Title: The ABB CM-UFD.M33 Solar Protection Relays | Zero Export
1ABB CM-UFD.M33 Solar Protection Relay
BCJ Controls
2Description
- The ABB CM-UFD.M33 is a multifunctioning grid
feeding monitoring relay. It trips the section
switch that is connected between the distributed
generation and the public grid allowing the
distributed generation to disconnect in case of
problems (e.g. unstable grid), faults, or grid
maintenance. - The device provides different monitoring services
to detect 10-minutes average overvoltage, real
time over- and under-voltage as well as over- and
under-frequency. Additionally, monitoring of
vector shift and ROCOF (rate of change of
frequency) can be configured to trip the
generation in a case of loss of mains.
3ABB CM-UFD.M33 Characteristics
- Monitoring of voltage and frequency in
single-phase and three-phase mains (2-wire,
3-wire or 4-wire AC systems). - Over- and under-voltage, 10-minutes average value
as well as over- and under-frequency monitoring. - Two-level threshold settings for
over-/under-voltage and over-/under-frequency. - ROCOF monitoring and vector shift detection are
configurable. - Interrupted neutral detection.
- Default settings in accordance with Great Britain
Engineering Recommendations G59/3 and G83/2
4ABB CM-UFD.M33 Characteristics
- True RMS measuring principle
- All threshold values and tripping delays are
adjustable - Error memory for up to 99 entries (incl. cause of
error, measured value, relative timestamp) - Password setting protection
- 3 control inputs (e.g. for feedback signal,
remote trip) - 3 c/o (SPDT) contacts
- Multiline, backlit LCD display
5ABB CM-UFD.M33 Application
- The ABB CM-UFD.M33 is a grid feeding monitoring
relay that monitors the voltage and the frequency
of the public low or medium voltage grid.
Whenever measured values are not within the range
of adjusted threshold values, the ABB CM-UFD.M33
causes the section switch to trip (consisting of
1 or 2 switching devices according to the
applicable standard). This tripping disconnects
the power generation of systems such as
photovoltaic systems, wind turbines, and
block-type thermal power stations from the grid.
The fault is indicated by a LED and the
corresponding plain text failure message is
displayed.
6Operating Mode
- The ABB CM-UFD.M33 can be set up to monitor
single-phase and three-phase mains (2-wire,
3-wire as well as 4-wire AC systems). The unit is
configurable by front-facing push-buttons. A
display with the corresponding menu enables the
selection of preset settings as well as the
precise adjustment of the various threshold
values and corresponding time delays.
Furthermore, the display portrays the measured
values clearly. Along with the front-facing LEDs,
it shows all information about operational states
of output relays and control inputs.
7Operating Mode
- The ABB CM-UFD.M33 provides three output relays
and three control inputs. Output relays R1
(1115-1216/1418) and R2 (2125-2226/2428) are
needed for disconnection of a distributed
generation system from the public grid. The
corresponding feedback signals from the external
contacts are monitored using the control inputs
Y1-Y0 and Y2-Y0. The third output relay R3
(3135-3236/3438) can be used for to command the
close of a motor drive for circuit breaker or as
signalization of output relays R1 and R2. The
additional control input Y3-Y0 allows tripping of
the grid feeding monitoring relay remotely. With
control input Y3-Y0 it is possible to suppress
both input Y1-Y0 and input Y2-Y0 or the vector
shift detection.
8Protective Functions
- If control supply voltage is applied, then all
phases are present and the switch-on conditions
for voltages and frequency are fulfilled. Output
relays R1 and R2 energize synchronously after the
altered switch-on delay. The green LED U/T
flashes during timing and becomes steady when the
switch-on delay is complete. If a measured value
is above or below the set threshold value
(overvoltage, under-voltage, over-frequency,
under-frequency, ROCOF or vector shift), R1 and
R2 de-energize after the altered tripping delay.
As soon as the value returns to the tolerance
range taking into account an adjustable
hysteresis and all further switch-on conditions
are fulfilled, R1 and R2 re-energize. The fault
is indicated by the red LED F and the type of
fault is shown in plain text on the display. The
event that caused the relay to trip is recorded
in the event list. The green LED U/T flashes
during timing and turns steady when the delay is
complete.
9Output Relay R3 (3135-3236/3438)
- Output relay R3 can be used to command the
closing of a breaker motor. For this function,
either of the working principles closed-circuit
or open-circuit must be selected. When output
relays R1 and R2 energize, the altered ON-delay
starts. When the timing is finished, R3 will be
activated for the ON-time duration or until R1
and R2 de-energize. Additionally, R3 can be
configured as either synchronous with R1/R2 or
disabled. For these two configurations, the
ON-delay and the ON-time settings have no
influence on the operating function.
