ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES - PowerPoint PPT Presentation

About This Presentation
Title:

ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES

Description:

environmental engineering concrete structures ce 498 design project september 26, 2006 outline introduction performance criteria design loads and conditions ... – PowerPoint PPT presentation

Number of Views:297
Avg rating:3.0/5.0
Slides: 58
Provided by: engineeri46
Category:

less

Transcript and Presenter's Notes

Title: ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES


1
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES
  • CE 498 Design Project
  • September 26, 2006

2
OUTLINE
  • INTRODUCTION
  • PERFORMANCE CRITERIA
  • DESIGN LOADS AND CONDITIONS
  • STRUCTURAL DESIGN
  • CONCRETE MIX DESIGN
  • ADDITIONAL CRITERIA

3
INTRODUCTION
  • Why concrete?
  • Concrete is particularly suited for this
    application because it will not warp or undergo
    change in dimensions
  • When properly designed and placed it is nearly
    impermeable and extremely resistant to corrosion
  • Has good resistance to natural and processing
    chemicals
  • Economical but requires significant quality
    control
  • What type of structure?
  • Our focus will be conventionally reinforced
    cast-in-place or precast concrete structures
  • Basically rectangular and/or circular tanks
  • No prestressed tanks

4
INTRODUCTION
  • How should we calculate loads?
  • Design loads determined from the depth and unit
    weight of retained material (liquid or solid),
    the external soil pressure, and the equipment to
    be installed
  • Compared to these loads, the actual live loads
    are small
  • Impact and dynamical loads from some equipments
  • What type of analysis should be done?
  • The analysis must be accurate to obtain a
    reasonable picture of the stress distribution
    in the structure, particularly the tension
    stresses
  • Complicated 3D FEM analysis are not required.
    Simple analysis using tabulated results in
    handbooks etc.

5
PERFORMANCE CRITERIA
  • What are the objective of the design?
  • The structure must be designed such that it is
    watertight, with minimum leakage or loss of
    contained volume.
  • The structure must be durable it must last for
    several years without undergoing deterioration
  • How do you get a watertight structure?
  • Concrete mix design is well-proportioned and it
    is well consolidated without segregation
  • Crack width is minimized
  • Adequate reinforcing steel is used
  • Impervious protective coating or barriers can
    also be used
  • This is not as economical and dependable as the
    approach of mix design, stress crack control,
    and adequate reinforcem.

6
PERFORMANCE CRITERIA
  • How to design the concrete mix?
  • The concrete mix can be designed to have low
    permeability by using low water-cement ratio and
    extended periods of moist curing
  • Use water reducing agents and pozzolans to reduce
    permeability.
  • How to reduce cracking?
  • Cracking can be minimized by proper design,
    distribution of reinforcement, and joint spacing.
  • Shrinkage cracking can be minimized by using
    joint design and shrinkage reinforcement
    distributed uniformly

7
PERFORMANCE CRITERIA
  • How to increase durability?
  • Concrete should be resistant to the actions of
    chemicals, alternate wetting and drying, and
    freeze-thaw cycles
  • Air-entrainment in the concrete mix helps improve
    durability. Add air-entrainment agents
  • Reinforcement must have adequate cover to prevent
    corrosion
  • Add good quality fly-ash or pozzolans
  • Use moderately sulphate-resistant cement

8
DESIGN LOADS AND CONDITIONS
  • All the loads for the structure design can be
    obtained from ASCE 7 (2006), which is the
    standard for minimum design loads for building
    structures endorsed by IBC
  • Content loads
  • Raw Sewage 63 lb/ft3
  • Grit from grit chamber .. 110 lb/ft3
  • Digested sludge aerobic. 65 lb/ft3
  • Digested sludge anerobic 70 lb/ft3
  • For other numbers see ACI 350.
  • Live loads
  • Catwalks etc 100 lb/ft2
  • Heavy equipment room 300 lb/ft2

