Fire Retardant (FR) Clothing NESC Compliance - PowerPoint PPT Presentation

1 / 37
About This Presentation
Title:

Fire Retardant (FR) Clothing NESC Compliance

Description:

Fire Retardant (FR) Clothing NESC Compliance Brent McKinney, P.E. Manager Electric T&D APPA Principal Member NESC Subcommittee 8 – PowerPoint PPT presentation

Number of Views:146
Avg rating:3.0/5.0
Slides: 38
Provided by: Kia55
Category:

less

Transcript and Presenter's Notes

Title: Fire Retardant (FR) Clothing NESC Compliance


1
Fire Retardant (FR)Clothing NESC Compliance
  • Brent McKinney, P.E.
  • Manager Electric TD
  • APPA Principal Member
  • NESC Subcommittee 8

2
Disclaimer
  • Compliance with NESC, NEC, OSHA and / or all
    applicable codes and rules are the responsibility
    of each individual utility. This presentation
    merely provides background information so that
    each utility can make its own decision concerning
    compliance.
  • Nothing contained in this presentation is
    intended to constitute legal advice. We
    recommend that you consult with qualified legal
    counsel regarding compliance with all codes,
    laws, and regulations.

3
(No Transcript)
4
Outline
  • Consensus Standard
  • NESC, NEC Scope
  • NESC Subcommittee Structure
  • NESC Subcommittee 8 FR Clothing History
  • NESC FR Clothing Compliance 2009
  • NESC FR Clothing Compliance 2012
  • Questions

5
  • Consensus Standard Standard which is generally
    agreed upon by all entities affected.
  • NESC NEC are Consensus Standards
  • NESC IEEE
  • NEC NFPA

6
  • NEC is primarily for non-utility companies past
    the meter.
  • NEC Utility Exemption See NFPA 70E 90.1.B.5

7
  • NFPA is proposing to remove utility exemption for
    NEC.

8
  • NESC is minimum safety consensus standard for
    electric utilities.
  • States, cities may adopt.
  • Accepted as national safety consensus standard.

9
  • NESC is governed by 7 subcommittees
  • 1.Purpose, Scope, Application, Definitions and
    References
  • 2. Grounding Methods
  • 3. Electric Supply Stations
  • 4. Overhead Lines - Clearances
  • 5. Overhead Lines Strength and Loading
  • 6. None
  • 7. Underground Lines
  • 8. Work Rules

10
  • NESC subcommittees made up of utility
    representatives, consultants, IBEW, NSPE, TelCom
    industry and others.
  • No one group can have more than 33
    representation.
  • NESC Subcommittee 8 responsible for worker safety
    rules.
  • Responsible for FR clothing rules.

11
FR Clothing History
  • Change Proposal (CP) submitted to SC8 by IBEW in
    2005
  • OSHA told committee it needed consensus standard
    for new 1910.269 Rule
  • OSHA would use NEC 70-E if NESC did not pass FR
    clothing rule.

12
FR Clothing History contd
  • Nearly all SC8 members now under OSHA
  • SC8 companies felt FR clothing rule must be
    passed
  • Significant disagreement among committee
  • Working group developed to write FR rule and
    bring back to subcommittee

13
FR Clothing History contd
  • EEI, NRECA, APPA, OSHA, IBEW representatives on
    committee 8-10 people
  • Committee met three times

14
Issues
  • APPA and NRECA insisted tables be provided
    instead of requiring Arc hazard analysis.
  • Little and poor data on Arc hazard incidents and
    tests.
  • OSHA used ArcPro 2.0 to determine arcs.

15
Issues contd
  • What arc distance should be used?
  • Would regular jeans be allowed?
  • Would the heat stress of the clothes be more of a
    problem than the arc hazards?
  • Who should pay for the clothes?
  • When should the rule begin?

16
Issues contd
  • What do we do for arcs under 1,000V?
  • OSHA must accept.

17
  • Finally consensus reached, no one completely
    happy.
  • APPA votes to reject rule.

18
Rules
  • 1. Effective as of January 1, 2009, the employer
    shall ensure that an assessment is performed to
    determine potential exposure to an electric arc
    for employees who work on or near energized parts
    or equipment. If the assessment determines a
    potential employee exposure greater than 2
    cal/cm2 exists (see Neal, Bingham, and Doughty
    B59), the employer shall require employees to
    wear clothing or a clothing system that has an
    effective arc rating not less than the
    anticipated level of arc energy

19
Rules contd
  • 2. When exposed to an electric arc or flame,
    clothing made from the following materials shall
    not be worn acetate, nylon, polyester, or
    polypropylene. The effective arc rating of
    clothing or a clothing system to be worn at
    voltages 1000 V and above shall be determined
    using Tables 410-1 and 410-2 or performing an arc
    hazard analysis. When an arc hazard analysis is
    performed, it shall include a calculation of the
    estimated arc energy based on the available fault
    current, the duration of the arc (cycles), and
    the distance from the arc to the employee.

