker locks must be listed with the
    breaker

17
1-5 Fundamentals
  • 1-5.2.6 Secondary Supply Capacity and Sources
  • within 30 seconds of of primary power being
    incapable of providing the minimum voltage and
    without loss of signals
  • shall provide energy to the system in the event
    of total failure of the primary
  • In non-alarm condition (standby) the following
    shall be the standby battery capacity
  • protected premises 24 hours
  • central station 24 hours
  • proprietary 24 hours
  • auxiliary 60 hours
  • remote station 60 hours
  • voice evacuation 24 hours

18
1-5 Fundamentals
  • 1-5.2.6 Secondary Supply Capacity and Sources
  • at the end of the the standby period, the
    secondary source shall be able to operate the
    systems for
  • protected premises 5 minutes
  • central station 5 minutes
  • proprietary 5 minutes
  • auxiliary 5 minutes
  • remote station 5 minutes
  • voice evacuation 2 hours
  • is equal to 15 minutes of evacuation alarm at
    maximum connected load
  • the following are acceptable for secondary supply
    source
  • storage battery
  • auto start, engine driven generator with FACP
    having 4 hours standby and 5 minutes of alarm
    capacity

19
1-5 Fundamentals
  • 1-5.3 Compatibility
  • All fire alarm devices that receive power from
    SLC or IDC shall be listed with for use with
    the respective FACP
  • 1-5.4 System Functions
  • 1-5.4.1.2 As of 1/1/02 the time delay between
    activation of an input device and the automatic
    activation of a function shall be 10 seconds.
  • A-1-5.4.1.2 The 10 seconds does not include
    the fan wind down, door closure, or elevator
    travel, etc

20
1-5 Fundamentals
  • 1-5.4.4 Fire Safety Function Status Indicators
  • All controls provided specifically for the
    purpose of manually overriding any automatic fire
    safety function shall provide a visible
    indication of the status of the associated
    control circuits.
  • status indicators shall be arranged to
    reflect the actual status of the associated
    equipment or function
  • periodic testing to verify proper operation
    operation of mechanical equipment . Failure to
    test and maintain mechanical equipment with
    potential consequences up to and including the
    loss of life.

21
1-5 Fundamentals
  • Alarm, Supervisory, Trouble Signals
  • Overview clearly indicates that these signals
    shall be distinct and clearly indicated from each
    other.

22
1-5 Fundamentals
  • 1-5.4.11 Positive Alarm Sequence
  • requires approval by AHJ
  • alarm signal shall be answered within 15 seconds
    of receipt at FACP, if not done then system
    activation occurs with all associated functions
  • trained personnel shall have up to 180 seconds
    during the alarm investigation phase to evaluate
    the fire condition, and reset the system.
  • failure to reset with 180 seconds causes system
    activation with all associated functions
  • second device (PAS) shall cause system activation
    with all associated functions
  • any other initiating device actuated shall cause
    system activation with all associated functions

23
1-5 Fundamentals
  • 1-5.6 Protection of Fire Alarm Control Unit(s)
  • Definition Fire Alarm Control Unit(s)
  • a system component that receives inputs from
    automatic and manual fire alarm devices
  • might supply power to
  • - detection devices
  • - a transponder
  • - off-premises transmitter
  • might transfer power to the notification
    appliances
  • transfer of condition to relays or devices

24
1-5 Fundamentals
  • 1-5.6 Protection of Fire Alarm Control Unit(s)
  • in areas not continuously occupied (24/7)
  • smoke detection shall be required at each fire
    alarm control unit
  • where the area is not suited for smoke
    detection, then heat detector may be used
  • if area is not suitable for smoke detector, then
    it is likely not suitable for the fire alarm
    control unit
  • only one smoke detector required at control
    unit, even if space exceeds the Standards
    allowable area for smoke detector

25
1-5 Fundamentals
  • A-1-5.7.1.2 Zone of Origination
  • Floor exceeds 20k sq. ft., then divide into zones
    of less than 20K sq. ft. consistent with existing
    fire and smoke barriers on the floor
  • Consult AHJ for zoning when floor exceeds 20K sq.
    ft. and no smoke or fire barriers exist
  • Waterflow switches should be individually zoned
    that serve
  • Multiple floors
  • Areas exceeding 20K sq. ft.
  • Areas inconsistent wih established detection
    system zoning

