Title: Fire Alarm Systems, 1999 NFPA 72 The Standard and Their Impact with Current Codes
1Fire Alarm Systems, 1999 NFPA 72The
StandardandTheir Impact with Current Codes
- Presented by
- Dave Miller, S.E.T.
- Miller Consulting Group, LLC
2What We Will Discuss Today
- NFPA 72
- Chapter 1
- 1-4 Definitions
- 1-5 Fundementals
- 1-6 Documentation
- Chapter 2
- Various Sub Chapters
- Chapters 3 5
- A quick and brief review
3What We Will Discuss Today
4Definitions
Control Unit A system component that monitors
inputs and outputs through various types of
circuits. Fire Alarm System A systemthat
consist of components and circuits arranged to
monitor and annunciate the status of fire alarm
or supervisory signal-initiating devices and to
initiate the appropriate responses to those
signals. (This definition includes fire alarm
systems whose sole purpose is to provide
sprinkler supervisory service.)
5Definitions
Signals Alarm Signal A signal indicating an
emergency that requires a immediate action, such
as a signal indicative of fire. Supervisory
Signal A signal indicating the need for action
in connection with the supervision of , the fire
suppression systems or equipment, or the
maintenance features of related systems. Trouble
Signal A signal initiated by the fire alarm
system or device indicative of a fault in
monitored circuit or component.
6Definitions
Actions Acknowledge To confirm that a message or
signal has been received, such as by the pressing
of a button or the selection of a software
command. Silence Action by which predetermined
audio/visual devices and the panel audible no
longer sound or flash. Reset A control function
that attempts to return a system or device to its
normal, non-alarm state.
7Definitions
Circuits Signaling Line Circuit A circuit or
path between any combination of circuit
interfaces, control units, or transmitters over
which multiple system inputs signals or output
signals, or both are carried. Comments SLCs
are typically configured as Style 4 (Class B)
or Style 7 (Class A) Campus High Rise
Networks use or are required to be Style
7 Devices use Style 4 typically
8Definitions
Circuits Initiating Device Circuit a circuit to
which automatic or manual initiating devices are
connected where the signal received does not
identify the individual device operated. Comments
IDCs are typically configured as Style B
(Class B) or Style D (Class A) Monitor
Modules on SLCs will have IDCs associated with
them.
9Definitions
Circuits Notification Appliance Circuit A
circuit or path directly connected to a
notification appliance(s). Comments NACs are
typically configured as Style Y (Class B) or
Style Z (Class A) Many devices are
synchronized via the NACs.
10Definitions
Industry Definitions Addressable A fire alarm
system component with discrete identification
that can have its status individually identified
or that is used to individually control other
functions. Ability to collect information, and
control/program logic functions varies amongst
various system manufacturers. Peer-to-Peer Two
or more fully functional fire alarm systems
communicating via a SLC. Each system typically
has full standalone capability if network
communication is lost. Master-Slave A fully
functional fire alarm system with transponders
networked via SLCs. Transponders typically have
limited standalone capability if network
communication is lost. Indicates NFPA 72
Definition
11Definitions
Industry Definitions Conventional/Hardwired Fire
alarm systems utilizing a zoned system of
non-addressable devices. IDCs are typical wired
with like devices on the same IDC. Combination
System A fire alarm system in which components
are used, in whole or part, in common with a
non-fire signaling system. Best example is a
burglar alarm system UL Listed for commercial
fire applications. Hybrid System A fire alarm
system were an SLC is used as data backbone for
interface modules and non-addressable smoke
detectors are then monitored from those modules.