9
DESIGN LOADS AND CONDITIONS
  • When using the LRFD (strength or limit states
    design approach), the load factors and
    combinations from ACI 318 can be used directly
    with one major adjustment
  • The load factors for both the lateral earth
    pressure H and the lateral liquid pressure F
    should be taken as 1.7
  • The factored load combination U as prescribed in
    ACI 318 must be increased by durability
    coefficients developed from crack width
    calculation methods
  • In calculations for reinforcement in flexure, the
    required strength should be 1.3 U
  • In calculations for reinforcement in direct
    tension, including hoop tension, the required
    strength should be 1.65 U
  • The required design strength for reinforcement in
    shear should be calculated as fVsgt 1.3 (Vu-fVc)
  • For compression use 1.0 U

10
STRUCTURAL DESIGN
  • Large reinforced concrete reservoirs on
    compressible soil may be considered as beams on
    elastic foundations.
  • Sidewalls of rectangular tanks and reservoirs can
    be designed as either (a) cantilever walls fixed
    at the bottom, or (b) walls supported at two or
    more edges.
  • Circular tanks normally resist the pressure from
    contents by ring tension
  • Walls supporting both interior water loads and
    exterior soil pressure must be designed to
    support the full effects of each load
    individually
  • Cannot use one load to minimize the other,
    because sometimes the tank is empty.

11
STRUCTURAL DESIGN
  • Large diameter tanks expand and contract
    appreciably as they are filled and drained.
  • The connection between wall and footing should
    either permit these movements or be strong enough
    to resist them without cracking
  • The analysis of rectangular wall panels supported
    at three or four sides is explained in detail in
    the PCA publication that is available in the
    library and on hold for the course
  • It contains tabulated coefficients for
    calculating stress distributions etc. for
    different boundary conditions and can be used
    directly for design
  • It also includes some calculation and design
    examples

12
STRUCTURAL DESIGN
  • Reinforced concrete walls at least 10 ft. high
    that are in contact with liquids should have a
    minimum thickness of 12 in.
  • The minimum thickness of any minor member is 6
    in., and when 2 in. cover is required then it is
    at least 8 in.
  • For crack control, it is preferable to use a
    large number of small diameter bars for main
    reinforcement rather than an equal are of larger
    bars
  • Maximum bar spacing should not exceed 12 in.
  • The amount of shrinkage and temperature
    reinforcement is a function of the distance
    between joints in the direction
  • Shrinkage and temperature reinforcement should
    not be less thank the ratios given in Figure 2.5
    or ACI 350
  • The reinforcement should not be spaced more than
    12 in. and should be divided equally between the
    two surfaces

13
STRUCTURAL DESIGN
  • Figure showing minimum shrinkage reinforcement
    and table showing minimum cover for reinforcement
    required

14
STRUCTURAL DESIGN
  • In order to prevent leakage, the strain in the
    tension reinforcement has to be limited
  • The strain in the reinforcing bars is transferred
    to the surrounding concrete, which cracks.
  • Hence, minimizing the stress and strain in the
    reinforcing bar will minimize cracking in the
    concrete.
  • Additionally, distributing the tension
    reinforcement will engage a greater area of the
    concrete in carrying the strain, which will
    reduce cracking even more.
  • The strength design requires the use of loads,
    load combinations and durability coefficients
    presented earlier

15
STRUCTURAL DESIGN
  • Serviceability for normal exposures
  • For flexural reinforcement located in one layer,
    the quantity Z (crack control factor of ACI)
    should not exceed 115 kips/in.
  • The designer can use the basic Gergley-Lutz
    equation for crack width for one way flexural
    members.
  • The reinforcement for two-way flexural member may
    be proportioned in each direction using the above
    recommendation too.
  • Alternate design by the working stress method
    with allowable stress values given and tabulated
    in ACI 350. Do not recommend this method for us.

16
STRUCTURAL DESIGN
  • Impact, vibration, and torque issues
  • When heavy machines are involved, an appropriate
    impact factor of 1.25 can be used in the design
  • Most of the mechanical equipment such as
    scrapers, clarifiers, flocculators, etc. are slow
    moving and will not cause structural vibrations
  • Machines that cause vibration problems are
    forced-draft fans and centrifuges for dewatering
    clarifier sludge or digester sludge
  • The key to successful dynamic design is to make
    sure that the natural frequency of the support
    structure is significantly different from
    frequency of disturbing force

17
STRUCTURAL DESIGN
  • To minimize resonant vibrations, ratio of the
    natural frequency of the structure to the
    frequency of the disturbing force must not be in
    the range of 0.5 to 1.5.
  • It should preferably be greater than 1.5
  • Methods for computing the structure frequency are
    presented in ACI 350 (please review if needed)
  • Torque is produced in most clarifiers where the
    entire mechanism is supported on a central column
  • This column must be designed to resist the torque
    shear without undergoing failure

