Optimizing Central Chilled Water Systems - PowerPoint PPT Presentation

1 / 35
About This Presentation
Title:

Optimizing Central Chilled Water Systems

Description:

Chilled water required for each building is determined by the building block cooling load ... Central plant chilled water system load diversity for multiple building ... – PowerPoint PPT presentation

Number of Views:1534
Avg rating:3.0/5.0
Slides: 36
Provided by: kent185
Category:

less

Transcript and Presenter's Notes

Title: Optimizing Central Chilled Water Systems


1
Optimizing CentralChilled Water Systems
  • Kent W. Peterson, P.E.
  • P2S Engineering, Inc.

2
Everything should be as simple as possible, but
no simpler - Albert Einstein
3
Foundation of Design
  • Goal -
  • Why look outside the plant?
  • Understand how loads impact plant operation
  • Understand how distribution system will operate
  • Understand how temperature differential will be
    effected by dynamics of system
  • Apply findings to chilled water system operation

Deliver CHW to all loads under various load
conditions as efficiently as possible throughout
the year
4
Chilled Water Plant Efficiency
  • Target kW/ton achievable in modern plants
    (includes chillers, cooling towers and pumps)
  • 0.5 - 0.7 Excellent
  • 0.7 - 0.85 Good
  • gt1.0 Needs Improvement
  • Do you know how your plant is performing?

5
Typical Facility Load Information
  • Chilled water required for each building is
    determined by the building block cooling load
  • Central chiller plant loads depend on the actual
    simultaneous load expected at the central plant
  • Central plant chilled water system load diversity
    for multiple building facilities varies between
    55-75

6
Understanding Loads
  • Estimated annual load profiles must be understood
    to design a chilled water system that will meet
    your performance expectations
  • Valuable data to measure and trend
  • Chilled water load profiles
  • Anticipated load diversity
  • Know your facility central plant diversity
  • Usually 400-500 GSF/ton

7
Understanding Hydronics
  • The pumping system will be required to operate
    under various load conditions
  • Variable flow system differential pressures
    throughout the system can be very dynamic
  • Hydronic system modeling should be used to design
    or troubleshoot complex piping distribution
    systems under various load conditions

8
Purpose of Pumping Systems
  • Purpose is to move enough water through system at
    a differential pressure that will satisfy all
    connected loads
  • CAUTION - Over sizing pumps can cause systems to
    not function as designed and waste considerable
    energy

9
Hydronic Fundamentals
Variable Flow System Dynamics
10
Hydronic Fundamentals
Variable Flow System Dynamics
11
Balancing Considerations
Variable Flow Systems
  • Too large a balancing valve pressure drop will
    affect the performance and flow characteristic of
    the control valve.
  • ASHRAE 2003 Applications Handbook, page 37.8
  • Options to Consider
  • No balancing valves, no balancing
  • Automatic differential pressure control valves to
    control differential pressure at close loads
  • Pressure-independent control valves
  • Options NOT to Consider
  • Balancing valves at variable speed pumps

12
Hydronic Pumping Conclusions
  • Coil heat transfer is easier to control in low
    head (lt50 ft head) systems
  • Remote, high head loads can be served more
    efficiently with variable speed series booster
    pumping
  • Looped systems can offer redundancy and reduced
    differential pressure in mains

13
CHW Temperature Differential
  • Lack of chilled water ?T is the largest
    contributor to poor chilled water plant
    performance
  • To predict ?T, you must know
  • Characteristics of cooling coils in system
  • Control valve requirements and limitations
  • Control valve control algorithms and setpoints
  • Load characteristics on coil

14
CHW Temperature Differential
  • Cooling Coil Characteristics
  • Lower CHWS temperature will typically yield
    higher CHWR temperature assuming load is adequate
  • Higher CHWS temperature will typically yield
    lower CHWR temperature
  • CHWR temperature will begin to lower when EAT
    gets close to CHWR temperature

15
Factors that Degrade ?T
Assuming Coils Are Selected for Desired ?T
  • Air economizers and 100 OSA systems
  • Excessive distribution differential pressure
  • Higher CHWS temperature - collapsing ?T
  • Account for heat gain on above grade piping
  • Coil control valves (specify close-off pressure)
  • Not capable of controlling against differential
    pressure
  • 3-way valves or 3-way converted to 2-way valves
  • Controls not controlling
  • Supply air setpoint cannot be achieved
  • Valves not interlocked with AHU, out of
    calibration
  • Improper coil selections

16
?T Conclusions
  • Design, construction and operation errors that
    cause low ?T can be avoided
  • Other causes for low ?T can never be eliminated
  • ?T degradation is inevitable, therefore, system
    design must accommodate level of degradation
    anticipated

