Earthing / Grounding Issues - PowerPoint PPT Presentation

1 / 22
About This Presentation
Title:

Earthing / Grounding Issues

Description:

Title: RPM Products Features Author: Wade Thompson Last modified by: dannyw Created Date: 10/3/2000 6:21:12 PM Document presentation format: (4:3) – PowerPoint PPT presentation

Number of Views:97
Avg rating:3.0/5.0
Slides: 23
Provided by: Wade99
Category:

less

Transcript and Presenter's Notes

Title: Earthing / Grounding Issues


1
Earthing / Grounding Issues
  • Reasons for Earthing and Bonding
  • Detect fault current and fast removal of power
    source at fault
  • Prevent potential differences which may cause
    electrocution or sparks
  • Minimise the effect of lightning strikes
  • Prevent build-up of ESD
  • Minimise the effect of electrical interferences
  • Meet Explosion-Proof apparatus safety requirements

Reference MTL website
2
Earthing / Grounding Issues
  • Ground / earth resistance and resistivity should
    be measured when
  • Installing new ground systems and electrical
    equipment
  • Periodically testing of ground and lightning
    protection rods
  • Prior to design of ground protection systems

3
Earth Testing Methods
  • Fall of Potential 3 and 4 Pole Testing
  • Resistivity
  • Selective Testing
  • Stakeless Testing

4
Earth Testing Methods (1)
Fall of Potential Three and Four Pole Testing
5
Earth Testing Methods (1)
Fall of Potential Three and Four Pole Testing
6
Earth Testing Methods (1)
Fall of Potential Creating the S Curve
  • The positioning of temporary electrode for the
    test is a critical issue
  • The distance between electrodes is dependant on
    the pool of potential of the earth system
    under test
  • Distances of temporary electrode should be
    varied to plot values as an S curve

7
Earth Testing Methods (2)
Resistivity Measurement
From the indicated resistance value RE, the soil
resistivity calculates according to the equation
?E 2 p . a . R E   ?E ...... mean value
of soil resistivity (W.m) RE ...... measured
resistance (W) a ...... probe distance (m)
8
Principle Wenner Method
Measurement of specific earth resistance ?
The measuring method according to Wenner
determines the soil resistivity down to a depth
of approx. the distance "a" between two earth
spikes. By increasing "a", deeper layers can be
measured and checked for homogeneity. By changing
"a" several times, a profile can be measured from
which a suitable earth electrode can be
determined. According to the depth to be
measured, "a" is selected between 2 m and 30 m.
This procedure results in curves
9
Earth Testing Methods (2)
Resistivity Measurement
Curve 1As ?E decreases only deeper down, a deep
earth electrode is advisable Curve 2As ?E
decreases only down to point A, an increase in
the depth deeper than A does not improve the
values. Curve 3With increasing depth ?E is not
decreasing a strip conductor electrode is
advisable.
10
Earth Testing Methods (3)
Selective Measurement Method
11
Earth Testing Methods (3)
Selective Measurement Method
12
Earth Testing Methods (3)
Principle Selective earth measurements
Advantage Distinct earth resistances within
meshed ground systems can be measured without
disconnection. Only clamp current Im is used for
calculation of RE. Important The minimum clamp
current is 0.5mA if not, an error message is
displayed.
R Display R E3 !!
13
Earth Testing Methods (3)
Selective Measurement Method on High Tension
Towers
14
Earth Testing Methods (3)
Measurements on high tension towers
  • Applicable for nearly all metal constructions!
  • Example Tower with four stands.
  • Important Do not move the current injection
    point (E) during test!
  • All stands are tested in sequence with the split
    core transformer.

split core transformer
ring earth electrode
15
Earth Testing Methods (3)
16
Earth Testing Methods (4)
Application Function RE selective
SATURN GEO X, SATURN GEO plus
Only the current from the current clamp is used
for calculation of RE. The precise value of RE
is on display!
Connection to equi- potential bus bar
Equi Potential bus bar
sum
Earth electrode
Auxiliary earth - (H)
Probe - (S)
Water pipe
RE
(injection of test current)
(voltage reference)
R
E
Water pipe
I
I
I
I
E
Water pipe
sum
E
E Water pipe
RDisplay U / IE RE
17
Earth Testing Methods (4)
Stakeless Measurement Method
18
Earth Testing Methods (4)
Stakeless Measurement Method
19
Earth Testing Methods (4)
Stakeless Measurement Method
20
Earth Testing Methods (4)
Stakeless earth loop measurements
I
I
Current amplifier
Voltage source
U
Rx
Rn
Rn m earth resistances in parallel
Assume that there are Rn resistances in parallel
(e.g. in meshed ground systems, telecom, electric
power distribution systems) earth connections are
inter-connected. Thus RnltltRx is valid. Rn is
negligible and the measuring loop resistance is
mainly Rx. In this case the value on display of
the ground loop tester is exactly Rx.
21
Earth Testing Methods (4)
Principle Stakeless earth measurements
  • Simply put both clamps around conductor, cable,
    pipe etc.
  • Clamps with a large variety of openings are
    available.

Adapter for GEO X only
black
red
Earth electrode
gt 10cm
  • For all applications with at least two earth
    electrodes...e.g. high tension towers, meshed
    grounding systems,
  • telecom-cables ......

22
Earth Testing Methods (4)
Example Stakeless earth measurement
Write a Comment
User Comments (0)
About PowerShow.com