18
MATERIAL DESIGN
  • The cement should conform to
  • Portland cement ASTM C150, Types I, IA, II, IIA,
    .
  • Blended hydraulic cement ASTM C595
  • Expansive hydraulic cement ASTM C845
  • They cannot be used interchangeably in the same
    structure
  • Sulfate-resistant cement must have C3A content
    not exceeding 8. This is required for concrete
    exposed to moderate sulfate acctak (150 to 1000
    ppm)
  • Portland blast furnace slab cement (C595 may be
    used)
  • Portland pozzolan cement (C595 IP) can also be
    used
  • But, pozzolan content not exceed 25 by weight of
    cementitous materials

19
MATERIAL DESIGN
  • The air entraining admixture should conform to
    ASTM C260
  • Improves resistant to freeze-thaw cycles
  • Improves workability and less shrinkage
  • If chemical admixtures are used, they should meet
    ASTM C494. The use of water reducing admixtures
    is recommended
  • The maximum water-soluble chloride ion content,
    expressed as a of cement, contributed by all
    ingredients of the concrete mix should not exceed
    0.10

20
MATERIAL DESIGN
  • Mix proportioning all material should be
    proportioned to produce a well-graded mix of high
    density and workability
  • 28 day compressive strength of 3500 psi where the
    concrete is not exposed to severe weather and
    freeze-thaw
  • 28 day compressive strength of 4000 psi where the
    concrete is exposed to severe weather and
    freeze-thaw
  • Type of cement as mentioned earlier
  • Maximum water-cement ratio 0.45
  • If pozzolan is used, the maximum water-cement
    pozzolan ratio should be 0.45
  • Minimum cementitious material content
  • 1.5 in. aggregate max 517 lb/yd3
  • 1 in. aggregate max 536 lb/yd3
  • 0.75 in. aggregate max 564 lb/yd3

21
MATERIAL DESIGN
  • Air entrainment requirements
  • 5.5 1 for 1.5 in. aggregate
  • 6.0 1 for 1.0 or 0.75 in. aggregate
  • Slump requirements
  • 1 in. minimum and 4 in. maximum
  • Concrete placement according to ACI 350 (read
    when you get a chance)
  • Curing using sprinkling, ponding, using moisture
    retaining covers, or applying a liquid
    membrane-forming compound seal coat
  • Moist or membrane curing should commence
    immediately after form removal

22
ADDITIONAL CRITERIA
  • Concrete made with proper material design will be
    dense, watertight, and resistant to most chemical
    attack. Under ordinary service conditions, it
    does not require additional protection against
    chemical deterioration or corrosion
  • Reinforcement embedded in quality concrete is
    well protected against corrosive chemicals
  • There are only special cases where additional
    protective coatings or barriers are required
  • The steel bars must be epoxy coated (ASTM A775)
  • In special cases, where H2S evolves in a stagnant
    unventilated environment that is difficult or
    uneconomical to correct or clean regularly, a
    coating may be required

23
REFERENCES
  • ACI 350 (1989)
  • Books on reserve in the library
  • Emails from Jeffrey Ballard, structural engineer,
    HNTB. He will visit to talk with us soon.

24
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES
  • CE 498 Design Project
  • November 16, 21, 2006

25
OUTLINE
  • INTRODUCTION
  • LOADING CONDITIONS
  • DESIGN METHOD
  • WALL THICKNESS
  • REINFORCEMENT
  • CRACK CONTROL

26
INTRODUCTION
  • Conventionally reinforced circular concrete tanks
    have been used extensively. They will be the
    focus of our lecture today
  • Structural design must focus on both the strength
    and serviceability. The tank must withstand
    applied loads without cracks that would permit
    leakage.
  • This is achieved by
  • Providing proper reinforcement and distribution
  • Proper spacing and detailing of construction
    joints
  • Use of quality concrete placed using proper
    construction procedures
  • A thorough review of the latest report by ACI 350
    is important for understanding the design of
    tanks.