26
1-5 Fundamentals
  • A-1-5.7.1.2 Zone of Origination
  • d) Duct smoke detectors should be individually
    zoned that serve
  • Air handling systems serving multiple floors
  • Areas exceeding 20K sq. ft.
  • Areas inconsistent wih established detection
    system zoning
  • e) Additional requirements
  • If floor area exceeds 20K sq. ft., additional
    zoning should be provided
  • Length of any zone should not exceed 300 in any
    direction
  • If the building has automatic sprinklers
    throughout, the area of the alarm zone should be
    permitted to be to coincide with the allowable
    area of the sprinkler zone

27
1-6 Documentation
  • 1-6.1 Approval and Acceptance
  • Prior to Installation
  • AHJ shall be notified prior to installation or
    alteration of equipment
  • AHJ can require complete information regarding
    the system or system alterations
  • Prior to requesting final approval
  • Installing contractor shall furnish a written
    statement
  • Installed in accordance with approved plans
  • Tested in accordance with manufacturers
    specifications and the appropriate NFPA standard

28
1-6 Documentation
  • 1-6.1 Approval and Acceptance
  • Record of Completion
  • Can be part of the written statement that is
    submitted prior to final approval by the AHJ
  • When multiple contractors are involved in the
    installation, each shall submit a form with the
    appropriate portions filled out

29
1-6 Documentation
  • 1-6.2 Completion Documents
  • Record of Completion
  • Parts 1, 2, and 4 through 10 shall be completed
    after the system is installed and installation
    wiring has been checked
  • Part 3 shall be completed after the operational
    acceptance tests have been completed
  • A preliminary copy shall be given to the system
    owner, and to the AHJ, if requested after wiring
    installation
  • A final copy shall be submitted after completion
    of operational acceptance testing

30
1-6 Documentation
  • 1-6.2 Completion Documents
  • Record of Completion
  • Shall be updated each time the system is modified
  • Shall include a revision date
  • Other documentation
  • Owners manual and installation instructions
    covering all system components (OMM)
  • Record drawings

31
1-6 Documentation
  • 1-6.2 Completion Documents
  • Central Station Fire Alarm Systems Certificated
  • Systems that comply with all aspects of this code
    shall be certificated by the organization that
    has listed the the prime contractor.
  • Certification document should be located at the
    FACP
  • The listing organization shall maintain a central
    repository of certification documents for the
    listed central station. This documentations
    shall be accessible to the AHJ.

32
1-6 Documentation
  • 1-6.2 Completion Documents
  • Central Station Fire Alarm Systems Placarded
  • Systems that comply with all aspects of this code
    shall be placarded by the prime contractor to
    indicated compliance.
  • Placard should be located at the FACP, and be a
    minimum of 20 sq.
  • The placard shall identify
  • The central station
  • The prime contractor by name and telephone number

33
1-6 Documentation
  • 1-6.3 Records
  • Complete, unalterable records of the tests and
    operations
  • Kept until the next test, and one year thereafter
  • Record shall be available for examination
  • If required, reported to the AHJ
  • Archiving by any means, so long as a hard copy
    can be provided promptly

34
Chapter 2 Initiating Devices
  • 2-1.3 Installation and Required Location of
    Initiating Devices
  • where subject to mechanical damage, an initiating
    device shall be protected
  • a mechanical guard shall be listed for use with
    the detector being used
  • in all cases, initiating devices shall be
    supported independently of their attachment to
    the circuit conductors
  • initiating devices shall be installed in all
    areas where required by other NFPA codes and
    standards, or the ahj
  • initiating devices shall be accessible for
    periodic maintenance and testing

35
Chapter 2 Initiating Devices
  • 2-1.4 Requirements for Smoke Heat Detectors
  • Detectors shall not be recessed in the mounting
    surface in any manner
  • Detector coverage
  • Total (Complete) Coverage
  • Partial Coverage
  • Selective Coverage
  • Supplementary (Nonrequired) Coverage

36
Chapter 2 Initiating Devices
  • 2-1.4 Requirements for Smoke Heat Detectors
  • 2-1.4.2.1 - Total (Complete) Coverage
  • included areas
  • all rooms, halls, storage areas, basements,
    attics, lofts, spaces above suspended ceilings,
    and other subdivisions and accessible spaces
    and the inside of all closets, elevator shafts,
    enclosed stairways, dumbwaiter shafts, and
    chutes. Inaccessible areas shall not be required
    to to be protected by detectors.
  • Exception No. 1 If inaccessible areas contain
    combustible material, they shall be made of
    accessible and be protected by detector(s).

