Transcript and Presenter's Notes

Title: ULTIMA


1
ULTIMA OPIR-5 Open Path Gas Detector
EVERY LIFE HAS A PURPOSE
2
Contents
  1. Product Overview
  2. False Alarm Immunity
  3. Detector Placement
  4. Installation
  5. Split Concentration Range
  6. Maintenance
  7. Fault Conditions
  8. HART
  9. AMS Device Manager
  10. Applications
  11. Summary

3
ULTIMA OPIR-5 Detector
  • Description
  • Open path infrared hydrocarbon gas monitoring
    system
  • Expected Customer Benefits
  • Low power consumption
  • Dual analog outputs, ppmM and LELM
  • Light and compact design
  • Resilient to solar radiation and fog
  • Long detection range
  • Available with HART and Modbus
  • Stainless steel construction
  • Integral display

4
Performance Specifications
Specifications Ultima OPIR-5
Response time (T90, s) lt 5
Repeatability lt ? 5
Linearity ? ? 5 FS or ? 10
Path length, max (m) 150
Operating temperature range (?C) -55 to 65
Solar blind All conditions
Fog immunity 90 blockage, ? 10 acc.
Combined weight, receiver and source (kg) 11.13 (SS only)
Supply power, nominal (W) 23
Bidirectional communication HART, Modbus
Event logging and AMS Device Manager Available
5
Solar Radiation Rejection
  • The ULTIMA OPIR-5 has superior immunity to solar
    radiation and other external IR radiation sources.

6
Performance Certifications
  • The ULTIMA OPIR-5 is the worlds first and only
    open path detector to meet agency performance
    requirements on both LELm and ppmm scales

7
Detector Placement
  • Open path detectors should be installed based on
    several considerations
  • Hazard conditions within the installation area
    covered
  • Ventilation rates, direction, and presence of
    recirculation and dead zones
  • Sensitivity to low (geometric) sunlight, fog, and
    reflections
  • Powerful sources of electromagnetic emissions
    like high powered electrical towers
  • Structures that may interfere with line of sight

Health and Safety Executive, Offshore
Division, Fire and Explosion Strategy, Issue 1,
2004.
8
Installation
  • When installing an ULTIMA OPIR-5 detector, it is
    useful to consider the following
  • Vibration can create issues
  • Solid foundation improves alignment integrity
  • The longer the line of sight path, the more solid
    the foundation required
  • Maintain a 6 to 12 radius around the line of
    site beam to avoid reflective interference from
    piping and supports
  • For outdoor installations, consider maximum snow
    levels
  • Good immunity to fog, steam, and rain but
    immunity degrades over longer distances
  • Avoid pedestrian traffic or overhead cranes
  • Keep beam low and down wind for heavy gases like
    propane and high for light gases like methane

9
Wiring
9 10 11 12 13 14 15 16
24V COM 0 20 mA L COM 0 20 mA P COM RST COM
8 MOD1- Modbus 1- Modbus 2- MOD2- 17
7 MOD1 Modbus1 Modbus 2 MOD2 18
6 A2 Alarm NO/NC Fault NO FLT1 19
5 AC Alarm C Fault C FLTC 20
4 A1 Alarm NC/NO Fault NC FLT2 21
3 W2 L Warn NO/NC Warn NC/NO W2 P 22
2 WC L Warn C Warn C WC P 23
1 W1 L Warn NC/NO Warn NC/NO W1 P 24
Ultima OPIR-5 Receiver
10
Split Concentration Range
  • With the split range function, users can monitor
    the entire span of gas concentration with a
    single analog signal
  • Reduces wiring and commissioning costs

11
Alignment
  • Simple alignment process
  • Arm or base mounts available
  • Display
  • Menus activated by magnet
  • Enables easy alignment, setup diagnostics

12
Maintenance
  • As with other combustible sensors, the ULTIMA
    OPIR-5 should be included in the plant
    maintenance schedule
  • Gas check frequency depends on operating
    conditions (ex. dusty, corrosive, or damp
    environment)
  • Before repair or maintenance, the gas detector
    should be removed to a safe place outside the
    area being protected
  • If the hazard is still potentially present, it
    will be necessary to use a replacement gas
    detector in the area until the original detector
    is reinstated

BS EN 500731999 Guide for the selection,
installation, use and maintenance of apparatus
for the detection and measurement of combustible
gases or oxygen.
13
Diagnostics
  • The ULTIMA OPIR-5 has self-diagnostics that
    inform users when certain types of device
    failures have occurred

Fault Code Description
F0 Excessive negative drift or high IR
F1 Partial beam block or dirty lens
F2 Alignment
F3 Beam block
F5 Setup menu not exited
F6 Low supply voltage
F7 Heater error
F8 Failed zeroing
F9 Gas left (timeout)
F10 Reset short
F11 Unit overheating
tF7 Source internal error
14
HART
  • The ULTIMA OPIR-5 is available with HART for
    better efficiency with remote communication
  • Only the primary scale, LELm or split range,
    connects through HART
  • Benefits of the HART-equipped ULTIMA OPIR-5
  • Better diagnostics
  • Improved management of maintenance history and
    event logging
  • Flexible and accurate digital transmission
  • Effective cost control of devices in the field
  • Installation savings due to fewer wires

15
HART Analog Signal for Faults
  • Because HART requires a minimum current for
    operation, the ULTIMA OPIR-5s fault conditions
    use 3.5 mA as minimum analog output

Function Current Level (mA) Current Level (mA) Current Level (mA) Current Level (mA)
Function Analog Output (Standard) Modbus HART (Default) HART-modified Analog Output
Fault 0 0 3.5 1.25
Test Gas 1.5 1.5 3.5 1.5
Setup Mode 1.5 1.5 3.5 1.5
Beam Block 2.0 2.0 3.5 2.0
Startup 0 0 3.5 1.25
Zero Reading 4.04 4.04 4.04 4.04
Gas Concentration 4 20 4 20 4 20 4 20
Over-range 21.7 21.7 21.7 21.7
On HART-equipped unit, user must select the
HART-modified AO in order use AO values below 3.5
mA
16
AMS Device Manager
  • Asset management and process improvement
  • Check compliance to calibration schedule
  • Coordinate calibrations so as to reduce labor
    cost
  • Aggregate calibration to a control room
  • Track gas level remotely
  • Read fault conditions from control room before
    sending technician to the field

17
Ultima OPIR-5 Summary
  • Ultima OPIR-5 Open Path IR Detector
  • Detects ppmMeter LELMeter
  • Path Length up to 150 M
  • Wide Temperature range
  • Global Approvals
  • Integral Display - Easy alignment, diagnostics
    and maintenance