20
Rules contd
  • 3. EXCEPTION 1 If the clothing required by this
    rule has the potential to create additional and
    greater hazards than the possible exposure to the
    heat energy of the electric arc, then clothing
    with an arc rating or arc thermal performance
    value (ATPV) less than that required by the rule
    can be worn.
  • EXCEPTION 2 For secondary systems below 1000 V,
    applicable work rules required by this part and
    engineering controls shall be utilized to limit
    exposure. In lieu of performing an arc hazard
    analysis, clothing or a clothing system with a
    minimum effective arc rating of 4 cal/cm2 shall
    be required to limit the likelihood of ignition.

21
Rules contd
  • 4. NOTE 1 A clothing system (multiple layers)
    that includes an outer layer of flame resistant
    material and an inner layer of non-flame
    resistant material has been shown to block more
    heat than a single layer. The effect of the
    combination of these multiple layers can be
    referred to as the effective arc rating.
  • NOTE 2 It is recognized that arc energy levels
    can be excessive with secondary systems.
    Applicable work rules required by this part and
    engineering controls should be utilized.

22
Rules contd
  • 5. Employers shall utilize positive procedures to
    secure compliance with these rules. Cases may
    arise, however, where the strict enforcement of
    some particular rule could seriously impede the
    safe progress of the work at hand in such cases
    the employee in charge of the work to be done
    should make such temporary modification of the
    rules as will accomplish the work without
    increasing the hazard.
  • If a difference of opinion arises with respect
    to the application of these rules, the decision
    of the employer or the employer's authorized
    agent shall be final. This decision shall not
    result in any employee performing work in a
    manner that is unduly hazardous to the employee
    or to the employee's fellow workers.

23
6.
24
  • NESC 2012 CPs initial meeting
  • Low voltage working group developed update FR
    clothing rule including new table under 1000 Volts

25
  • Table 410- 23 Live-line tool work clothing and
    clothing systemsvoltage, fault current, and
    maximum clearing time for voltages 46.1 to 800 kV
    1 AC
  • (See Rule 410A3)
  • Supporting Comments
  • Currently, Rule 410A3 requires the use of
    clothing or clothing systems with a minimum
    effective arc rating of 4 cal /cm2 for voltages
    less than 1000 V, in lieu of performing an arc
    hazard analysis.
  • Subcommittee 8 established a Low Voltage Arc
    Flash Work Group (WG) to evaluate the necessary
    minimum clothing or clothing system requirements
    for employees working on energized lines and
    parts operating at voltages less than 1000V and
    to develop a Change Proposal, if needed, to
    revise Rule 410A3.

26
  • The WGs initial evaluations concluded that aside
    from anecdotal evidence no technically
    substantiated data based upon specific industry
    testing existed to justify the creation of a new
    table, similar to existing Tables 410-1 and
    410-2, for voltages less than 1000V. However,
    during the spring and summer of 2008, the Pacific
    Gas and Electric Company initiated and completed
    a series of scientific tests to determine the arc
    flash characteristics of 480V self-contained
    metering equipment by creating fault conditions
    at various kA levels (sans fault protection
    devices).
  • Based on PGEs test results and the application
    of an accepted industry standard (IEEE
    1584-2002), the WG submitted a report to
    Subcommittee 8 which included revisions to Rule
    410A3 and a new Table (410-1).

27
  • The revisions to Rule 410A3 seek to clarify the
    difference between performing an assessment and
    an arc hazard analysis, the conditions under
    which an arc hazard analysis is to be performed,
    and the employers requirements for determining
    the necessary clothing or clothing systems.
  • New Table 410-1 Clothing and Clothing Systems
    (per cm2) for voltages 50 to 1000 V (AC) and
    existing Tables (renumbered to 410-2 and 410-3)
    are cited in new text 410A3a to offer employers
    the option of using tabulated values for clothing
    and clothing systems in lieu of performing an arc
    hazard analysis.

28
  • The supplemental notes to new Table 410 -1
    identify certain parameters that vary from the
    pre-existing tables (new 410-2 and 410-3). One
    such difference is the use of an 18 in. worker
    separation distance. On this particular topic, it
    should be noted that the supporting test results
    are based on the application of IEEE Std. 1584
    test methodologies and typical working distances
    for low voltage motor control centers and panel
    boards (Table 3 p. 9). It seemed prudent to the
    workgroup to apply the 18 in. working distances
    to determine the cal/cm2 values for other listed
    equipment and for other voltage ranges, since
    Section 4.8 (IEEE 1584) states that arc flash
    protection is based on the incident energy level
    on the workers face and body, not the incident
    energy on the hands and arms.
  • The supplemental notes to new Table 410-1 also
    include statements identical to those in
    pre-existing tables (renumbered 410-2 and 410-3)
    that allow the user to apply different methods of
    calculating arc exposure values.

