Regulators Indices on Power Quality
  • DNO Argentinean common experiences are
  • There are 3 quality levels fixed by the
    regulator and control stages more complexes with
    time
  • Voltage continuity (sustained interruptions)
  • Voltage quality (voltage level and disturbances)
  • Commercial quality (meter readings, claims, etc.)
  • DNO are responsible () for problems from TNO

2
Voltage Continuity (Interruptions)
  • Stage 1 average indices based on nominal kVA
    from interrupted MV/LV transformers (LV level
    excluded). ENS compute easily. A global fine as
    function of ENS, returned to all customers.
  • Stage 2 tracking of all interruptions (coming
    from HV, MV or LV systems) on each individual
    customer. ENS determination very complex.
    Monetary refund calculated separately for each
    customer.

3
ENS PENALTIES (VOLTAGE CONTINUITY)
CUSTOMERS ANUAL BILLING
STANDARD DEMAND PROFILE
ENERGY NOT SUPPLIED
(kWH billed in the last year)
1
AE (kWh)
0
24
ENS FOR EACH CLIENT
TO THE CLIENTS ENERGY BILL
ENS VALUE1.40 TO 2.71 /kWh
4
Voltage Quality
  • Voltage Level At customer level more strict
    that EN 50160 ( 5 on underground network, 97
    of recording time (7 days)). Limits change on
    overhead and rural networks. Fine as function of
    a complex calculation of delivery energy.
  • Voltage Disturbances Flicker and Harmonics
    control. Sophisticated and expensive recorders.
    Must be registered till the 40th harmonic and the
    kWh linked to each harmonic to calculate fines.

5
VOLTAGE LEVELS PENALTIES SCHEMA
7
6
5
V
Vn
- 5
- 6
- 7
I
6
VOLTAGE LEVEL PENALTIES
  • PENALTY
  • (/kWh)
  • Max. Rate
  • (0.105 /kWh)
  • Min. Rate
  • (0.027 /kWh)