Noti-Fire-NetTM - PowerPoint PPT Presentation

1 / 60
About This Presentation
Title:

Noti-Fire-NetTM

Description:

Doc. 50257 Network Components Noti-Fire-NetTM A series of modules and products which allow a group of Fire Alarm Control Panels and other control equipment to connect ... – PowerPoint PPT presentation

Number of Views:211
Avg rating:3.0/5.0
Slides: 61
Provided by: Way67
Category:
Tags: nettm | fire | interface | noti

less

Transcript and Presenter's Notes

Title: Noti-Fire-NetTM


1
Noti-Fire-NetTM
  • Doc. 50257

2
(No Transcript)
3
Network Components
4
Noti-Fire-NetTM
  • A series of modules and products which allow a
    group of Fire Alarm Control Panels and other
    control equipment to connect forming a true
    peer-to-peer network.
  • Page 4

5
Noti-Fire-NetTM
  • Equipment that connects to NOTI-FIRE-NET and
    communicates with other equipment using the
    network may be referred to as a network node.
    NOTI-FIRE-NET supports up to 103 nodes with a
    total capacity of 201,960 points. A node may be
  • AM2020 Fire Alarm Control Panel
  • AFP1010 Fire Alarm Control Panel
  • NRT Network Reporting Terminal
  • AFP-200 with NAM-232 Module
  • INA Intelligent Network Annunciator
  • Page 4

6
Media Interface Board
  • The Media Interface Board (MIB) provides the
    physical interface to the following medium which
    connects node together forming a network
  • MIB-W - Two twisted pair wire ports
  • MIB-F - Two fiber optic cable ports
  • MIB-WF - One twisted pair port and one fiber
    optic cable port
  • Page 4

7
Network Adapter Module
  • NAM-232 Provides a physical interface from the
    AFP-200 or AM2020/AFP1010 Analog Fire Panel
    through the EIA-232 data port to the Network
  • NAM-232W - Two twisted pair wire ports
  • NAM-232F - Two fiber optic cable ports
  • Page 5

8
The Serial Interface Board
  • The Serial Interface Board (SIB-NET) connects an
    AM2020 or AFP1010 to the network through an MIB.
  • Each AM2020/AFP1010 requires a network node
    address and the SIB-NET permits communication
    between the AM2020/AFP1010 and other nodes on the
    network.
  • The SIB-NET also provides an EIA-232 and EIA-485
    output circuits for other external devices.
  • Page 5

9
The NRT-NET Board
  • The NRT-NET interface card and a MIB allow the
    Network Reporting Terminal (NRT) to communicate
    with the network.
  • The NRT-NET interface card plugs directly into a
    computer expansion slot located on the NRT mother
    board.
  • The MIB plugs onto the NRT-NET card to complete
    the network interface.
  • Each NRT requires a network node address.
  • Page 5

10
The Repeaters (RPTs)
  • The Repeaters (RPT) boost data signals between
    network nodes extending communication distances.
  • RPT-W supports twisted pair wire
  • RPT-F supports fiber optic cable
  • RPT-WF supports twisted pair wire and fiber optic
    cable.
  • Page 5

11
Related Documents
  • AM2020/AFP1010 Fire Alarm Control Panel
    50119/15088
  • Liquid Crystal Display (LCD-80) 15037
  • Network Reporting Terminal (NRT) 15090
  • Intelligent Network Annunciator (INA) 15092
  • Universal Zone Coder Installation
    (UZC-256) 15216
  • Product Installation Document (CCM-1) 15328
  • Product Installation Document (MPS-TR) 15331
  • AM2020/AFP1010 Operator Instructions 15337
  • Notifier Device Compatibility Document 15378
  • Analog Fire Panel (AFP-200) 15511
  • Canadian Requirements for the AM2020/AFP1010 1563
    1
  • Network Interface Board (NIB-96) 15666
  • Smoke Control Manual 15712
  • NR45-24 Charger 15760
  • Page 6

12
Related Documents
  • Annunciator Control System 15842
  • Lamp Driver Modules (LDM) 15886
  • The XP Transponder Series 15888
  • Voice Alarm Multiplex 15889
  • Network Adapter Module (NAM-232) 50038
  • The UDACT Universal. Dig. Alarm
    Comm/Transmitter 50050
  • FCPS-24/FCPS-24E Field Charger Power
    Supply 50059
  • Video Graphics Annunciator System (VGAS) Inst.
    Manual 50251
  • Media Interface Board (MIB) 50255
  • Repeater (RPT) 50256
  • Telephone/Panel Interface (TPI-232) 50372
  • Media Evaluation Tool (MET-1) 50480
  • MMX-2 Installation Instructions M500-03-00
  • Page 6