27
LOADING CONDITIONS
  • The tank must be designed to withstand the loads
    that it will be subjected to during many years of
    use. Additionally, the loads during construction
    must also be considered.
  • Loading conditions for partially buried tank.
  • The tank must be designed and detailed to
    withstand the forces from each of these loading
    conditions

28
LOADING CONDITIONS
  • The tank may also be subjected to uplift forces
    from hydrostatic pressure at the bottom when
    empty.
  • It is important to consider all possible loading
    conditions on the structure.
  • Full effects of the soil loads and water pressure
    must be designed for without using them to
    minimize the effects of each other.
  • The effects of water table must be considered for
    the design loading conditions.

29
DESIGN METHODS
  • Two approaches exist for the design of RC members
  • Strength design, and allowable stress design.
  • Strength design is the most commonly adopted
    procedure for conventional buildings
  • The use of strength design was considered
    inappropriate due to the lack of reliable
    assessment of crack widths at service loads.
  • Advances in this area of knowledge in the last
    two decades has led to the acceptance of strength
    design methods
  • The recommendations for strength design suggest
    inflated load factors to control service load
    crack widths in the range of 0.004 0.008 in.

30
Design Methods
  • Service state analyses of RC structures should
    include computations of crack widths and their
    long term effects on the structure durability and
    functional performance.
  • The current approach for RC design include
    computations done by a modified form of elastic
    analysis for composite reinforced steel/concrete
    systems.
  • The effects of creep, shrinkage, volume changes,
    and temperature are well known at service level
  • The computed stresses serve as the indices of
    performance of the structure.

31
DESIGN METHODS
  • The load combinations to determine the required
    strength (U) are given in ACI 318. ACI 350
    requires two modifications
  • Modification 1 the load factor for lateral
    liquid pressure is taken as 1.7 rather than 1.4.
    This may be over conservative due to the fact
    that tanks are filled to the top only during leak
    testing or accidental overflow
  • Modification 2 The members must be designed to
    meet the required strength. The ACI required
    strength U must be increased by multiplying with
    a sanitary coefficient
  • The increased design loads provide more
    conservative design with less cracking.
  • Required strength Sanitary coefficient X U
  • Where, sanitary coefficient 1.3 for flexure,
    1.65 for direct tension, and 1.3 for shear beyond
    the capacity provided by the concrete.

32
WALL THICKNESS
  • The walls of circular tanks are subjected to ring
    or hoop tension due to the internal pressure and
    restraint to concrete shrinkage.
  • Any significant cracking in the tank is
    unacceptable.
  • The tensile stress in the concrete (due to ring
    tension from pressure and shrinkage) has to kept
    at a minimum to prevent excessive cracking.
  • The concrete tension strength will be assumed 10
    fc in this document.
  • RC walls 10 ft. or higher shall have a minimum
    thickness of 12 in.
  • The concrete wall thickness will be calculated as
    follows

33
WALL THICKNESS
  • Effects of shrinkage
  • Figure 2(a) shows a block of concrete with a
    re-bar. The block height is 1 ft, t corresponds
    to the wall thickness, the steel area is As, and
    the steel percentage is r.
  • Figure 2(b) shows the behavior of the block
    assuming that the re-bar is absent. The block
    will shorten due to shrinkage. C is the shrinkage
    per unit length.
  • Figure 2(c) shows the behavior of the block when
    the re-bar is present. The re-bar restrains some
    shortening.
  • The difference in length between Fig.2(b) and
    2(c) is xC, an unknown quantity.

34
WALL THICKNESS
  • The re-bar restrains shrinkage of the concrete.
    As a result, the concrete is subjected to
    tension, the re-bar to compression, but the
    section is in force equilibrium
  • Concrete tensile stress is fcs xCEc
  • Steel compressive stress is fss (1-x)CEs
  • Section force equilibrium. So, rfssfcs
  • Solve for x from above equation for force
    equilibrium
  • The resulting stresses are
  • fssCEs1/(1nr) and fcsCEsr/(1nr)
  • The concrete stress due to an applied ring or
    hoop tension of T will be equal to
  • T Ec/(EcAcEsAs) T 1/AcnAs
    T/Ac(1nr)
  • The total concrete tension stress CEsAs
    T/AcnAs