37
Chapter 2 Initiating Devices
  • Exception No. 2 Detectors may be omitted from
    combustible blind spaces where any of the
    following conditions prevail 
  • (a)ceiling is attached directly to the underside
    of the supporting beams of a combustible roof or
    floor deck 
  • (b)Where the concealed space is entirely filled
    with a noncombustible insulation... 
  • (c)small, concealed spaces over rooms, space in
    question does not exceed 50 ft2 (4.6 m2) in area 
  • (d)In spaces formed by sets of facing studs or
    solid joists in walls, floors, or ceilings where
    the distance between the facing studs or solid
    joists is less than 6 in. (150 mm) 

38
Chapter 2 Initiating Devices
  • Exception No. 3 Detectors may be omitted from
    below open grid ceilings where all of the
    following conditions exist 
  • (a) Openings of the grid are 1/4 in. (6.4 mm) or
    larger in the least dimension. 
  • (b) Thickness of the material does not exceed the
    least dimension. 
  • (c) Openings constitute at least 70 percent of
    the area of the ceiling material
  • Exception No. 4 Concealed, accessible spaces
    above suspended ceilings, used as a return air
    plenum meeting the requirements of NFPA 90A,
    Standard for the Installation of Air Conditioning
    and Ventilating Systems, where equipped with
    smoke detection at each connection from the
    plenum to the central air-handling system.

39
Chapter 2 Initiating Devices
  • Exception No. 5 Detectors shall not be required
    underneath open loading docks or platforms and
    their covers and for accessible underfloor spaces
    if all of the following conditions exist
  • (a) Space is not accessible for storage purposes
    or entrance of unauthorized persons and is
    protected against the accumalation of windborne
    debris
  • (b) Space contains no equipment such as steam
    pipes, electric wiring, shafting, or conveyors
  • (c) Floor over the space is tight
  • (d) No flammable liquids are processed, handled,
    or stored on the floor above.

40
Chapter 2 Initiating Devices
  • 2-1.4.2.2 Partial Coverage
  • If required, partial detection systems shall be
    provided in all common areas and work spaces,
    such as corridors, lobbies, storage rooms,
    equipment rooms, and other tenantless spaces in
    those environments suitable for proper detector
    operation in accordance with this code.
  • 2-1.4.2.3 Selective Coverage
  • Where codes, standards, laws, or AHJs require
    the protection of selected areas only, the
    specified areas shall be protected in accordance
    with this code.
  • 2-1.4.2.4 Supplementary (Nonrequired) Coverage
  • Where installed, detection that is not required
    by an applicable law, code, or standard, whether
    total (complete), partial, or selective coverage,
    shall conform to the requirements of this code.
  • Exception Spacing requirements of Chapter 2

41
UBC, Section 1004.3.4Corridors
  • 1004.3.4.3 Construction
  • fully enclosed by
  • walls
  • floor
  • - ceiling
  • - permitted protected openings
  • - walls and ceilings of fire- resistive
    materials

42
UBC, Section 1004.3.4Corridors
  • Exceptions4.
  • Office spaces lt 100 occupants
  • Entire story is fully sprinkled
  • Smoke detection in the corridor
  • Audible alarms in all areas served by the
    corridors

43
UBC, Section 1004.3.4Corridors
  • Exceptions 6.
  • Group B constructed as Type I, Type II-FR, Type
    II-one hour construction
  • Corridors within office spaces of a single tenant
  • Entire story is fully sprinkled
  • Smoke detection in the corridor
  • Audible alarms in all areas served by the
    corridors

44
Typical Comm. Layout
45
Basic System
46
With FSDs Added
47
Note
  • Detector spacing in corridors may go up to 41 on
    center, and 20.5 from the end of the corridor.
  • If building is sprinkled, then many of
    requirements could already be in place.
  • Reduced cost of construction.