Essentially a distributed, zoned
system. Indicates NFPA 72 Definition
121-5 Fundamentals
- 1-5.1.3 System Design
- plans and specifications by persons who are
experienced in the proper design, application,
installation, and testing of fire alarm systems. - The system designer shall be identified on the
system design documents - Evidence of qualifications shall be provided when
requested by the authority having jurisdiction. - PE Stamp
- NICET Statement
13NICET Statement
These plans have been designed and reviewed
by David C. Miller, Jr., S.E.T. Mr. Miller holds
a National Institute for Certification in
Engineering Technologies Level IV Fire Alarm
Systems, Certificate 96867. ___________________
_____ ___________ Signature
Date
- These plans have been designed and reviewed
- David C. Miller, Jr., S.E.T. Mr. Miller holds a
National Institute for Certification in
Engineering Technologies Level IV Fire Alarm
Systems, Certificate 96867. - ________________________ ___________
- Signature
Date
141-5 Fundamentals
- 1-5.2 Power Supplies
- 1-5.2.2 All power supplies shall be installed
in compliance with NFPA 70. - 1-5.2.3 Fire alarm systems shall be provided
with - One primary
- One secondary (standby)
151-5 Fundamentals
- 1-5.2 Power Supplies
- 1-5.2.4 Primary Supply
- - shall have a high degree of reliability
- - shall have adequate capacity for the intended
service - - and shall consist of one of the following
- (1) Light and power service
- (2) Engine driven generator, manned 24/7
- 1-5.2.5.2 Dedicated Branch Circuit
161-5 Fundamentals
- 1-5.2.5.2 Dedicated Branch Circuit
- circuits shall be mechanically protected
- connections shall be mechanically protected
- circuit disconnects shall have red marking
- accessible only to authorized personnel
- identified as FIRE ALARM CIRCUIT CONTROL
- location of circuit disconnect shall be
permanently identified in the FACP - 1-5.2.5.2 Overcurrent Protection
- overcurrent device shall be located immediately
adjacent to the connection to light and power
connections - circuit breaker locks must be listed with the
breaker
171-5 Fundamentals
- 1-5.2.6 Secondary Supply Capacity and Sources
- within 30 seconds of of primary power being
incapable of providing the minimum voltage and
without loss of signals - shall provide energy to the system in the event
of total failure of the primary - In non-alarm condition (standby) the following
shall be the standby battery capacity - protected premises 24 hours
- central station 24 hours
- proprietary 24 hours
- auxiliary 60 hours
- remote station 60 hours
- voice evacuation 24 hours
181-5 Fundamentals
- 1-5.2.6 Secondary Supply Capacity and Sources
- at the end of the the standby period, the
secondary source shall be able to operate the
systems for - protected premises 5 minutes
- central station 5 minutes
- proprietary 5 minutes
- auxiliary 5 minutes
- remote station 5 minutes
- voice evacuation 2 hours
- is equal to 15 minutes of evacuation alarm at
maximum connected load - the following are acceptable for secondary supply
source - storage battery
- auto start, engine driven generator with FACP
having 4 hours standby and 5 minutes of alarm
capacity
191-5 Fundamentals
- 1-5.3 Compatibility
- All fire alarm devices that receive power from
SLC or IDC shall be listed with for use with
the respective FACP - 1-5.4 System Functions
- 1-5.4.1.2 As of 1/1/02 the time delay between
activation of an input device and the automatic
activation of a function shall be 10 seconds. - A-1-5.4.1.2 The 10 seconds does not include
the fan wind down, door closure, or elevator
travel, etc
201-5 Fundamentals
- 1-5.4.4 Fire Safety Function Status Indicators
- All controls provided specifically for the
purpose of manually overriding any automatic fire
safety function shall provide a visible
indication of the status of the associated
control circuits. - status indicators shall be arranged to
reflect the actual status of the associated
equipment or function - periodic testing to verify proper operation
operation of mechanical equipment . Failure to
test and maintain mechanical equipment with
potential consequences up to and including the
loss of life. -
211-5 Fundamentals
- Alarm, Supervisory, Trouble Signals
- Overview clearly indicates that these signals
shall be distinct and clearly indicated from each
other.