35
WALL THICKNESS
  • The usual procedure in tank design is to provide
    horizontal steel As for all the ring tension at
    an allowable stress fs as though designing for a
    cracked section.
  • Assume AsT/fs and realize Ac12t
  • Substitute in equation on previous slide to
    calculate tension stress in the concrete.
  • Limit the max. concrete tension stress to fc
    0.1 fc
  • Then, the wall thickness can be calculated as
  • t CEsfsnfc/12fcfs T
  • This formula can be used to estimate the wall
    thickness
  • The values of C, coefficient of shrinkage for RC
    is in the range of 0.0002 to 0.0004.
  • Use the value of C0.0003
  • Assume fs allowable steel tension 18000 psi
  • Therefore, wall thickness t0.0003 T

36
WALL THICKNESS
  • The allowable steel stress fs should not be made
    too small. Low fs will actually tend to increase
    the concrete stress and potential cracking.
  • For example, the concrete stress fc
    CEsfs/AcfsnTT
  • For the case of T24,000 lb, n8, Es29106 psi,
    C0.0003 and Ac12 x 10 120 in3
  • If the allowable steel stress is reduced from
    20,000 psi to 10,000 psi, the resulting concrete
    stress is increased from 266 psi to 322 psi.
  • Desirable to use a higher allowable steel stress.

37
REINFORCEMENT
  • The amount size and spacing of reinforcement has
    a great effect on the extent of cracking.
  • The amount must be sufficient for strength and
    serviceability including temperature and
    shrinkage effects
  • The amount of temperature and shrinkage
    reinforcement is dependent on the length between
    construction joints

38
REINFORCEMENT
  • The size of re-bars should be chosen recognizing
    that cracking can be better controlled by using
    larger number of small diameter bars rather than
    fewer large diameter bars
  • The size of reinforcing bars should not exceed
    11. Spacing of re-bars should be limited to a
    maximum of 12 in. Concrete cover should be at
    least 2 in.
  • In circular tanks the locations of horizontal
    splices should be staggered by not less than one
    lap length or 3 ft.
  • Reinforcement splices should confirm to ACI 318
  • Chapter 12 of ACI 318 for determining splice
    lengths.
  • The length depends on the class of splice, clear
    cover, clear distance between adjacent bars, and
    the size of the bar, concrete used, bar coating
    etc.

39
CRACK CONTROL
  • Crack widths must be minimized in tank walls to
    prevent leakage and corrosion of reinforcement
  • A criterion for flexural crack width is provided
    in ACI 318. This is based on the Gergely-Lutz
    equation zfs(dcA)1/3
  • Where z quantity limiting distribution of
    flexural re-bar
  • dc concrete cover measured from extreme tension
    fiber to center of bar located closest.
  • A effective tension area of concrete
    surrounding the flexural tension reinforcement
    having the same centroid as the reinforcement,
    divided by the number of bars.

40
CRACK CONTROL
  • In ACI 350, the cover is taken equal to 2.0 in.
    for any cover greater than 2.0 in.
  • Rearranging the equation and solving for the
    maximum bar spacing give max spacing z3/(2 dc2
    fs3)
  • Using the limiting value of z given by ACI 350,
    the maximum bar spacing can be computed
  • For ACI 350, z has a limiting value of 115 k/in.
  • For severe environmental exposures, z 95 k/in.

41
ANALYSIS OF VARIOUS TANKS
  • Wall with fixed base and free top triangular
    load
  • Wall with hinged base and free top triangular
    load and trapezoidal load
  • Wall with shear applied at top
  • Wall with shear applied at base
  • Wall with moment applied at top
  • Wall with moment applied at base

42
CIRCULAR TANK ANALYSIS
  • In practice, it would be rare that a base would
    be fixed against rotation and such an assumption
    would lead to an improperly designed wall.
  • For the tank structure, assume
  • Height H 20 ft.
  • Diameter of inside D 54 ft.
  • Weight of liquid w 62.5 lb/ft3
  • Shrinkage coefficient C 0.0003
  • Elasticity of steel Es 29 x 106 psi
  • Ratio of Es/Ec n 8
  • Concrete compressive strength fc 4000 psi
  • Yield strength of reinforcement fy 60,000 psi

43
CIRCULAR TANK ANALYSIS
  • It is difficult to predict the behavior of the
    subgrade and its effect upon restraint at the
    base. But, it is more reasonable to assume that
    the base is hinged rather than fixed, which
    results in more conservative design.
  • For a wall with a hinged base and free top, the
    coefficients to determine the ring tension,
    moments, and shears in the tank wall are shown in
    Tables A-5, A-7, and A-12 of the Appendix
  • Each of these tables, presents the results as
    functions of H2/Dt, which is a parameter.
  • The values of thickness t cannot be calculated
    till the ring tension T is calculated.
  • Assume, thickness t 10 in.
  • Therefore, H2/Dt (202)/(54 x 10/12) 8.89
    (approx. 9 in.)

