Title: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system
1Direct Digital DBT, RH, and Condensate Control
for a DOAS-CRCP system
- ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6,
2005Stanley A. Mumma, Ph.D., P.E. Jae-Weon
Jeong, Ph.D.Architectural Engineering
DepartmentPenn State University, _at_ Univ. Park, PA
sam11_at_psu.edu jqj102_at_psu.eduhttp//
doas-radiant.psu.edu
2Presentation Outline
- First thoughts when considering DOAS-CRCP
control. - DOAS-CRCP design philosophy.
- Summary of the design issues you may wish to
consider. - Field experience with single zone controls.
- Extension to multi-zone applications designed
with a DOAS supply air temperature equal to the
required design SA DPT. Why you ask!
3First Thoughts about control?
Points list
Nyquist Plots
Stability and dynamic response
Schematics
Z and Laplace Transforms
Sequence of operation
Bodi Plots
BACnet
4DOAS-CRCP Design Concept
5Issues that impact Control
- Thermal comfort, temperature and humidity
control. - DOAS SAT, neutral or cold.
- Envelope, Internal generation (high or low occ.
Density), Geo. Loc. - Std. 62, and IAQ.
- ADPI with low to very low air flow.
- Condensation control.
- Instrumentation for control and monitoring.
- Controlled devices.
- Desire for BACnet compatibility Web Access.
- Control hardware and software.
6Schematic Control Points Single Zone
DOAS-CRCP System
72. Occupied-Unoccupied Control
83. Enthalpy Wheel Control
94. Chiller Control
105. Cooling Coil Control
116. CRCP Control
127. Thermodynamic Calculations
13Extension to Multi-Zone Facility
- Case 1, Low Occupancy Density Facilities such as
Offices. - Maintain low SAT, i.e. EW with CC.
- Modulate the panel inlet water Temperature rather
than flow as in the single zone. - Space DPT sensing not required, provided DOAS
supply conditions maintained, but condensation
sensing is still needed in some perimeter spaces. - If movable sash facility, sash position sensing
is required.
14Extension to Multi-Zone Facility
- Case 2, High Occupancy Density Facilities such as
schools. - Maintain low design SAT with capability of
central free reheat, i.e. EW-CC-SW. - A critical space reset control will be discussed
next. The intent is to minimize terminal reheat
energy use.
15Paper Figure 3
ReHt
EW--CC-- SW
CRCP
Is Terminal Reheat allowed? Yes!!! See ASHRAE
Std. 90.1- 2004 Sec. 6.5.2.1 If the air
reheated does not exceed that required to meet
ASHRAE Std. 62.1
Space 1 of nDBT, RH
16OA h
ReHt
RA h,
EW--CC-- SW
CRCP
Operate the EW whenOA h gt RA h, otherwise off
SpaceDBT, RH
17CC CV
ReHt
EW--CC-- SW
CRCP
Modulate the CC CV so no space RH gt 55orno
space DBT gt 75
SpaceDBT, RH
18(No Transcript)
19CRCP CV
ReHt
EW--CC-- SW
CRCP
Modulate the SW speed to hold at least one
CRCPCV wide open
SpaceDBT, RH
20(No Transcript)
21ReHt CV
CRCP CV
ReHt
EW--CC-- SW
CRCP
Modulate the CRCP CV the ReHt CV in sequence
to maintain the Space DBT _at_ 75F
SpaceDBT, RH
22(No Transcript)
23Conclusions
- The single zone DOAS-CRCP system has been
operating superbly now for over 3 years with the
controls presented here. - Without a single incidence of condensation.
- Maintenance free.
- Based upon that experience, the control was
extended to a multi-zone building utilizing low
SAT. A CRITICAL ZONE DBT AND DPT RESET SCHEME - The many interacting local control loops in the
reset control will require care (slow response)
to avoid hunting.
24Questions