Title: 2-Stage Heat Pump Defrost Options


1
2-Stage Heat Pump Defrost Options
  • Defrost options
  • 30, 60, 90, 120 or Auto (Infinity/Evolution only)
  • Defrost initiate temp 32 F
  • Defrost terminate temp 65 F
  • Lower defrost noise
  • Normal defrost only occurs below 50 F outdoor
    temperature

2
Ideal/Perfect Defrost Infinity/Evolution Set as
Default in UI
3
2- Stage Heat Pump Forced Defrost
  • Forced defrost pins provided on board
  • Command also available at User Interface
  • Short pins for 5 sec and release or UI command
  • If coil temp is below initiate and outdoor temp
    is below 50 full defrost cycle
  • If coil temp is above initiate temp OR outdoor
    temp is above 50 30 second defrost cycle occurs

4
Time Delays
  • One minute off between stages Bristol only
  • 5 minute mandatory high Stage on power up or 12
    hours of standby Bristol only
  • Auxiliary heat remains energized for 15 seconds
    after defrost completion

5
Time Delays
  • 20 second outdoor fan delay after defrost
  • Reduces fog effect
  • 1 minute delay in cooling mode before turning
    outdoor fan off if outdoor temp is 100 deg F or
    higher
  • For easier starting

6
Time Delays
  • 2 minute to return to standby from last valid
    communication
  • 5-minute time guard between compressor cycles
  • Can be defeated by shorting forced defrost pins
    for 1 second and releasing
  • Can also be sped up by pressing fan and temp up
    together

7
Outdoor Thermistors Verification
  • Considered open if resistance is reads 500K Ohms
    or higher (-50ºF or below)
  • Considered shorted if resistance reads 1K ohms Or
    lower (188ºF or higher)
  • Coil and Outdoor temp thermistors are compared to
    verify proper range
  • If thermistors are failed, system reverts to
    default operation

8
Outdoor Thermistors Comparison
  • Begins 20 min after defrost termination
  • Ignored during low ambient cooling
  • Ignored until unit as run for 5 consecutive
    minutes

9
Outdoor Thermistors ComparisonRange Error
Heating Might Change
  • If the outdoor thermistor indicates
  • ? 30?F warmer than the coil thermistor
  • OR
  • If the outdoor thermistor indicates ? 10?F cooler
    than the coil thermistor

10
Outdoor Thermistors ComparisonRange Error
CoolingMIGHT CHANGE
  • If the outdoor thermistor indicates ? 10?F warmer
    than the coil thermistor
  • OR
  • If the outdoor thermistor indicates ? 20?F cooler
    than the coil thermistor

11
Thermistor Failure Default Operation