13
NOTI-FIRE-NET Specifications
  • When designing the wiring layout of a
    NOTI-FIRE-NET system, the following distance
    limitations must be considered
  • 1.The length of each individual twisted pair or
    fiber optic segment is limited. A segment is
    either point-to-point of two nodes/repeaters or
    bus connection (wire only) containing three or
    mode nodes.
  • Page 7

14
NOTI-FIRE-NET Specifications Wire
15
NOTI-FIRE-NET Specifications
  • NOTI-FIRE-NET distance limitations
  • Twisted Pair circuits
  • The length of cable for each segment in the
    system must be within the range specified in
    Table 1.5-1. If the distance required is greater
    than permitted, a RPT must be inserted into the
    circuit.
  • Cable type should be selected to satisfy the code
    requirement specific to a particular application.
  • Note This table has been expanded to include
    more wire sizes and styles since original
    preparation. See the table in the manual for more
    information.
  • Page 7

16
Twisted Pair LengthsTable 1.5-1
17
Twisted Pair LengthsTable 1.5-1
18
Twisted Pair LengthsTable 1.5-1
19
Twisted Pair LengthsTable 1.5-1
20
NOTI-FIRE-NET Specifications
  • NOTI-FIRE-NET distance limitations
  • Fiber Optic circuits
  • Cable attenuation between two nodes must not
    exceed a 10 dB limit. Distances greater than
    permitted require a repeater module inserted at
    intervals less than or equal to 10 dB.
  • To determine loss, find the rated dB loss per
    foot and multiply by the distance required, and
    add the dB loss for each connector and splice
  • Loss ((loss/ft) X (length in feet)) conn.
    loss.
  • Page 10

21
NOTI-FIRE-NET Specifications
  • NOTI-FIRE-NET distance limitations
  • 2. System path length is limited and determined
    by using Table 1.5-2. The path is defined as the
    distance of travel from one end of the network to
    the other, and is influenced by the number of
    MIB, NAM and RPT devices, and medium of the
    circuit path.
  • Page 10

22
System Path Length

System Path Length Sum of the length of
Segments 1, 2, 3, 4, and 5.
23
Node versus Medium Distance Table 1.5-2
24
Minimum Requirements
  • An NRT or INA and a fire panel with initiating
    devices and notification appliances define the
    minimum system requirements for a NOTI-FIRE-NET.
  • For each AM2020/AFP1010 panel configured for NFPA
    72-1993 Local Fire Alarm System a CMX module set
    at Loop 1, address 96 with Type ID EVGA is also
    required.
  • Page 11

25
NFPA Style 4 Configuration
  • Noti-Fire-Net is capable of communicating using
    NFPA Style 4 SLC.
  • Under this style of operation, a single open,
    wire-to-wire short, wire-to-wire short and open,
    wire-to-wire short and ground, or open and ground
    results in fragmentation of the network.
  • A single ground does not affect communication,
    but is detected.
  • Each fragment of the network reconfigures to
    permit communications among nodes within the
    fragment.
  • Page 12

26
NFPA Style 4 Configuration
NFPA Style 4 SLC Without Regeneration (Bus
Connection)
NOTE A wire-to-wire short
here results in loss of commu- nication between
all four nodes/repeaters on this bus connection
as well as fragmentation of the net- work. Bus
connections should be no longer than 100 within
conduit or the same enclosure.
27
NFPA Style 4 Configuration
  • In an NFPA Style 4 fiber-optic system, a single
    break will result in loss of communication
    between network nodes within the fragment of the
    network that can only receive signals from the
    other fragment.
  • Page 13

28
NFPA Style 7 Configuration
  • Noti-Fire-Net is capable of communicating using
    NFPA Style 7 SLC.
  • Under this style of operation, a single open,
    wire-to-wire short, wire-to-wire short and open,
    wire-to-wire short and ground, or open and ground
    will not result in fragmentation of the network.
  • A single ground does not affect communication,
    but is detected.
  • Style 7 operation may be achieved using fiber
    optic cable or mixed media (wire and fiber)
  • Page 12