221-5 Fundamentals
- 1-5.4.11 Positive Alarm Sequence
- requires approval by AHJ
- alarm signal shall be answered within 15 seconds
of receipt at FACP, if not done then system
activation occurs with all associated functions - trained personnel shall have up to 180 seconds
during the alarm investigation phase to evaluate
the fire condition, and reset the system. - failure to reset with 180 seconds causes system
activation with all associated functions - second device (PAS) shall cause system activation
with all associated functions - any other initiating device actuated shall cause
system activation with all associated functions -
231-5 Fundamentals
- 1-5.6 Protection of Fire Alarm Control Unit(s)
- Definition Fire Alarm Control Unit(s)
- a system component that receives inputs from
automatic and manual fire alarm devices - might supply power to
- - detection devices
- - a transponder
- - off-premises transmitter
- might transfer power to the notification
appliances - transfer of condition to relays or devices
241-5 Fundamentals
- 1-5.6 Protection of Fire Alarm Control Unit(s)
- in areas not continuously occupied (24/7)
- smoke detection shall be required at each fire
alarm control unit - where the area is not suited for smoke
detection, then heat detector may be used - if area is not suitable for smoke detector, then
it is likely not suitable for the fire alarm
control unit - only one smoke detector required at control
unit, even if space exceeds the Standards
allowable area for smoke detector
251-5 Fundamentals
- A-1-5.7.1.2 Zone of Origination
- Floor exceeds 20k sq. ft., then divide into zones
of less than 20K sq. ft. consistent with existing
fire and smoke barriers on the floor - Consult AHJ for zoning when floor exceeds 20K sq.
ft. and no smoke or fire barriers exist - Waterflow switches should be individually zoned
that serve - Multiple floors
- Areas exceeding 20K sq. ft.
- Areas inconsistent wih established detection
system zoning -
261-5 Fundamentals
- A-1-5.7.1.2 Zone of Origination
- d) Duct smoke detectors should be individually
zoned that serve - Air handling systems serving multiple floors
- Areas exceeding 20K sq. ft.
- Areas inconsistent wih established detection
system zoning - e) Additional requirements
- If floor area exceeds 20K sq. ft., additional
zoning should be provided - Length of any zone should not exceed 300 in any
direction - If the building has automatic sprinklers
throughout, the area of the alarm zone should be
permitted to be to coincide with the allowable
area of the sprinkler zone -
271-6 Documentation
- 1-6.1 Approval and Acceptance
- Prior to Installation
- AHJ shall be notified prior to installation or
alteration of equipment - AHJ can require complete information regarding
the system or system alterations - Prior to requesting final approval
- Installing contractor shall furnish a written
statement - Installed in accordance with approved plans
- Tested in accordance with manufacturers
specifications and the appropriate NFPA standard
281-6 Documentation
- 1-6.1 Approval and Acceptance
- Record of Completion
- Can be part of the written statement that is
submitted prior to final approval by the AHJ - When multiple contractors are involved in the
installation, each shall submit a form with the
appropriate portions filled out
291-6 Documentation
- 1-6.2 Completion Documents
- Record of Completion
- Parts 1, 2, and 4 through 10 shall be completed
after the system is installed and installation
wiring has been checked - Part 3 shall be completed after the operational
acceptance tests have been completed - A preliminary copy shall be given to the system
owner, and to the AHJ, if requested after wiring
installation - A final copy shall be submitted after completion
of operational acceptance testing
301-6 Documentation
- 1-6.2 Completion Documents
- Record of Completion
- Shall be updated each time the system is modified
- Shall include a revision date
- Other documentation
- Owners manual and installation instructions
covering all system components (OMM) - Record drawings
311-6 Documentation
- 1-6.2 Completion Documents
- Central Station Fire Alarm Systems Certificated
- Systems that comply with all aspects of this code
shall be certificated by the organization that
has listed the the prime contractor. - Certification document should be located at the
FACP - The listing organization shall maintain a central
repository of certification documents for the
listed central station. This documentations
shall be accessible to the AHJ.