48
Radius to be .7 times the spacing
49
Spacing for Rectangular Areas
50
Fire/Smoke Damper Detection
  • Oregon Washington Codes

51
UBC 713.10
  • Smoke dampers shall be closed by actuation of a
    smoke detector installed in accordance with the
    Fire Code and one of the following applicable
    methods

52
UBC 713.10
  • damper within a duct, a smoke detector shall be
    installed within 5 feet of the damper
  • Selective Coverage per NFPA 72

53
Detection in Ducts w/FSD
54
Recommended Placement
55
UBC 713.10
  • 2. damper is installed within an unducted
    opening in a wall, a spot-type detector
    installed within 5 feet horizontally of the
    damper.
  • Selective Coverage per NFPA 72

56
Duct up to 36
57
Width up to 72
58
Width Greater than 72
59
(No Transcript)
60
Return HVAC/Return FSD
61
Supply FSD
62
Shutdown
63
Individual Damper Control
64
Single Pt. Control
65
UBC 713.10
  • 3. damper is installed in a ceiling, a spot-type
    detector within 5 feet of the damper.
  • Selective Coverage per NFPA 72

66
UBC 713.10
  • 4. damper in a corridor wall or ceiling, it may
    be controlled by a smoke-detection system
    installed in the corridor.
  • Partial Coverage per NFPA 72

67
Corridor with FSDs Detection
68
UBC 713.10
  • 5. When a total-coverage smoke-detection is
    provided within all areas served by an HVAC
    system, dampers may be controlled by the
    smoke-detection system.
  • Selective Coverage per NFPA 72
  • Or
  • Total Coverage per NFPA 72

69
Mechanical Specialty Code, Section 607
  • Smoke dampers shall also close whenever the
    fan serving the duct system is shut off.

70
  • How do we shut off the HVAC systems, and what is
    required?

71
State of Oregon1999 Mechanical Code
  • Section 606
  • Smoke Detection Systems Control

72
Section 606
  • 606.1 Controls Required. Air Distribution
    systems shall be equipped with smoke detectors

73
Section 606
  • 606.2.1 Return Air Systems
  • return air systems
  • gt 2,000 cfm
  • prior to any filters, exhaust air connections,
    outdoor air connections, or decontamination
    equipment or appliances.
  • Exception not required where the space served
    is protected by a system of area smoke detectors
    The area smoke detectors shall comply with
    Section 606.4.

74
Single Unit Interface
75
Section 606
  • 606.2.2 Common Supply and Return Air Systems.
  • multiple air-handling systems share common
    supply or return air ducts or plenums
  • with a combined design capacity greater than
    2,000 cfm
  • the return air system shall be provided with
    smoke detectors in accordance with Section
    606.2.1.

76
Multiple Units for Same Area
77
Section 606
  • 606.2.3 Return Risers
  • return air risers serve two or more stories
  • and are part of a return air system having a
    design capacity gt 15,000 cfm
  • smoke detectors shall be installed at each
    story.
  • smoke detectors shall be located upstream
    between the return air riser and any air ducts or
    plenums.

78
Multi-floor/15K cfm
79
Section 606
  • 606.3 Installation
  • in accordance with NFPA 72.
  • to monitor the entire airflow conveyed by the
    system
  • Access shall be be provided

80
Placement of Detector
81
Issues of Duct Smoke Detectors
  • NEMA Recommends six (6) widths of the duct,
    downstream from any bends or turbulence causing
    effect, to ensure laminar flow in duct.
  • Placement _at_ shaft penetrations on multi-story
    buildings Functionality, code compliant, and
    effective maintenance.
  • Size and configuration of duct work, to allow for
    best detection potential.

82
Section 606
  • 606.4 Controls Operation
  • smoke detectors shall shut down the air
    distribution system.
  • Air distribution systems that are part of a smoke
    control system shall switch to the smoke control
    mode upon activation of a detector.