29
NFPA Style 7 Configuration
30
Configuration Definitions
  • Point-to-Point wiring configuration is defined as
    a twisted-pair segment with only two nodes/
    repeaters attached to it. Terminating resistors
    are required at each end of every segment, and
    are built into each MIB, NAM-232, and RPT.
  • Page 14

31
Configuration Definitions
  • Characteristic Impedance in a Point-to-Point
    Configuration
  • Wire segment of each connection is a transmission
    line.
  • Physical construction of the cable used
    determines the characteristic impedance of that
    segment.
  • To minimize unwanted data reflections, never mix
    more than one brand name, gauge or type of wire
    within a segment.
  • Page 14

32
Configuration Definitions
NFPA Style 4 or Style 7 System Point-to-Point
Configuration
Add this segment for a Style 7 System
33
Bus Configuration
  • A bus wiring configuration is defined as a
    twisted pair network with more than two nodes.
    Terminating resistors are only needed on the
    first and last node of the bus pair, all other
    resistor must be removed.
  • Page 16

34
Bus Configuration
  • In a bus configuration, more than one node
    /repeater shares the same circuit.
  • A fault anywhere along the bus will affect the
    rest of the nodes/ repeaters on the bus.
  • Because of their inherent weakness, bus
    configurations are best employed for wiring
    between nodes/repeaters local to each other
    (within the same cabinet or room).
  • Page 16

35
Bus Configuration
  • Wiring Distances Between Nodes on a Bus
  • In a bus configuration, data is shared between
    all ports on the twisted pair, thereby reducing
    the allowable transmission distance to a maximum
    of 100 ft.
  • Page 16

36
Bus Configuration
  • Characteristic Impedance in a Bus Configuration
  • The wire segment for each bus connection is a
    transmission line.
  • The physical construction of the twisted-pair
    cable used for a segment determines the
    characteristic impedance of that segment.
  • To minimize unwanted data reflections, never mix
    more than one brand name, gauge, or type of wire
    within a bus segment.
  • Always make bus connections at the module
    terminals provided.
  • Do not make branch connections at other points.
  • Page 16

37
Combination Configuration
  • A Combination configuration can be used to
    distribute the network circuit from a central
    facility, saving on wiring run lengths.
  • A repeater is bus-wired to two existing nodes in
    each central facility (located in the same room)
    to support point-to-point connections in the
    remaining buildings in the system.
  • Page 17

38
Terminating Point-to-Point and Bus Configurations
  • Both point-to-point and bus twisted wire pair
    configurations require end-of-line termination at
    each end of the respective circuit.
  • Whereas a point-to-point circuit has a
    terminating resistor at each node/repeater port,
    a bus circuit spans multiple nodes/repeaters,
    with termination only at the outer edges of the
    circuit.
  • Page 18

39
Terminating Point-to-Point and Bus Configurations
  • Terminating resistors are present on all MIBs,
    NAMs, and repeaters. The terminating resistor on
    the first and last nodes/repeaters of a wire
    segment must remain intact. The terminating
    resistors on all the other nodes/repeaters
    connected to the same bus segment must be cut and
    removed from each board.
  • Page 18

40
On-Board Terminating ResistorsTable 1.10-1
41
On-Board Terminating Resistors
Point-to-Point Termination
These point-to-point segments are terminated at
each node/repeater.
42
On-Board Terminating Resistors
43
On-Board Terminating Resistors
44
Network Wiring Ground Fault Detection
  • Twisted pair communications links between nodes
    can be isolated through the MIB/ NAM transformer
    coupling, so a single ground fault has no effect
    on circuit operation.
  • Ground fault of the isolated link is not
    necessary unless required by LAHJ.
  • Ground fault detection from a node power supply
    may be fed-through or disabled at the MIB/NAM.
  • Page 20

45
Network Wiring Ground Fault Detection
  • Media Interface Board (MIB)
  • SW1 corresponds to Channel A
  • SW2 corresponds to Channel B
  • Network Adapter Module (NAM-232)
  • JP1 corresponds to Channel A
  • JP2 corresponds to Channel B
  • Page 20

Switch set ON to enable ground fault
feed-through. Switch set OFF to disable ground
fault feed through
Jumper set ON to enable ground fault
feed-through. Jumper set OFF to disable ground
fault feed through
3 2 1
3 2 1
46
Network Wiring Ground Fault Detection
  • Ground fault circuit operation
  • Ground fault detection may be provided by a FACP
    node which is powered by a MPS-24A or by an
    AFP-200 connected with a NAM-232.
  • INA and NRT cannot provide ground fault
    detection. Switches SW1 and SW2 on the INA or NRT
    must always be off.
  • Page 20

