Acorn Safety Your Safety is Our Business - PowerPoint PPT Presentation

1 / 66
About This Presentation
Title:

Acorn Safety Your Safety is Our Business

Description:

Acorn Safety submittals, price guide, crossovers, rough-in sheets, installation ... PCP = Polished chrome plated -PDV = Push down valve (desk mounted units) ... – PowerPoint PPT presentation

Number of Views:120
Avg rating:3.0/5.0
Slides: 67
Provided by: imim8
Category:

less

Transcript and Presenter's Notes

Title: Acorn Safety Your Safety is Our Business


1
(No Transcript)
2
Acorn SafetyYour Safety is Our Business
Rev. March 2008 - LLPPT
3
Web Site
  • Acorn Safety submittals, price guide, crossovers,
    rough-in sheets, installation operation
    instruction sheets, literature and information
    requests are available online at
  • www.AcornSafety.com

4
Product Structure
  • S 1st I 2nd I 3rd I 4th I Options
  • 1st position Showerhead
  • 2nd position Mounting
  • 3rd position Bowl (receptor configuration)
  • 4th position Drench hose
  • Options

5
1st Position Showerhead
  • 0 None
  • 1 Plastic
  • 2 Stainless steel
  • 3 Stainless steel, recessed

6
2nd Position Mounting
  • 0 None
  • 1 Vertical
  • 2 Horizontal
  • 3 Pedestal
  • 4 Wall
  • 5 Wall, recessed
  • 6 Wall, swing down
  • 7 Deck
  • 8 Deck, swing down
  • 9 Deck, swivel
  • A Deck, swivel with 1/2" valve
    push flag
  • P Portable plastic, gravity feed tank

7
3rd Position Bowl/Receptor
  • 0 None
  • 1 Plastic bowl, eyewash
  • 2 Plastic bowl, eye/face wash
  • 3 Stainless steel bowl, eyewash
  • 4 Stainless steel bowl, eye/face wash
  • 5 No bowl, eyewash
  • 6 No bowl, eye/face wash
  • 7 Stainless steel shrouded bowl, eyewash
  • 8 Stainless steel shrouded bowl, eye/face wash

8
4th Position Drench Hose
  • 0 None
  • 1 Single head with a self-closing valve
  • 2 Single head with a stay-open valve
  • 3 Single head with a self-closing valve push
    handle
  • 4 Single head with a stay-open 1/2" ball valve
    push handle
  • 5 Two heads with a self-closing valve
  • 6 Two heads with a stay-open valve
  • 7 Two heads with a self-closing valve push
    handle
  • 8 Two heads with a stay-open 1/2" ball valve
    push handle
  • G Auxiliary hand-held drench hose (heat
    traced, combination shower units)
  • H Auxiliary hand-held drench hose (gravity fed
    unit)

9
-Options
  • -AL1 Electric alarm with light and horn
  • -AL2 Electric alarm with flashing light and
    horn
  • -AL3 Electric alarm for recessed laboratory
    applications
  • -AS All stainless steel
  • -BF Barrier free
  • -BFP Back flow preventor, double
    check valve with vent to atmosphere
  • -BS1 Bottom supply inlet
  • -C1D1 Class 1, Division 1
  • -C1D2 Class 1, Division 2

10
-Options
  • -CH12 12 foot coiled hose
  • -CS1 SS clam shell cover
  • -DB1 Double pole (for flow switches)
  • -FLW1 Flow switch, single pole (showers)
  • -FLW2 Flow switch, single pole (eyewashes)
  • -FPB Frost proof bury
  • -FPV Freeze protection valve (1/2")
  • -FRV Freeze resistant valve (thru wall models)
  • -HFC Hand foot control
  • -HG Hose guide (under counter)
  • -HT Heat traced
  • -IWH1 Instantaneous water heater 208V
  • -IWH2 Instantaneous water heater 240V
  • -LGT1 Area light (blue globe)
  • -LH Left hand operation

11
-Options
  • -LWB Less mounting bracket
  • -MC1 Modesty curtain (for horizontal arms)
  • -MC2 Modesty curtain (for vertical arms)
  • -MC3 Modesty curtain (for wall installation)
  • -PAN Waste water drain pan
  • -PCP Polished chrome plated
  • -PDV Push down valve (desk mounted units)
  • -PE_ _ Pipe extension (in inches)
  • -PR_ _ Pull rod length (in inches)
  • -PT1 1-1/4" P-trap
  • -RA Recessed wall activation

12
-Options
  • -RH Right hand operation
  • -SDC Stainless steel dust cover
  • -SGN1 Sign for eyewash or eye/face wash
  • -SGN2 Sign for shower
  • -SGN3 Sign for shower eyewash or
    eye/face wash combination
  • -SGN4 Sign for drench hose
  • -SPV Scald protection valve (1/2")
  • -SSE Stainless steel eyewash head
  • -SSH Stainless steel hose
  • -STK Shower test kit
  • -SV1 1" stainless steel ball valve
  • -SV2 1/2" stainless steel ball valve