44
Table A-5 showing the ring tension values
45
Table A-7, A-12 showing the moment and shear
46
CIRCULAR TANK ANALYSIS
  • In these tables, 0.0 H corresponds to the top of
    the tank, and 1.0 H corresponds to the bottom of
    the tank.
  • The ring tension per foot of height is computed
    by multiplying wu HR by the coefficients in Table
    A-5 for the values of H2/Dt9.0
  • wu for the case of ring tension is computed as
  • wu sanitary coefficient x (1.7 x Lateral
    Forces)wu 1.65 x (1.7 x 62.5) 175.3 lb/ft3
  • Therefore, wu HR 175.3 x 20 x 54/2 94, 662
    lb/ft3
  • The value of wu HR corresponds to the behavior
    where the base is free to slide. Since, it cannot
    do that, the value of wu HR must be multiplied by
    coefficients from Table A-5

47
CIRCULAR TANK ANALYSIS
  • A plus sign indicates tension, so there is a
    slight compression at the top, but it is very
    small.
  • The ring tension is zero at the base since it is
    assumed that the base has no radial displacement
  • Figure compares the ring tension for tanks with
    free sliding base, fixed base, and hinged base.

48
CIRCULAR TANK ANALYSIS
  • Which case is conservative? (Fixed or hinged
    base)
  • The amount of ring steel required is given by
  • As maximum ring tension / (0.9 Fy)
  • As 67494/(0.9 60000) 1.25 in2/ft.
  • Therefore at 0.7H use 6bars spaced at 8 in. on
    center in two curtains.
  • Resulting As 1.32in2/ft.
  • The reinforcement along the height of the wall
    can be determined similarly, but it is better to
    have the same bar and spacing.
  • Concrete cracking check
  • The maximum tensile stress in the concrete under
    service loads including the effects of shrinkage
    is
  • fc CEsAs Tmax, unfactored/AcnAs 272
    psi lt 400 psi
  • Therefore, adequate

49
CIRCULAR TANK ANALYSIS
  • The moments in vertical wall strips that are
    considered 1 ft. wide are computed by multiplying
    wuH3 by the coefficients from table A-7.
  • The value of wu for flexure sanitary
    coefficient x (1.7 x lateral forces)
  • Therefore, wu 1.3 x 1.7 x 62.5 138.1 lb/ft3
  • Therefore wuH3 138.1 x 203 1,104,800 ft-lb/ft
  • The computed moments along the height are shown
    in the Table.
  • The figure includes the moment for both the
    hinged and fix conditions

50
CIRCULAR TANK ANALYSIS
  • The actual restraint is somewhere in between
    fixed and hinged, but probably closer to hinged.
  • For the exterior face, the hinged condition
    provides a conservative although not wasteful
    design
  • Depending on the fixity of the base, reinforcing
    may be required to resist moment on the interior
    face at the lower portion of the wall.
  • The required reinforcement for the outside face
    of the wall for a maximum moment of 5,524
    ft-lb/ft. is
  • Mu/(f fc bd2) 0.0273 (where d t cover
    dbar/2)
  • From the standard design aid of Appendix A, take
    the value of 0.0273 and obtain a value for w from
    the Table.
  • Obtain w0.0278
  • Required As w bdfc/fy 0.167 in2

51
CIRCULAR TANK ANALYSIS
  • r0.167/(12 x 7.5) 0.00189
  • rmin 200/Fy 0.0033 gt 0.00189
  • Use 5 bars at the maximum allowable spacing of
    12 in.
  • As 0.31 in2 and r 0.0035
  • The shear capacity of a 10 in. wall with fc4000
    psi is
  • Vc 2 (fc)0.5 bwd 11,384 kips
  • Therefore, f Vc 0.85 x 11,284 9676 kips
  • The applied shear is given by multiplying wu H2
    with the coefficient from Table A-12
  • The value of wu is determined with sanitary
    coefficient 1.0 (assuming that no steel rft.
    will be needed)
  • wuH2 1.0 x 1.7 x 62.5 x 202 42,520 kips
  • Applied shear Vu 0.092 x wuH2 3912 kips lt
    fVc