17
?T Selection
  • What is the optimum ?T for chilled water and
    condenser water systems?
  • There is no optimum ?T for all systems,
    however, the following guidelines can lead to an
    answer
  • Select chillers at various ?Ts and estimate life
    cycle costs (12-20F)
  • If majority of chiller operating hours are at
    reduced load, consider 2 gpm/ton on condenser
    water

18
Understanding Refrigerant Lift
  • Lift SCT SST
  • Saturated Condensing Temperature (SCT) is
    dependent upon LEAVING condenser water
    temperature
  • Saturated Suction Temperature (SST) is based off
    of LEAVING chilled water temperature

19
Lift Effect on Part Load Chiller Efficiencies
20
VFD Effect on Part Load Chiller Efficiencies
21
Chilled Water Plant Design
  • Optimize equipment sizing, selection and
    operation to efficiently provide chilled water to
    the loads under various load conditions
  • Consider maintenance when selecting and laying
    out equipment
  • Select a plant configuration that best suits the
    system requirements
  • Do not make control sequences too complicated -
    the plant operator must understand the sequences

22
Chiller Selection
  • Pick a short list of vendors based on past
    experience, local representation, etc.
  • Determine the functional and operational
    requirements by assessing the cooling load and
    load profiles including hours of operation
  • Estimate energy usage of options
  • Select system (chillers) based on lowest life
    cycle cost considering capital costs, recurring
    costs of operation including maintenance and
    repairs

23
Primary-Secondary Variable Flow
Part Load Operation - 1500 Tons
DP
750 tons
750 tons
Off
4000 GPM
VFD
42 F
51 F
Secondary Pumps
42 F
LOAD 1500 TONS
1600 GPM
57 F
FM
2400 GPM
24
Variable Primary Flow
Part Load Operation - 1500 Tons
TYPICAL
DP
DP
  • Auto isolation valves
  • preferred to dedicated pumps
  • allows slow staging
  • better redundancy
  • extends 1 pump operation

750 tons
750 tons
Off
2400 GPM
42 F
VFD
Primary Pumps On VFDs
42 F
LOAD 1500 TONS
NO FLOW
57 F
57 F
FM
FM
2400 GPM
2400 GPM
25
Advantages of Variable Primary Flow
  • Lower First Costs
  • Less Plant Space Required
  • Reduced Pump Energy
  • Higher efficiency pumps
  • Reduced pressure drop due to fewer pump
    connections, less piping

26
Variable Primary Flow Design Issues
  • Evaporator flow
  • Typically minimum 3 fps extended
  • Rate of change limits (usually maximum 30 per
    minute)
  • Complexity of control
  • Not as fail-safe - what if bypass valve fails at
    low flow?
  • Must avoid abrupt flow shut-off (e.g. valves
    interlocked with AHUs all timed to stop at same
    time)
  • Flow fluctuation when staging chillers on
  • CHW TES integration can be difficult

27
Thermal Storage
  • Chilled water thermal storage is a viable means
    of increasing chiller plant efficiencies to
    reduce KW/ton of delivered chilled water
  • Near full load operation during charge
  • Ambient relief on tower to reduce condenser water
    temperatures
  • Reduction in peak chiller capacity requirement
  • Keep it simple

28
Control Issues
  • Control strategies should consider impact on
    complete system including HVAC systems
  • Control strategies should try to continually
    optimize energy consumption for entire system
  • Reliable controls are essential
  • Remember to keep it as simple as possible

29
Building Interface Considerations
  • Avoid chilled water tertiary loops whenever
    possible
  • Remember cooling coil fundamentals
  • A variable speed booster pump should be used to
    boost differential pressure when required

30
A Case for Metering
  • Most efficiently designed systems are horribly
    inefficient after several years of operation
  • Do you really know how your systems are
    operating?
  • How can we improve if we dont monitor key
    metrics?
  • Load and utility consumption data are essential
    for efficient operations

31
A Case for Commissioning
  • Commissioning is a systematic process of assuring
    that a system performs in accordance with the
    design intent and the owners operational needs
  • Re-commissioning

32
Summary
  • Start design process outside the plant
  • Understand parameters that affect chiller plant
    and overall system performance
  • Right size your equipment to deliver CHW to all
    loads under various load conditions as
    efficiently as possible throughout the year
  • Commission plant
  • Optimize control sequences

33
Energy Trend
  • World energy demand is forecasted to increase
    170 from 2000 to 2030
  • Electrical demand will double
  • Fossil fuel will provide 90 of increase in
    demand
  • Carbon dioxide emissions will increase 170
  • Energy Efficiency is a Must
  • What is our responsibility?

34
For More Information
  • ASHRAE Self Directed Learning Course
    Fundamentals of Water System Design
  • ASHRAE 2003 HVAC Systems and Equipment Handbook
  • ASHRAE Transactions and Journal
  • Hydronic System Design Operation by E.G. Hansen

35
Optimizing CentralChilled Water Systems
Write a Comment
User Comments (0)
About PowerShow.com