13
-Options
  • -TMB1 Thermostatic mixing valve with external
    cold water bypass - eyewash
    or eye/face wash (14 gpm)
  • -TMB2 Thermostatic mixing valve with external
    cold water bypass
    combination station (36 gpm)
  • -TMB3 Thermostatic mixing valve with external
    cold water bypass - multiple
    combination units (66 gpm)
  • -TMV1 Thermostatic mixing valve
    eyewash or eye/face wash (14 gpm)
  • -TMV2 Thermostatic mixing valve
    combination station (36 gpm)
  • -TMV3 Thermostatic mixing valve
    multiple combination units (66 gpm)

14
-Options
  • -TS1 Top supply inlet
  • -WS1 Wall supply inlet
  • -240V 240 volt, 50 hertz

15
Acorn AdvantageEye Eye/Face Washes
  • Integral in-line strainer standard
  • Flip top dust covers
  • Durable ABS plastic or Stainless Steel bowl
  • Stainless Steel push handle (14 ga)
  • Protective, hi-vis yellow powder coating

16
Eyewash Wall MountedS0410
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 4, Mounting wall
  • 3rd position 1, Bowl/Receptor plastic, eyewash
  • 4th position 0, Drench hose none
  • Typical options BF, PT1, TMV1

17
S0410
18
S0430
19
S0470
20
Eye/Face Wash Wall MountedS0420
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 4, Mounting wall
  • 3rd position 2, Bowl/Receptor plastic, eye/face
    wash
  • 4th position 0, Drench hose none
  • Typical options BF, PT1, TMV1

21
S0420
22
S0440
23
S0440-BF
24
S0480
25
Eyewash Eye/face PedestalS0310, S0320 -
Plastic BowlS0330, S0340 Stainless Steel Bowl
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 3, Mounting pedestal
  • 3rd position 1, 3, Bowl/Receptor plastic or
    stainless steel bowl, eyewash
  • 4th position 0, Drench hose none
  • Typical options AS, CS1, HFC, SDC, SSE, drench
    hose
  • Delivered fully assembled

26
S0310
27
S0330
28
S0340
S0320
29
Eyewash Laboratory
  • S0650 Wall mount, swing down S0850
    Swing downS0950 SwivelS0A50 Swivel with
    1/2" valve push handle
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 7, 8, 9, A, Mounting deck
  • 3rd position 3, 5, Bowl/Receptor stainless
    steel or no bowl, eyewash
  • 4th position 0, Drench hose none
  • Typical options AS, LH, PCP, PDV, RH, SSE,
    TMVSwivel with 1/2 valve doesnt meet Z358.1
    (activation).

30
S0850-RH
31
S0950-RH
32
S0650-RH
33
Eye/Face Wash Laboratory
  • S0660 Wall mount, swing downS0740-PDV deck
    mount, push down valveS0860 Swing downS0960
    SwivelS0A60 Swivel with 1/2 valve push
    handle
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 7,8,9,A, Mounting deck
  • 3rd position 4, 6, Bowl/Receptor stainless
    steel or no bowl, eye/face wash
  • 4th position 0, Drench hose none
  • Typical options AS, BF, LH, PCP, PDV, RH, TMV1

34
S0860-RH
35
S0960-LH
36
S660-LH
37
Eye/Face Wash Wall Mounted, RecessedS0560
  • S Acorn Safety prefix
  • 1st position 0, Showerhead none
  • 2nd position 5, Mounting wall, recessed
  • 3rd position 6, Bowl/Receptor no bowl, eye/face
    wash
  • 4th position 0, Drench hose none
  • Typical options - AS, PAN, PCP, SDC, TMV1
  • Fits in four (4) inch wall

38
S0560
39
Acorn Advantage - Showers
  • Full sheeting "wall of water" shower head spray
    pattern, common on all Acorn showers
  • Yellow protective powder coating
  • Standard 20 gpm flow control
  • Stainless steel actuator arm and pull rod

40
Drench Showers - VerticalS1100 Plastic
HeadS2100 Stainless Steel Head
  • S Acorn Safety prefix
  • 1st position 1, 2, Showerhead plastic or
    stainless steel
  • 2nd position 1, Mounting vertical
  • 3rd position 0, Bowl/Receptor none
  • 4th position 0, Drench hose none
  • Typical options - MC2, PR_ _, RA, TMV2

41
S1100
S2100
42
Drench Showers HorizontalS1200 Plastic
HeadS2200 Stainless Steel Head
  • S Acorn Safety prefix
  • 1st position 1, 2, Showerhead plastic or
    stainless steel
  • 2nd position 2, Mounting horizontal
  • 3rd position 0, Bowl/Receptor none
  • 4th position 0, Drench hose none
  • Typical options MC1, RA, TMV2
  • .