47
Network Wiring Ground Fault Detection
  • Point-to-Point Configuration
  • In point-to-point without repeaters, enable
    ground fault in only one of two nodes.
  • Page 20

48
Network Wiring Ground Fault Detection
  • Point-to-Point Configuration
  • If an RPT-W is used, two ground fault detection
    schemes are possible. One or both nodes may
    provide detection depending on the RPT pass
    through switch (SW3) Setting.
  • Page 21

49
Network Wiring Ground Fault Detection
  • Point-to-point
  • Left side node provides detection. Port B SW2 is
    ON.
  • RPT passes through detection. SW3 is ON.
  • Right node blocks detection. Port A SW1 is OFF.
  • Page 21

50
Network Wiring Ground Fault Detection
  • Point-to-Point
  • Left side node provides detection. Port B SW2 is
    ON.
  • RPT blocks detection. SW3 is OFF.
  • Right node provides detection. Port A SW1 is ON.
  • Page 21

Ports
Network Node
Network Node
51
Network Wiring Ground Fault Detection
  • Ground fault detection feed-through is effective
    for a maximum of two point-to-point repeaters.
  • A maximum of 5 repeaters can be serially
    connected for proper ground fault operation.
  • Page 21

ON NODE
ON RPT
ON RPT
OFF RPT
ON NODE
ON RPT
ON RPT
52
Network Wiring Ground Fault Detection
  • Bus Configuration
  • In a bus configuration, as in point-to-point,
    only one node can provide ground fault detection
    along the bus.
  • The primary difference is that one node can
    provide ground fault detection for multiple nodes
    along the bus.
  • Page 22

53
Network Wiring Ground Fault Detection
  • Bus Configuration
  • 2nd node from right provides ground fault
    detection.
  • All other nodes have ground fault disabled.
  • Note Termination resistors removed from
    pass-through bus ports.
  • Page 22

54
Network Wiring Ground Fault Detection
  • Bus Configuration
  • Node on the left and 2nd node from right provide
    ground fault detection, and RPT SW3 is off to
    prevent pass through.
  • This creates two separate ground fault circuits.
  • All other nodes have ground fault disabled.
  • Page 22

55
FCC Considerations
  • In order to comply with FCC regulations regarding
    radio frequency emissions, a ferrite cylinder
    (Notifier p/n 29087) must be installed on every
    twisted pair circuit connected to a MIB-W (two
    cylinders included) and MIB-WF (one cylinder
    included).
  • Page 20

56
FCC Considerations
  • NRT Installation
  • Thread the twisted pair(s) through the ferrite
    cylinder.
  • Slide the cylinder along the pair(s) toward the
    MIB on the back of the NRT so that the closest
    edge of the cylinder is no more than 3 inches
    away from the terminal connection block.
  • Secure the ferrite cylinder to the wiring with
    the supplied toe wrap at each end of the
    cylinder.
  • Page 23

57
FCC Considerations
  • INA SIB-NET Installation
  • Thread the twisted pair(s) through the ferrite
    cylinder.
  • Slide the cylinder along the pairs toward the
    entrance point on the cabinet (not toward the
    MIB) so that the edge of the cylinder and the
    cabinet are separated by no more than three
    inches.
  • Secure the ferrite cylinder to the wiring with
    the supplied tie wrap at each end of the
    cylinder.
  • Repeat for the second MIB-W port.
  • Page 23

58
Tips and Techniques
  • How to recognize and fix ground loops
  • Its important to realize that a ground loop is
    not the same as a surge. A ground loop is a
    consistent electrical state, causing a steady
    high voltage with high current capability. A
    voltage surge, although it may be higher and more
    powerful, is typically an induced voltage with a
    very fast rise time.

59
Noti-Fire-Net Data Pulse
  • The two thresholds available are HIGH (1.4 Volts)
    and LOW (800mV). If the pulse width 2.1 at the
    HIGH(TH, 1.4V) and 2.4 at the LOW(TL, .8V), the
    threshold should be set to HIGH. The main
    criteria is to look for is a pulse width gt 1.1
    uSec at each threshold.

60
(No Transcript)
Write a Comment
User Comments (0)
About PowerShow.com