Distribution Automation Overview, Activities, and Roadmap David G' Hart - PowerPoint PPT Presentation

1 / 30
About This Presentation
Title:

Distribution Automation Overview, Activities, and Roadmap David G' Hart

Description:

Automation is the ability to remotely monitor and control ... Hertz * Requires Voltage Inputs. ABB Power T&D Company. ABB. PCD2000 - Data records. Load Profile ... – PowerPoint PPT presentation

Number of Views:414
Avg rating:3.0/5.0
Slides: 31
Provided by: david2810
Category:

less

Transcript and Presenter's Notes

Title: Distribution Automation Overview, Activities, and Roadmap David G' Hart


1
Distribution AutomationOverview, Activities, and
RoadmapDavid G. Hart Jay ParkSeptember 1,
1999
2
Overview - Automation
  • Automation is the ability to remotely monitor and
    control the network, collect information, and
    provide information in a useful manner to the
    end user

3
Overview - Levels of Automation
LEVEL 4 Off-Line Analysis
LEVEL 3 Real-Time Control
LEVEL 2 Communications
LEVEL 1 Intelligent Equipment
4
Substation Automation
  • ABB Distribution Substation Solution

Power RICH System
MicroShield OC
PCD2000
5
Substation Automation - Power RICH System
  • Provides graphical user interface for control,
    monitoring, and device settings
  • Utilizes standard local area network - MODBUS,
    MODBUS PLUS, DNP 3.0 160 other protocols
  • Allows integration of digital protection/
    control/ metering/ load profile using the 2000
    series
  • Supports MODBUS DNP 3.0 with PCD2000

6
Substation Automation - Applications
  • Interface to SCADA
  • Control with Power RICH System
  • Monitoring with Power RICH System
  • Restoration of system following an outage
  • etc.

7
Automation - Benefits
  • Provides remote, immediate, status of the
    substations in the region
  • Power RICH System provides monitor control of
    multiple vendors devices NOW in the future
  • Personnel safety via remote control
  • One point of contact, ABB contact list
  • Advanced problem analysis with advanced ABB
    devices

8
Feeder Automation
  • ABB Feeder Solution

VR3S Recloser
VS3S Switch
9
15-27kV Three Phase Automatic Recloser
  • RATINGS
  • 15 kV 27 kV 38 kV
  • Max. Voltage 15.5 27 38 kV
  • Cont. Current 560/800 560/800 560/800 A
  • Int. Current 12/16 12.5/16 12.5/16 kA
  • BIL 110 125 170 kV

10
Interrupting Unit
Encapsulated vacuum Interrupters - low
maint- enance 10,000 loadbreak operations
Integrated Sensors - protected from the
environment, designed to not saturate during
fault conditions for fault information
Heavy gauge cabinet - Available in mild
or stainless steel
Recloser cable includes wires for for 3 phase
voltage transformer wiring
Mechanical trip - for manual operation
Large easy to view Open/Close Indicators
11
Mounting Arrangements
  • Substation Mounted
  • Pole Mounted

12
PCD2000 Recloser Control Features
PCD2000 -front panel
LCD Display - backlit Displays metering vals and
post fault information
Fault indicating targets - highly visible,
pickup, phase and ground trip and lockout lights
HMI - Human machine interface password
protected, easy to use
Push-button controls with indicating LEDs
Optical communications port RS-232C
Control status indication - uses self-checking
diagnostics
Open/Close push-buttons and position
indicating light
13
PCD2000 - Advanced Protective Functions
  • Under/Over Voltage control and alarming
  • Very useful for detection of high side fuse
    operation/ single phasing condition
  • Also used for loop sectionalizing, voltage
    transfer
  • Allows time delayed load shedding
  • Under/Over Frequency control and alarming
    (1phase or 3 phase)
  • Allows enhanced load shedding capability
  • Directional specific overcurrent protection
  • Allows for closed loop schemes
  • Directional specific power flow control
  • Allows for changing to alternate profile during
    backfeed condition
  • Directional specific overcurrent protection
  • Allows for closed loop schemes
  • Requires voltage inputs

14
PCD2000 MeteringAccuracy of Volts and Amps to 1
Requires Voltage Inputs
15
PCD2000 - Data records
  • Load Profile
  • Up to 160 days of data
  • Records kW, kVAR volts per phase
  • Operation/Fault Records
  • 128 recloser operations
  • Fault duty accumulator for interrupters
  • Operation and trip counters
  • Fault records
  • Records detailed fault data for last 32 faults
    (including relay times, distance to fault)
  • Basic fault data for last 128 faults