321-6 Documentation
- 1-6.2 Completion Documents
- Central Station Fire Alarm Systems Placarded
- Systems that comply with all aspects of this code
shall be placarded by the prime contractor to
indicated compliance. - Placard should be located at the FACP, and be a
minimum of 20 sq. - The placard shall identify
- The central station
- The prime contractor by name and telephone number
331-6 Documentation
- 1-6.3 Records
- Complete, unalterable records of the tests and
operations - Kept until the next test, and one year thereafter
- Record shall be available for examination
- If required, reported to the AHJ
- Archiving by any means, so long as a hard copy
can be provided promptly
34Chapter 2 Initiating Devices
- 2-1.3 Installation and Required Location of
Initiating Devices - where subject to mechanical damage, an initiating
device shall be protected - a mechanical guard shall be listed for use with
the detector being used - in all cases, initiating devices shall be
supported independently of their attachment to
the circuit conductors - initiating devices shall be installed in all
areas where required by other NFPA codes and
standards, or the ahj - initiating devices shall be accessible for
periodic maintenance and testing
35Chapter 2 Initiating Devices
- 2-1.4 Requirements for Smoke Heat Detectors
- Detectors shall not be recessed in the mounting
surface in any manner - Detector coverage
- Total (Complete) Coverage
- Partial Coverage
- Selective Coverage
- Supplementary (Nonrequired) Coverage
36Chapter 2 Initiating Devices
- 2-1.4 Requirements for Smoke Heat Detectors
- 2-1.4.2.1 - Total (Complete) Coverage
- included areas
- all rooms, halls, storage areas, basements,
attics, lofts, spaces above suspended ceilings,
and other subdivisions and accessible spaces
and the inside of all closets, elevator shafts,
enclosed stairways, dumbwaiter shafts, and
chutes. Inaccessible areas shall not be required
to to be protected by detectors. - Exception No. 1 If inaccessible areas contain
combustible material, they shall be made of
accessible and be protected by detector(s). -
37Chapter 2 Initiating Devices
-
- Exception No. 2 Detectors may be omitted from
combustible blind spaces where any of the
following conditions prevail - (a)ceiling is attached directly to the underside
of the supporting beams of a combustible roof or
floor deck - (b)Where the concealed space is entirely filled
with a noncombustible insulation... - (c)small, concealed spaces over rooms, space in
question does not exceed 50 ft2 (4.6 m2) in area - (d)In spaces formed by sets of facing studs or
solid joists in walls, floors, or ceilings where
the distance between the facing studs or solid
joists is less than 6 in. (150 mm)
38Chapter 2 Initiating Devices
- Exception No. 3 Detectors may be omitted from
below open grid ceilings where all of the
following conditions exist - (a) Openings of the grid are 1/4 in. (6.4 mm) or
larger in the least dimension. - (b) Thickness of the material does not exceed the
least dimension. - (c) Openings constitute at least 70 percent of
the area of the ceiling material - Exception No. 4 Concealed, accessible spaces
above suspended ceilings, used as a return air
plenum meeting the requirements of NFPA 90A,
Standard for the Installation of Air Conditioning
and Ventilating Systems, where equipped with
smoke detection at each connection from the
plenum to the central air-handling system.
39Chapter 2 Initiating Devices
- Exception No. 5 Detectors shall not be required
underneath open loading docks or platforms and
their covers and for accessible underfloor spaces
if all of the following conditions exist - (a) Space is not accessible for storage purposes
or entrance of unauthorized persons and is
protected against the accumalation of windborne
debris - (b) Space contains no equipment such as steam
pipes, electric wiring, shafting, or conveyors - (c) Floor over the space is tight
- (d) No flammable liquids are processed, handled,
or stored on the floor above. -
40Chapter 2 Initiating Devices
- 2-1.4.2.2 Partial Coverage
- If required, partial detection systems shall be
provided in all common areas and work spaces,
such as corridors, lobbies, storage rooms,
equipment rooms, and other tenantless spaces in
those environments suitable for proper detector
operation in accordance with this code. - 2-1.4.2.3 Selective Coverage
- Where codes, standards, laws, or AHJs require
the protection of selected areas only, the
specified areas shall be protected in accordance
with this code. - 2-1.4.2.4 Supplementary (Nonrequired) Coverage
- Where installed, detection that is not required
by an applicable law, code, or standard, whether
total (complete), partial, or selective coverage,
shall conform to the requirements of this code. - Exception Spacing requirements of Chapter 2
-
41UBC, Section 1004.3.4Corridors
- 1004.3.4.3 Construction
- fully enclosed by
- walls
- floor
- - ceiling
- - permitted protected openings
- - walls and ceilings of fire- resistive
materials
42UBC, Section 1004.3.4Corridors
- Exceptions4.