43
S1200
44
Combination Shower EyewashS1310 S1330
  • S Acorn Safety prefix
  • 1st position 1, Showerhead plastic
  • 2nd position 3, Mounting pedestal
  • 3rd position 1 or 3, Bowl/Receptor plastic or
    stainless eyewash
  • 4th position 0, Drench hose none
  • Typical options BF, FPB, HFC, MC1, TMV2,
  • Eyewash section fully assembled

45
S1310
46
S1330
47
Combination Shower Eye/Face WashS1320 1340
  • S Acorn Safety prefix
  • 1st position 1, Showerhead plastic
  • 2nd position 3, Mounting pedestal
  • 3rd position 2, Bowl/Receptor plastic, eye/face
    wash
  • 4th position 0, Drench hose none
  • Typical options - BF, CS1, FPB, HFC, MC1, PR_ _,
    TMV2, drench hose
  • Eye/face wash section full assembled

48
S1320
49
S1340
50
Stainless SteelCombination Shower Eye/Face
WashS2340-AS
  • S Acorn Safety prefix
  • 1st position 2, Showerhead stainless steel
  • 2nd position 3, Mounting pedestal
  • 3rd position 4, Bowl/Receptor stainless steel,
    eye/face wash
  • 4th position 0, Drench hose none
  • Suffix -AS, All Stainless Steel
  • Typical options BF, CS1, FPB, HFC, MC1, TMV2
  • Eye/face wash section fully assembled

51
S2340-AS-BF
52
Combination Shower Eye/Face WashS1360 (no
bowl)
  • S Acorn Safety prefix
  • 1st position 1, Showerhead plastic
  • 2nd position 3, Mounting pedestal
  • 3rd position 6, Bowl/Receptor no bowl, eye/face
    wash
  • 4th position 0, Drench hose none
  • Typical options BF, FPB, HFC, MC1, TMV2,

53
S1360
54
Heat TracedCombination Shower Eye/Face
WashS1360-HT
  • S Acorn Safety prefix
  • 1st position 1, Showerhead plastic
  • 2nd position 3, Mounting pedestal
  • 3rd position 6, Bowl/Receptor no bowl, eye/face
    wash
  • 4th position 0, Drench hose none
  • Suffix -HT, heat traced (freeze resistance)
  • Typical options AL1, BSI, C1D1, FPV, LGT1, TSI,
    G drench hose

55
Acorn Advantage
  • Certified to -50F
  • Insulation 1 inch wall thickness
  • 180 inches heat trace tape
  • Class 1, Division 2 is standard

56
S1360-HT-BSI
57
Combination Shower Eye/Face Wash, Recessed
ActivationS2260-RA
  • S Acorn Safety prefix
  • 1st position 2, Showerhead stainless steel
  • 2nd position 2, Mounting vertical
  • 3rd position 6, Bowl/Receptor no bowl, eye/face
    wash
  • 4th position 0, Drench hose none
  • Suffix -RA, recessed shower activation
  • Fully recessed in on off positions
  • Fits in a four (4) inch wall
  • Typical options PAN, TMV2

58
S2260-PAN-RA
59
Drench Hoses
  • S0402 single head, wall, stay-open
  • S0402-CH12 single head, wall, stay-open, 12
    foot coiled hose
  • S0702 single head, deck mounted, stay-open
  • S0406 two heads, wall, stay-open
  • S0406-CH12 two heads, wall, stay-open, 12 foot
    coiled hose
  • S0706 two heads, deck mounted, stay-open

60
S0402
S0406
S0406-CH12
61
Tempered Water Mixing Valves
  • TMV series Thermostatic Mixing Valve, internal
    bypass
  • TMV1 - (14 gpm) - all eye eye/face wash units,
    multiple units, drench hoses
  • TMV2 - (36 gpm) all drench showers
    combination showers, one unit only
  • TMV3 - (66 gpm) multiple units

62
S0000-TMV2
S0000-TMV3
63
Tempered Water External Bypass Mixing Valves
  • TMB series Thermostatic Mixing Valve with
    External Bypass.
  • TMB1 - (14 gpm) full flow cold water bypass
  • TMB2 - (36 gpm) full flow cold water bypass
  • TMB3 - (66 gpm) full flow cold water bypass
  • Proprietary bypass - pressure differential

64
Codes Compliance
  • ANSI Z358.1- 2004, Emergency Eyewash and Shower
    Equipment
  • Voluntary Standard, not enforceable
  • OSHA uses as a guideline, cites through the
    general duty clause 29 CFR 1910.151, which
    requires that......where the eyes or body of
    any person may be exposed to injurious corrosive
    materials, suitable facilities for quick
    drenching or flushing of the eyes and body shall
    be provided within the work area for immediate
    emergency use.
  • Affects equipment manufacturers, engineers and
    owners
  • The Owner has to know his work place
    environment

65
ANSI Z358.1 - 2004
  • The standard which governs the configuration,
    performance, installation, testing and
    maintenance of all emergency drench equipment.
  • Owner, Engineer and Manufacturer must work
    together to determine proper equipment selection.
  • Acorn Safety products are compliant and will be
    third party certified (IAPMO)

66
Z358.1 - 2004 Highlights
  • 20 GPM shower
  • 1 second activation
  • Accessible within 10 seconds
  • Same level access
  • Highly visible sign, location
  • Tepid Water luke warm, moderately warm
  • Appendix B.6 - 100 too high, 60 too low
Write a Comment
User Comments (0)
About PowerShow.com