10Control inputs Y1-Y0, Y2-Y0
- The control inputs, Y1-Y0 and Y2-Y0, are used as
feedback contacts for the two switching devices
of the section switch. The current status for the
switching devices is monitored by the grid
feeding monitoring relay. The control inputs
configuration for the working principle can be
set as normally closed, normally open, auto
detection, or completely disabled. A failure
in the feedback loop has to be manually removed
on the device. Please note 1. Normally here
refers to good status of the grid, this is when
all the monitored voltages and the frequency stay
within set threshold values and the output relays
R1 and R2 are energized. 2. The grid feeding
standards vary for different countries.
11Control inputs Y1-Y0, Y2-Y0
- Some require that a section switch consists of
two independent switching devices, while others
only require one switching device working as a
section switch. In addition, monitoring of the
switching devices by the feedback monitoring is
not required by all standards. For this reason,
the monitoring functions of control inputs Y1-Y0
and Y2-Y0 are disabled by default. They can be
enabled manually in the menu. The function of
control input Y3-Y0 can be configured as remote
trip, suppress Y1, suppress Y2, suppress
Y1/Y2, or suppress vector shift detection. The
working principle of the control input can be
configured as normally open, normally closed,
or completely disabled.
12Control inputs Y1-Y0, Y2-Y0
- Remote trip With Y3-Y0 configured as normally
closed, output relays R1 and R2 de-energize if
Y3-Y0 is open, and vice versa.Suppress Y1,
suppress Y2, suppress Y1/Y2 These functions can
be used to suppress evaluation of the chosen
feedback loop during generator synchronization,
so that the status of the feedback signal wont
be considered a feedback error. A different
solution is to make the release window of the
corresponding feedback loop larger than the
possible duration of synchronization process.
13ROCOF (Rate of Change of Frequency df/dt)
- Output relay R3 can be used to command the
closing of a breaker motor. For this function,
either of the working principles closed-circuit
or open-circuit must be selected. When output
relays R1 and R2 energize, the altered ON-delay
starts. When the timing is finished, R3 will be
activated for the ON-time duration or until R1
and R2 de-energize. Additionally, R3 can be
configured as either synchronous with R1/R2 or
disabled. For these two configurations, the
ON-delay and the ON-time settings have no
influence on the operating function.
14Vector Shift Detection
- This function is another possible way of
detecting a loss of mains (islanding). The vector
shift detection is enabled by default and can be
disabled manually in the menu. Through zero
crossings, the device detects the vector shift of
mains voltage and de-energizes output relays R1
and R2 instantly if the shift exceeds the
adjusted threshold value (e.g. 12 ). Only after
the set error time will the switch-on conditions
be evaluated in order to start an auto
re-connection.
15Switch-On Conditions
- In order to turn on the section switch after
applying control supply voltage or after a fault,
the voltages and the frequency must stay within
the set switch-on conditions during the switch-on
delay. This window of voltage and frequency can
be restricted more in the menu Switch-on
conditions. If one parameter exits the window,
the switch-on process is interrupted. When all
parameters fulfill the switch-on conditions
again, the switch-on delay restarts. When the
switch-on time is finished, relays R1 and R2
re-energize automatically. If the function Short
interruption is enabled in the menu Switch-on
conditions -gt Switch-on delay, the switch-on
delay will be reduced to 5 s in case of an
interruption of less than 3 s.
16Interrupted Neutral Detection
- Interrupted neutral detection is active whenever
one of the phase-neutral measuring principles is
selected in the menu Nominal voltage. The
interruption of the neutral conductor will result
in an instant tripping of the output relays R1
and R2.
Automatic Reconnecting Attempts
- If an error occurs at feedback loop Y1-Y0 or
Y2-Y0 (e.g. under-voltage release because of a
lightning strike), between zero and three
automatic reconnecting attempts will be carried
out, accounting for the switch-on conditions.
Therefore a temporary feedback error doesnt need
to be handled manually. The corresponding error
in the feedback loop is stored in the error list.
17Test Function
- The test function can be used to simulate an
error in the installation, so that the time
delays of the feedback loops can be determined. A
feedback loop includes the output relay, the
corresponding switching device, and the feedback
contact. The test function can be started by
pressing the ESC button for 3 s. The output
relays R1 and R2 de-energize immediately and the
ABB CM-UFD.M33 gets feedback signals from the
section switch through control inputs Y1-Y0 and
Y2-Y0 respectively. The time intervals from
de-energizing both output relays to receiving
both feedback signals is displayed. The menu is
returned to by confirming with the OK button.
18BCJ Controls Protection Relays Specialist
- When you have a large solar system connecting to
the grid, the utility requires special
precautions to keep the grid safe. For that you
need a 'Grid Protection System' - it is what
stands between your solar system and the
electricity grid. BCJ Controls helps solar
installers navigate the grid connection process
to get the system on-line. - We start by supplying a design for the Grid
Protection System to use to apply to the utility
(aka. DNSP) including information about the
network protection relay or zero export device.
19BCJ Controls
- http//bcjcontrols.com.au/