- Office spaces lt 100 occupants
- Entire story is fully sprinkled
- Smoke detection in the corridor
- Audible alarms in all areas served by the
corridors
43UBC, Section 1004.3.4Corridors
- Exceptions 6.
- Group B constructed as Type I, Type II-FR, Type
II-one hour construction - Corridors within office spaces of a single tenant
- Entire story is fully sprinkled
- Smoke detection in the corridor
- Audible alarms in all areas served by the
corridors
44Typical Comm. Layout
45Basic System
46With FSDs Added
47Note
- Detector spacing in corridors may go up to 41 on
center, and 20.5 from the end of the corridor. - If building is sprinkled, then many of
requirements could already be in place. - Reduced cost of construction.
48Radius to be .7 times the spacing
49Spacing for Rectangular Areas
50Fire/Smoke Damper Detection
51UBC 713.10
- Smoke dampers shall be closed by actuation of a
smoke detector installed in accordance with the
Fire Code and one of the following applicable
methods
52UBC 713.10
- damper within a duct, a smoke detector shall be
installed within 5 feet of the damper -
- Selective Coverage per NFPA 72
53Detection in Ducts w/FSD
54Recommended Placement
55UBC 713.10
- 2. damper is installed within an unducted
opening in a wall, a spot-type detector
installed within 5 feet horizontally of the
damper. - Selective Coverage per NFPA 72
56Duct up to 36
57Width up to 72
58Width Greater than 72
59(No Transcript)
60Return HVAC/Return FSD
61Supply FSD
62Shutdown
63Individual Damper Control
64Single Pt. Control
65UBC 713.10
- 3. damper is installed in a ceiling, a spot-type
detector within 5 feet of the damper. - Selective Coverage per NFPA 72
66UBC 713.10
- 4. damper in a corridor wall or ceiling, it may
be controlled by a smoke-detection system
installed in the corridor. - Partial Coverage per NFPA 72
67Corridor with FSDs Detection
68UBC 713.10
- 5. When a total-coverage smoke-detection is
provided within all areas served by an HVAC
system, dampers may be controlled by the
smoke-detection system. - Selective Coverage per NFPA 72
- Or
- Total Coverage per NFPA 72
69Mechanical Specialty Code, Section 607
- Smoke dampers shall also close whenever the
fan serving the duct system is shut off.
70- How do we shut off the HVAC systems, and what is
required?
71State of Oregon1999 Mechanical Code
- Section 606
- Smoke Detection Systems Control
72Section 606
- 606.1 Controls Required. Air Distribution
systems shall be equipped with smoke detectors
73Section 606
- 606.2.1 Return Air Systems
- return air systems
- gt 2,000 cfm
- prior to any filters, exhaust air connections,
outdoor air connections, or decontamination
equipment or appliances. -
- Exception not required where the space served
is protected by a system of area smoke detectors
The area smoke detectors shall comply with
Section 606.4.
74Single Unit Interface
75Section 606
- 606.2.2 Common Supply and Return Air Systems.
- multiple air-handling systems share common
supply or return air ducts or plenums - with a combined design capacity greater than
2,000 cfm - the return air system shall be provided with
smoke detectors in accordance with Section
606.2.1.
76Multiple Units for Same Area
77Section 606
- 606.2.3 Return Risers
- return air risers serve two or more stories
- and are part of a return air system having a
design capacity gt 15,000 cfm - smoke detectors shall be installed at each
story. - smoke detectors shall be located upstream
between the return air riser and any air ducts or
plenums.