83
Section 606
  • 606.4.1 Supervision.
  • shall be connected to a fire alarm system.
  • shall activate a visible and audible supervisory
    signal at a constantly attended location.

84
Section 606
  • Exceptions
  • supervisory signal not required where
    activates the buildings alarm-indicating
    appliances.

85
Section 606
  • Exceptions
  • In occupancies not required to be equipped with a
    fire alarm system
  • activate a visible and audible signal in an
    approved location.
  • Smoke detector trouble conditions shall be
    identified as air duct detector trouble.

86
Supervision w/o FACP
87
Supervision w/FACP S/D
88
  • Detection for Fire/Smoke Doors per
  • UFC Standard 10-2
  • Section 5-11.7

89
UFC Section 5-11.7
  • 5-11.7.1
  • door release not initiated by a fire alarm
    system smoke detectors protecting areas on both
    sides of the door
  • smoke detectors applied as specified in 5-11.7.

90
Section 5-11.7
  • 5-11.7.4.1
  • be closed in response to smoke flowing in either
    direction

91
(No Transcript)
92
(No Transcript)
93
(No Transcript)
94
Section 5-11.7
  • 5-11.7.4.1.3
  • depth of the wall section above the door gt 60
    inches
  • additional detectors may be required
  • an engineering evaluation.

95
Section 5-11.7
  • 5-11.7.4.1.4
  • specifically listed for door frame mounting
  • a listed combination or integral detector-door
    closer assembly is used
  • only one detector shall be required

96
Section 5-11.7
  • 5-11.7.4.2
  • release is indicated to prevent smoke
    transmission from one space to another
  • in one direction only
  • one detector located in the space to which smoke
    is to be confined shall suffice

97
(No Transcript)
98
(No Transcript)
99
(No Transcript)
100
(No Transcript)
101
Chapter 2 Initiating Devices
  • 2-8 Manually Actuated Alarm-Initiating Devices
  • 2-8.2.2 - Manual Pull Stations shall be located
    within 5 of the exit door way on each exit on
    each floor
  • 2-8.2.3 - Manual Pull Stations shall be mounted
    on both sides of group openings over 40 in width

102
Chapter 2 Initiating Devices
  • 2-9 Supervisory Signal-Initiating Devices
  • 2-9.2 Pressure Supervisory Signal-Initiating
    Device
  • (a) pressure tank supervisory indicates increase
    or decrease by 10 psi
  • (b) dry pipe supervisory indicates increase or
    decrease by 10 psi
  • (c) steam pressure supervisory indicates a fall
    below 110 of minimum operating pressure
  • (d) other supervisory devices shall be as
    indicated by the AHJ.

103
Chapter 2 Initiating Devices
  • 2-9 Supervisory Signal-Initiating Devices
  • 2-9.3 Water Level Supervisory Signal-Initiating
    Device
  • (a) pressure tank supervisory indicates when
    water level rises or falls by 3
  • (b) other water storage supervisory indicates
    when water level falls by 12
  • 2-9.4 Water Temperature Supervisory
    Signal-Initiating Device
  • (a) temperature supervisory indicates when
    water temperature falls under 40 F and when
    it returns to over 40 F

104
Chapter 2 Initiating Devices
  • 2-9 Supervisory Signal-Initiating Devices
  • 2-9.4 Room Temperature Supervisory
    Signal-Initiating Device
  • (a) temperature supervisory indicates when
    room temperature falls under 40 F and when
    it returns to over 40 F

105
Chapters 3 5
  • Chapter 3 Protected Premises Systems
  • All systems essentially fall under this Chapter
    of the Standard
  • Chapter 5 Distinguishes the difference between
    the various types of systems

106
Chapter 5
  • Protected Premises System Complies with all
    applicable chapters of NFPA 72, and does not go
    to an offsite location
  • Central Station Service A Protected Premises
    System with offsite monitoring by a UL Listed
    Central station.
  • Remote Supervising Station A Protected Premises
    System with offsite monitoring by a listed UL
    Central station.
  • Proprietary Supervising Station A Protected
    Premises System with monitoring by trained
    personnel at the location, or another location of
    the same owner.