52
RECTANGULAR TANK DESIGN
  • The cylindrical shape is structurally best suited
    for tank construction, but rectangular tanks are
    frequently preferred for specific purposes
  • Rectangular tanks can be used instead of circular
    tanks when the footprint needs to be reduced
  • Rectangular tanks are used where partitions or
    tanks with more than one cell are needed.
  • The behavior of rectangular tanks is different
    from the behavior of circular tanks
  • The behavior of circular tanks is axisymmetric.
    That is the reason for our analysis of only unit
    width of the tank
  • The ring tension in circular tanks was uniform
    around the circumference

53
RECTANGULAR TANK DESIGN
  • The design of rectangular tanks is very similar
    in concept to the design of circular tanks
  • The loading combinations are the same. The
    modifications for the liquid pressure loading
    factor and the sanitary coefficient are the same.
  • The major differences are the calculated moments,
    shears, and tensions in the rectangular tank
    walls.
  • The requirements for durability are the same for
    rectangular and circular tanks. This is related
    to crack width control, which is achieved using
    the Gergely Lutz parameter z.
  • The requirements for reinforcement (minimum or
    otherwise) are very similar to those for circular
    tanks.
  • The loading conditions that must be considered
    for the design are similar to those for circular
    tanks.

54
RECTANGULAR TANK DESIGN
  • The restraint condition at the base is needed to
    determine deflection, shears and bending moments
    for loading conditions.
  • Base restraint conditions considered in the
    publication include both hinged and fixed edges.
  • However, in reality, neither of these two
    extremes actually exist.
  • It is important that the designer understand the
    degree of restraint provided by the reinforcing
    that extends into the footing from the tank wall.
  • If the designer is unsure, both extremes should
    be investigated.
  • Buoyancy Forces must be considered in the design
    process
  • The lifting force of the water pressure is
    resisted by the weight of the tank and the weight
    of soil on top of the slab

55
RECTANGULAR TANK BEHAVIOR
Mx moment per unit width about the x-axis
stretching the fibers in the y direction when the
plate is in the x-y plane. This moment determines
the steel in the y (vertical direction).
My moment per unit width about the y-axis
stretching the fibers in the x direction when the
plate is in the x-y plane. This moment determines
the steel in the x (horizontal direction).
Mz moment per unit width about the z-axis
stretching the fibers in the y direction when the
plate is in the y-z plane. This moment determines
the steel in the y (vertical direction).
56
RECTANGULAR TANK BEHAVIOR
  • Mxy or Myz torsion or twisting moments for
    plate or wall in the x-y and y-z planes,
    respectively.
  • All these moments can be computed using the
    equations
  • Mx(Mx Coeff.) x q a2/1000
  • My(My Coeff.) x q a2/1000
  • Mz(Mz Coeff.) x q a2/1000
  • Mxy(Mxy Coeff.) x q a2/1000
  • Myz(Myz Coeff.) x q a2/1000
  • These coefficients are presented in Tables 2 and
    3 for rectangular tanks
  • The shear in one wall becomes axial tension in
    the adjacent wall. Follow force equilibrium -
    explain in class.

57
RECTANGULAR TANK BEHAVIOR
  • The twisting moment effects such as Mxy may be
    used to add to the effects of orthogonal moments
    Mx and My for the purpose of determining the
    steel reinforcement
  • The Principal of Minimum Resistance may be used
    for determining the equivalent orthogonal moments
    for design
  • Where positive moments produce tension
  • Mtx Mx Mxy
  • Mty My Mxy
  • However, if the calculated Mtx lt 0,
  • then Mtx0 and MtyMy Mxy2/Mx gt 0
  • If the calculated Mty lt 0
  • Then Mty 0 and Mtx Mx Mxy2/My gt 0
  • Similar equations for where negative moments
    produce tension
Write a Comment
User Comments (0)
About PowerShow.com