78Multi-floor/15K cfm
79Section 606
-
- 606.3 Installation
- in accordance with NFPA 72.
- to monitor the entire airflow conveyed by the
system - Access shall be be provided
80Placement of Detector
81Issues of Duct Smoke Detectors
- NEMA Recommends six (6) widths of the duct,
downstream from any bends or turbulence causing
effect, to ensure laminar flow in duct. - Placement _at_ shaft penetrations on multi-story
buildings Functionality, code compliant, and
effective maintenance. - Size and configuration of duct work, to allow for
best detection potential.
82Section 606
- 606.4 Controls Operation
- smoke detectors shall shut down the air
distribution system. - Air distribution systems that are part of a smoke
control system shall switch to the smoke control
mode upon activation of a detector.
83Section 606
- 606.4.1 Supervision.
- shall be connected to a fire alarm system.
- shall activate a visible and audible supervisory
signal at a constantly attended location.
84Section 606
- Exceptions
- supervisory signal not required where
activates the buildings alarm-indicating
appliances.
85Section 606
- Exceptions
- In occupancies not required to be equipped with a
fire alarm system - activate a visible and audible signal in an
approved location. - Smoke detector trouble conditions shall be
identified as air duct detector trouble.
86Supervision w/o FACP
87Supervision w/FACP S/D
88- Detection for Fire/Smoke Doors per
- UFC Standard 10-2
- Section 5-11.7
89UFC Section 5-11.7
- 5-11.7.1
- door release not initiated by a fire alarm
system smoke detectors protecting areas on both
sides of the door - smoke detectors applied as specified in 5-11.7.
90Section 5-11.7
-
- 5-11.7.4.1
- be closed in response to smoke flowing in either
direction -
91(No Transcript)
92(No Transcript)
93(No Transcript)
94Section 5-11.7
- 5-11.7.4.1.3
- depth of the wall section above the door gt 60
inches - additional detectors may be required
- an engineering evaluation.
95Section 5-11.7
- 5-11.7.4.1.4
- specifically listed for door frame mounting
- a listed combination or integral detector-door
closer assembly is used - only one detector shall be required
96Section 5-11.7
- 5-11.7.4.2
- release is indicated to prevent smoke
transmission from one space to another - in one direction only
- one detector located in the space to which smoke
is to be confined shall suffice -
97(No Transcript)
98(No Transcript)
99(No Transcript)
100(No Transcript)
101Chapter 2 Initiating Devices
- 2-8 Manually Actuated Alarm-Initiating Devices
- 2-8.2.2 - Manual Pull Stations shall be located
within 5 of the exit door way on each exit on
each floor - 2-8.2.3 - Manual Pull Stations shall be mounted
on both sides of group openings over 40 in width
102Chapter 2 Initiating Devices
- 2-9 Supervisory Signal-Initiating Devices
- 2-9.2 Pressure Supervisory Signal-Initiating
Device - (a) pressure tank supervisory indicates increase
or decrease by 10 psi - (b) dry pipe supervisory indicates increase or
decrease by 10 psi - (c) steam pressure supervisory indicates a fall
below 110 of minimum operating pressure - (d) other supervisory devices shall be as
indicated by the AHJ.
103Chapter 2 Initiating Devices
- 2-9 Supervisory Signal-Initiating Devices
- 2-9.3 Water Level Supervisory Signal-Initiating
Device - (a) pressure tank supervisory indicates when
water level rises or falls by 3 - (b) other water storage supervisory indicates
when water level falls by 12 - 2-9.4 Water Temperature Supervisory
Signal-Initiating Device - (a) temperature supervisory indicates when
water temperature falls under 40 F and when
it returns to over 40 F
104Chapter 2 Initiating Devices
- 2-9 Supervisory Signal-Initiating Devices
- 2-9.4 Room Temperature Supervisory
Signal-Initiating Device - (a) temperature supervisory indicates when
room temperature falls under 40 F and when
it returns to over 40 F
105Chapters 3 5
- Chapter 3 Protected Premises Systems
- All systems essentially fall under this Chapter
of the Standard - Chapter 5 Distinguishes the difference between
the various types of systems
106Chapter 5
- Protected Premises System Complies with all
applicable chapters of NFPA 72, and does not go
to an offsite location - Central Station Service A Protected Premises
System with offsite monitoring by a UL Listed
Central station. - Remote Supervising Station A Protected Premises
System with offsite monitoring by a listed UL
Central station. - Proprietary Supervising Station A Protected
Premises System with monitoring by trained
personnel at the location, or another location of
the same owner.