16
PCD2000 - Advanced Data records
  • Oscillographic capture
  • Valuable tool for analyzing post fault waveforms
  • Records total of 64 cycles per phase currents and
    voltages 8 distinct events
  • Power Quality records per ANSI/IEEE 1159 Standard
  • Very powerful tool for pinpointing source of
    power quality problems
  • Records voltage sags, swells, Total Harmonic
    Distortion, Total Demand Distortion
  • Can use ANSI recommended voltage/duration
    thresholds or can be user specified
  • Holds up to 256 records

17
PCD2000 Communication Features
  • Open protocols, DNP3.0, Modbus ASCII RTU
    included with each unit
  • Doesnt require additional hardware for protocols
  • RS232, RS485, programmable I/O and optical port
    are all standard. Fiber port is optional
  • Fiber port is unsurpassed, fully regenerates
    signal, preventing signal attenuation
  • Software for the PCD2000, WinPCD, has dial up
    capability and an extensive control interface
  • Control Cabinet has plenty of room for a radio or
    modem, and a 12 V DC power supply is optional

18
Soon to be released
  • Single phase tripping
  • Very advantageous for residential loads
  • Reduces affected customers by 2/3 rds
  • Single or three phase lockout selection
  • Option to block ground tripping after single
    phase trip/lockout
  • Can change to three phase trip only based on KW
    demand threshold
  • Loop Scheme automatic reconfiguration (10/99)
  • Does not require communications between units or
    master
  • One control used for both main feeder and tie (or
    midpoint) reclosers
  • Has separate user interface with per phase
    voltage indication recloser status and override.

19
SCD2000 Switch Control Features
SCD2000 -Front Panel
LCD Display - backlit Displays metering vals and
post fault information
Fault indicating targets - highly visible,
pickup, phase and ground trip and lockout lights
HMI - Human machine interface password
protected, easy to use
Push-button controls with indicating LEDs
Optical communications port RS-232C
Control status indication - uses self-checking
diagnostics
Open/Close push-buttons and position
indicating light
20
SCD2000 - Control Functions
  • Features
  • Fault indication that utilizes currents or
    currents and voltages
  • Phase imbalance
  • Switch failure alarm
  • Number of operations
  • Sectionalizing function
  • Automatic source transfer

21
Substation/Feeder Integration
Power RICH System
Communications Gateway
22
DCD2000
  • DCD 2000 Communications Gateway Development -
    Located in substation to link substation and
    feeder devices
  • Provides multiple master/slave operation in one
    integrated box
  • Provides interface to multiple applications
  • Port for Power RICH System
  • Port for existing SCADA RTU
  • MODEM for off-line applications being developed
    such as PQ
  • Provides interface to substation and field
    devices
  • RS-232 with handshaking for feeder long distance
    radio
  • RS-485 twisted pair to connect substation relays
  • fiber optic to connect yard equipment
  • Support standard protocols (MODBUS and DNP 3.0)

23
DCD2000 Communications Gateway
Substation
Real Time Control
Gateway
Leased Line
Power RICH System
Modem/232
Dial-Up
Off-Line Applications
Feeder
Industrial PLC
24
DCD2000 Communications Gateway
Power RICH System
PLC
SCADA
Twisted Pair
Radio
Fiber
Feeder
Off-Line Applications
Substation
25
Substation/Feeder Integration - Application
  • PLC monitors DPU2000 to determine breaker is
    open, opens other side of fault, and restores
    power with tie switch

DCD2000 Gateway
PLC
26
Substation/Feeder Integration - Application
  • Power RICH System provides HMI and control
  • PQIS monitors key customers

PQIS
Power RICH System
27
Off-Line Applications
  • Provide utility with new off-line applications
    that utilize intelligence in equipment
  • Topics PQ, load profile, fault location, etc.

28
Off-Line Applications
  • Power Quality - Provide industrial account
    representative with PQ data on key customers from
    reclosers/switches, relays and meters
  • Use IEEE definitions
  • Easy to understand presentation
  • Distributed PC users in different departments
  • Local or corporate database (s)
  • Scalable number of monitoring devices
  • Data captured in relay/controller

29
Demonstration
Phone Simulator
Off-Line Application
PLC
MDS Radio
Modbus over RS-232
ABB PCD 2000
PCD2000
Modbus over RS-485
Gateway
OC Relay
Power RICH System
30
Summary
  • Family of products for substation and feeder
    automation
  • Innovative new concepts being developed and
    tested
Write a Comment
User Comments (0)
About PowerShow.com