107
Chapter 4 Notification Appliances
  • 4-2.3 Mechanical Protection
  • Guards or covers shall be listed for use with
    the appliance
  • Their effect on the appliances field of
    performance shall be in accordance with listing
    requirements.

108
Chapter 4 Notification Appliances
  • Example of private mode is a hospital patient
    care area
  • If allowed by code or the AHJ, audible appliances
    could be eliminated entirely in areas such as
    surgery or critical care

109
Chapter 4 Notification Appliances
  • 4-3 Audible Characteristics
  • 4-3.1.1 Average sound level of 105 dBA shall
    require a visible signal appliance
  • 4-3.2 Public Mode Audible Requirements
  • 4-3.2.2 - 15dBA over ambient or 5dBA above the
    maximum sound level having a duration of at least
    60 seconds use whichever method is greater
  • Exception 1 Elevator cars can meet private
    mode
  • Exception 2 If approved by AHJ, restrooms can
    meet private mode
  • Exception 3 If approved by AHJ, then a method
    of reducing ambient noise may be employed

110
Chapter 4 Notification Appliances
  • 4-3 Audible Characteristics
  • 4-3.3 Private Mode Audible Requirements
  • 4-3.3.1 - 45 dBA _at_ 10 and no more than 120 dBA
    at the minimum hearing distance
  • 4-3.3.2 - 10 dBA over ambient or 5dBA above the
    maximum sound level having a duration of at least
    60 seconds use whichever method is greater
  • 4-3.4 Sleeping Areas
  • 15 dBA over ambient or 5dBA above the maximum
    sound level having a duration of at least 60
    seconds or sound level of at least 70 dBA use
    whichever method is greater

111
Chapter 4 Notification Appliances

112
Chapter 7 Inspection, Testing, and Maintenance
Table 7-2.2 Smoke Detectors System/Spot Must
verify entry into smoke chamber, magnet is not
acceptable Duct Type Ensure that device samples
the air stream
113
Case Studies
  • OR
  • Also Known As
  • Dont try this in your Jurisdiction, building,
    design, etc.

114
  • 1
  • A Tale of Two Schools

115
A Tale of Two Schools
  • Group E, Division 3
  • Same Architect
  • Same MEP Consultants
  • Same GC
  • Same Mechanical Contractor
  • But Different Jurisdictions

116
A Tale of Two Schools
  • Approximately 15,000 Sq. Ft.
  • Single Story
  • Fully Sprinkled
  • Manual Pull Stations at All Exterior Exits
  • Audio/Visual Appliances Throughout
  • Monitoring of Sprinkler Systems and Kitchen Hood

117
A Tale of Two Schools
  • HVAC System
  • 13 Air Handler Units
  • 5 are Greater than 2000 CFM in Capacity
  • 7 Units Provide Either Supply or Return Air to
    the Corridor (1350 CFM at Returns)
  • FSDs Originally Shown on the Drawings for
    Corridor

118
A Tale of Two Schools
  • Fire Alarm System Design
  • Engineer Originally Showed Smoke Detection in
    the Corridor
  • Also Provided Detection in Areas Deemed
    Appropriate such as Laundry Room, Communications,
    Staff Areas, etc
  • Duct Smoke Detectors on the 5 HVAC Units

119
A Tale of Two Schools
  • School 1
  • FSDs for Corridor have been Eliminated from
    Project, but Actual Designation of Egress Path
    has not Changed from Corridor
  • AHJ has Owner Remove All Area Smoke Detectors,
    Not Necessary
  • All FSDs Have Been Removed, Except for the Two
    Servicing the Staff Restrooms, Compliance for
    Detection of FSDs is not Being Met

120
A Tale of Two Schools
  • School 1
  • Duct Smoke Detectors for Return Air Side of HVAC
    Units
  • Do Not Meet Spacing/Placement Requirements of
    NFPA 72

121
(No Transcript)
122
(No Transcript)
123
A Tale of Two Schools
  • School 2
  • FSDs for Corridor have been Eliminated from
    Project, but Actual Designation of Egress Path
    has not Changed from Corridor
  • Duct Smoke Detectors Have Been Placed on the 5
    Units, Except this Time the Devices are on the
    Supply Side
  • 3 Devices Will Probably Not Work
  • 2 Will Not Work Due to the Sampling Tubes
    Being Placed Parallel to Air Flow
  • Covers Were Left Off After Completion of
    Inspection