107Chapter 4 Notification Appliances
- 4-2.3 Mechanical Protection
- Guards or covers shall be listed for use with
the appliance - Their effect on the appliances field of
performance shall be in accordance with listing
requirements.
108Chapter 4 Notification Appliances
- Example of private mode is a hospital patient
care area - If allowed by code or the AHJ, audible appliances
could be eliminated entirely in areas such as
surgery or critical care
109Chapter 4 Notification Appliances
- 4-3 Audible Characteristics
- 4-3.1.1 Average sound level of 105 dBA shall
require a visible signal appliance - 4-3.2 Public Mode Audible Requirements
- 4-3.2.2 - 15dBA over ambient or 5dBA above the
maximum sound level having a duration of at least
60 seconds use whichever method is greater - Exception 1 Elevator cars can meet private
mode - Exception 2 If approved by AHJ, restrooms can
meet private mode - Exception 3 If approved by AHJ, then a method
of reducing ambient noise may be employed
110Chapter 4 Notification Appliances
- 4-3 Audible Characteristics
- 4-3.3 Private Mode Audible Requirements
- 4-3.3.1 - 45 dBA _at_ 10 and no more than 120 dBA
at the minimum hearing distance - 4-3.3.2 - 10 dBA over ambient or 5dBA above the
maximum sound level having a duration of at least
60 seconds use whichever method is greater - 4-3.4 Sleeping Areas
- 15 dBA over ambient or 5dBA above the maximum
sound level having a duration of at least 60
seconds or sound level of at least 70 dBA use
whichever method is greater -
111Chapter 4 Notification Appliances
112Chapter 7 Inspection, Testing, and Maintenance
Table 7-2.2 Smoke Detectors System/Spot Must
verify entry into smoke chamber, magnet is not
acceptable Duct Type Ensure that device samples
the air stream
113Case Studies
- OR
- Also Known As
- Dont try this in your Jurisdiction, building,
design, etc.
114 115A Tale of Two Schools
- Group E, Division 3
- Same Architect
- Same MEP Consultants
- Same GC
- Same Mechanical Contractor
- But Different Jurisdictions
116A Tale of Two Schools
- Approximately 15,000 Sq. Ft.
- Single Story
- Fully Sprinkled
- Manual Pull Stations at All Exterior Exits
- Audio/Visual Appliances Throughout
- Monitoring of Sprinkler Systems and Kitchen Hood
117A Tale of Two Schools
- HVAC System
- 13 Air Handler Units
- 5 are Greater than 2000 CFM in Capacity
- 7 Units Provide Either Supply or Return Air to
the Corridor (1350 CFM at Returns) - FSDs Originally Shown on the Drawings for
Corridor
118A Tale of Two Schools
- Fire Alarm System Design
- Engineer Originally Showed Smoke Detection in
the Corridor - Also Provided Detection in Areas Deemed
Appropriate such as Laundry Room, Communications,
Staff Areas, etc - Duct Smoke Detectors on the 5 HVAC Units
119A Tale of Two Schools
- School 1
- FSDs for Corridor have been Eliminated from
Project, but Actual Designation of Egress Path
has not Changed from Corridor - AHJ has Owner Remove All Area Smoke Detectors,
Not Necessary - All FSDs Have Been Removed, Except for the Two
Servicing the Staff Restrooms, Compliance for
Detection of FSDs is not Being Met -
120A Tale of Two Schools
- School 1
- Duct Smoke Detectors for Return Air Side of HVAC
Units - Do Not Meet Spacing/Placement Requirements of
NFPA 72
121(No Transcript)
122(No Transcript)
123A Tale of Two Schools
- School 2
- FSDs for Corridor have been Eliminated from
Project, but Actual Designation of Egress Path
has not Changed from Corridor - Duct Smoke Detectors Have Been Placed on the 5
Units, Except this Time the Devices are on the
Supply Side - 3 Devices Will Probably Not Work
- 2 Will Not Work Due to the Sampling Tubes
Being Placed Parallel to Air Flow - Covers Were Left Off After Completion of
Inspection -
-
124A Tale of Two Schools
- School 2
- Temporal Code for Audible Devices are not
Synched from the FACP - When There is More Than One Audible for an Area,
the Signal Becomes Indistinct Over Time -
125A Tale of Two Schools
- MCG Solutions
- Eliminate Duct Smoke Detectors
- Provide 100 Detection in All Below Ceiling
Spaces - Interconnect HVAC Units to Provide Shutdown for
All Units Serving Same Common Space - Provide Shutdown to HVAC Units Requiring
Shutdown via Alarm of Space Detection - Provide Synchronization of Audible/Visual
Appliances
126- 2
- When is Enough, Enough?
