Title: High Voltage Substation Surveillance using Radio Frequency Interference Measurement
1High Voltage Substation Surveillance using Radio
Frequency Interference Measurement
2(No Transcript)
3Detecting partial discharge (indirect measurement)
RFI
Thermal
Electric
Partial discharge
Pressure/ Acoustic
Light
Acoustic
Chemical
4RF pulse from a PD related source
Partial discharge pulse
RFI emission FFT frequency spectrum of PD pulse
5CASE Inkoo 110 kV CT
5
- Selective testing targeting mainly old 110 kV CTs
discovered a unit with a high C2 power factor
0,95 . (Strömberg KOTU F41 type, manuf. 1972) - A DGA follow up showed considerable gassing TCG
18 000 ppm (H2 12037 ppm, CH4 4839 ppm, C2H6 1058
ppm) diagnosed as D1 low energy discharge - Suitable test case...?
- Doble were asked for a PDS100 blind test.
66
Pvm
Esityksen nimi / Tekijä
7Baseline measurement
7
Baseline measured outside the fences Low
backround noise levels
Discharges in oil will have higher frequency
content
GSM
Typical frequency zone for air discharges lt150 MHz
88
No signals
Baseline
Suspected item
Measuring points on the service road between CBs
and CTs
9Measurements
9
- The faulty unit was succesfully located
- A small PD signal was registered 15dB above
baseline - Attennuation of high frequencies is useful in the
location process - The 110 kV CT was replaced - no signal after
replacement (one month later)
10HV Lab testing of the CT
10
- PD Ignites at 74 kV phase-to-earth voltage (128
kV main voltage), apparent charge was 50-60 pC - Extinguishing voltage is considerably lower
around 45 kV (77 kV main voltage) - At 1,2 x Um/ (85 kV) discharge level was 150 pC
- Internal pressure 0,75 bar (0,6 considered
normal) - Tandelta slightly increasing as a function of
voltage up to 70 kV, 0,43...0,59 - Tandelta increases rapidly when PD ignites at 74
kV being 1,76 at 123 kV - CT passed the 0,75 x 230 kV, 50 Hz 1 min
overvoltage test
11Advantages of RFI
- Non-invasive, no need for physical or electrical
connection. - Does not require equipment under test to be taken
out of service. - May be adopted for first-line substation
surveillance. - Rate and severity of discharge can be monitored
and trended.
12Thanks for your kind attention! Questions?
Contact Alan Nesbitt Brian Stewart Glasgow
Caledonian University Scotland, UK ane2_at_gcal.ac.uk
Contact Micael Hellquist Hans Ove Kristiansen
Doble TransiNor AS Norway info_at_doble.no