124
A Tale of Two Schools
  • School 2
  • Temporal Code for Audible Devices are not
    Synched from the FACP
  • When There is More Than One Audible for an Area,
    the Signal Becomes Indistinct Over Time

125
A Tale of Two Schools
  • MCG Solutions
  • Eliminate Duct Smoke Detectors
  • Provide 100 Detection in All Below Ceiling
    Spaces
  • Interconnect HVAC Units to Provide Shutdown for
    All Units Serving Same Common Space
  • Provide Shutdown to HVAC Units Requiring
    Shutdown via Alarm of Space Detection
  • Provide Synchronization of Audible/Visual
    Appliances

126
  • 2
  • When is Enough, Enough?

127
When is Enough, Enough?
  • 20,000 Sq. Ft. plus Elementary School
  • Fully Sprinkled Building
  • Full 100 Detection Below Ceilings
  • HVAC Ducted Supply and Returns
  • Problems were Sporadic Nuisance Alarms

128
Isnt this nice?
129
How About that Spacing?
20 Corridor
130
Think this will work?
131
Or this?
132
What about this?
133
What happened to 6 widths downstream?
134
Isnt this special???
135
Spaghetti anyone?
136
Recommendations
  • Redo the Spacing on Area Detection
  • Remove Duct Smoke Detectors
  • Install Control Modules to Facilitate HVAC Unit
    S/D
  • Install Conduit Path to NEMA 4X Boxes at Exterior
    Locations

137
  • 3
  • What About the Kitchen?

138
What About the Kitchen?
  • Code Essentially Requires Only that Fuel and/or
    Power Be Shutoff Under the Kitchen Hood When
    Discharge Occurs
  • What About When There is a Building Evacuation?
  • Under Certain Circumstances, It May be
    Adviseable to Shutdown Fuel and/or Power on
    Evacuation
  • How to do that?

139
(No Transcript)
140
  • 4
  • Uhm, What About the Smoke Control?

141
Uhm, What About the Smoke Control?
  • 3 Story Atrium
  • Under 1991 UBC
  • Smoke Control Fans and Associated Controls Were
    Forgotten
  • Large Areas Contiguous and Open to Atrium
  • Basic Addressable System was Already Installed

142
Uhm, What About the Smoke Control?
  • System Required Extensive Logic Functions
  • Unlock Doors, and then Force Doors Open
  • Firemans Panel Required Logic Functions for
    Lighting LEDs, etc
  • Existing FACP Was not Capable of Timed, And, Or,
    and Other Logic Functions

143
Uhm, What About the Smoke Control?
  • Recommendations
  • Added Smoke Detection to Atrium
  • Added Fire/Smoke Doors to Minimize Area Adjacent
    to Atrium
  • Designed Controls Including Positive Feedback
  • Included Monitoring of Main Power Switch to
    Exhaust Fans for Status

144
(No Transcript)
145
(No Transcript)
146
(No Transcript)
147
  • 5
  • And Last But Not Least

148
And Last But Not Least
  • Group E, Division 1 or 2
  • Type IV Construction
  • Not Sprinkled
  • Alarm and Detection System Installed Utilizing a
    Combination Fire Alarm/Burglar Alarm System

149
And Last But Not Least
  • Issues
  • Detection does not meet spacing requirements
  • Over Reliance on Heat Detectors
  • Strobes are Not Properly Sized for
    Applications
  • System Utilizes only a Single Phone Line for
    Offsite Dialing
  • Audible/Visual Appliances Start to Die About 2
    Minutes into Alarm (probably related to voltage
    drop)
  • Oh, and Did I Mention that My Son Goes to School
    Here

150
Thank You!!!
  • Miller Consulting Group, LLC
  • PO Box 1076
  • Newberg, OR 97132-1076
  • 503.537.9200
  • dcmiller_at_mcg-llc.net
Write a Comment
User Comments (0)
About PowerShow.com