127When is Enough, Enough?
- 20,000 Sq. Ft. plus Elementary School
- Fully Sprinkled Building
- Full 100 Detection Below Ceilings
- HVAC Ducted Supply and Returns
- Problems were Sporadic Nuisance Alarms
128Isnt this nice?
129How About that Spacing?
20 Corridor
130Think this will work?
131Or this?
132What about this?
133What happened to 6 widths downstream?
134Isnt this special???
135Spaghetti anyone?
136Recommendations
- Redo the Spacing on Area Detection
- Remove Duct Smoke Detectors
- Install Control Modules to Facilitate HVAC Unit
S/D - Install Conduit Path to NEMA 4X Boxes at Exterior
Locations
137- 3
- What About the Kitchen?
138What About the Kitchen?
- Code Essentially Requires Only that Fuel and/or
Power Be Shutoff Under the Kitchen Hood When
Discharge Occurs - What About When There is a Building Evacuation?
- Under Certain Circumstances, It May be
Adviseable to Shutdown Fuel and/or Power on
Evacuation - How to do that?
139(No Transcript)
140- 4
- Uhm, What About the Smoke Control?
141Uhm, What About the Smoke Control?
- 3 Story Atrium
- Under 1991 UBC
- Smoke Control Fans and Associated Controls Were
Forgotten - Large Areas Contiguous and Open to Atrium
- Basic Addressable System was Already Installed
142Uhm, What About the Smoke Control?
- System Required Extensive Logic Functions
- Unlock Doors, and then Force Doors Open
- Firemans Panel Required Logic Functions for
Lighting LEDs, etc - Existing FACP Was not Capable of Timed, And, Or,
and Other Logic Functions
143Uhm, What About the Smoke Control?
- Recommendations
- Added Smoke Detection to Atrium
- Added Fire/Smoke Doors to Minimize Area Adjacent
to Atrium - Designed Controls Including Positive Feedback
- Included Monitoring of Main Power Switch to
Exhaust Fans for Status
144(No Transcript)
145(No Transcript)
146(No Transcript)
147 148And Last But Not Least
- Group E, Division 1 or 2
- Type IV Construction
- Not Sprinkled
- Alarm and Detection System Installed Utilizing a
Combination Fire Alarm/Burglar Alarm System
149And Last But Not Least
- Issues
- Detection does not meet spacing requirements
- Over Reliance on Heat Detectors
- Strobes are Not Properly Sized for
Applications - System Utilizes only a Single Phone Line for
Offsite Dialing - Audible/Visual Appliances Start to Die About 2
Minutes into Alarm (probably related to voltage
drop) - Oh, and Did I Mention that My Son Goes to School
Here -
150Thank You!!!
- Miller Consulting Group, LLC
- PO Box 1076
- Newberg, OR 97132-1076
- 503.537.9200
- dcmiller_at_mcg-llc.net