29
Revisions to Rule 410A3
  • Effective as of January 1, 2009, tThe employer
    shall ensure that an assessment is performed to
    determine potential exposure to an electric arc
    for employees who work on or near energized
    lines, parts or equipment.
  • If the assessment determines a potential
    employee exposure greater than 2 cal/cm2 exists
    (see Neal, Bingham, and Doughty B59), the
    employer shall
  • a. Perform a detailed arc hazard analysis, or
    use Table 410-1, Table 410-2, or Table 410-3 to
    determine the effective arc rating of clothing or
    clothing system to be worn by employees working
    on or near energized lines, parts, or equipment
    at voltages 50 800,000 volts.
  • When an The arc hazard analysis is performed, it
    shall include a calculation of the estimated arc
    energy based on the available fault current, the
    duration of the arc (cycles), and the distance
    from the arc to the employee.

30
  • b. Require employees to wear clothing or a
    clothing system that haswith an effective arc
    rating not less than the anticipated level of arc
    energy.
  • When exposed to an electric arc or flame,
    clothing or a clothing system made from the
    following materials, unless flame resistant,
    shall not be worn acetate, nylon, polyester, or
    polypropylene.

31
  • EXCEPTION 1 If the clothing or clothing system
    required by this rule has the potential to create
    additional andor greater hazards than the
    possible exposure to the heat energy of the
    electric arc, then clothing with an arc rating or
    arc thermal performance value (ATPV) less than
    that required by theis rule canmay be worn.

32
  • NOTE 1 Assessments performed to determine
    potential exposure to an electric arc consider
    the affected employees assigned tasks and/or
    work activities.
  • NOTE 12 A clothing system (multiple layers) that
    includes an outer layer of flame resistant
    material and an inner layer of non-flame
    resistant natural fiber material has been shown
    to block more heat than a single layer. The
    effect of the combination of these multiple
    layers canmay be referred to as the effective arc
    rating.
  • NOTE 23 It is recognized that arc energy levels
    can be excessive with secondary systems.
    Applicable work rules required by this part and
    engineering controls should be utilized.
  • Engineering controls can be utilized to reduce
    arc energy levels and work practices can be
    utilized to reduce exposure levels.

33
New Table 410-1
  • Table 410-1 Clothing and Clothing Systems (per
    cm2) for voltages 50 to 1000 V (AC)
  • (See Rule 410A3.)
  • Nominal Voltage Range and Calories/Cm 2
  • Equipment Type 50 250V 251
    500V 501 1000 V
  • Self-contained Metering
  • Pad-mounted transformers/
  • Panels cabinets 42 204
    308
  • CT Meters and
  • control wiring 42 45
    68
  • Metal-clad Switchgear /
  • Motor Control Centers 83 406
    608
  • Subsurface/ Pedestal-
  • mounted Equipment 42
    87 12 8
  • Open Air (includes lines) 42
    42 68

34
  • Notes
  • 1. This table is based on maximum fault current
    of 51kA.
  • Calculations are based on an 18-in separation
    distance from the arc to the employee. See IEEE
    1584-2002.
  • Other methods are available to estimate arc
    exposure values and may yield slightly different
    but equally acceptable results.
  • The use of the table in the selection of
    clothing is intended to reduce the amount or
    degree of injury but may not prevent all burns.
  • Industry testing by two separate major utilities
    has demonstrated that voltages 50 - 240V will not
    sustain arcs for more than 0.5 cycles thereby
    limiting exposure to less than 4 calories/cm2.
  • Value based on industry test results and IEEE
    Std. 1584-2002 formula for Motor Control Centers.
    (Gap 1 in.) (Xd 1.641) (18 in. distance) 51kA
    (Based on a 208V, 1000kVA, 5.3 Z, served from a
    500mVA system) Maximum duration (from tests) is
    10 cycles 46.5 cal/s/cm2 0.167 sec 7.8
    cal/cm2
  • 4. Industry testing on 480V equipment indicates
    exposures for self-contained meters do not exceed
    20 calories/cm2.

35
  • Industry testing on 480V equipment indicates
    exposures for CT meters and control wiring does
    not exceed 4 calories/cm2.
  • Value based on industry test results and IEEE
    Std. 1584-2002 formula for Motor Control Centers.
    (Gap 1 and Xd 1.641, 18 inch distance)
    12.7kA at 480 V (worst case energy value from
    testing). Maximum duration from tests is 85
    cycles 26.2 cal/s/cm2 1.42 sec 37 cal/cm2
  • Incident analysis on this equipment indicates
    exposures do not exceed 8 calories/cm2.
  • 8. Incident analysis and industry testing
    indicates that applying a 150 multiplier to the
    480V exposure values provides a conservative
    value for equipment and open air lines operating
    at 501 1000V.

36
Questions?Contact Information
  • Brent McKinney
  • Manager, Electric TD
  • City Utilities of Springfield
  • Phone 417/831-8762
  • Email brent.mckinney_at_cityutilities.net
  • Nathan Mitchell
  • Director of Engineering Services
  • American Public Power Association
  • Phone 202/467-2925
  • Email nmitchell_at_appanet.org

Mike Hyland VP of Engineering Services American
Public Power Association Phone
202/467-2986 Email mhyland_at_appanet.org
37
Additional Information Available at
  • EO Conference March 22-25, 2009 Austin, Texas
  • The 14th Edition of the APPA Safety Manual
    Available Now at APPAnet.org
Write a Comment
User Comments (0)
About PowerShow.com