Title: The Decision Making Process ( P. 1 ) Decisions are made by


1
Voyager Micro Controls
2
The Decision Making Process ( P. 1 )
  • Decisions are made by the UCP, not the device on
    the wall.
  • 9x 9 board, same location in all units.
  • DDC control, better space temp. control.
  • Jam packed with features benefits.

3
Increased Reliability
  • Fewer Components and moving electromechanical
    parts.
  • Less likelihood of equipment down time or
    failure.
  • Standard on Voyager Microcontrol units.

4
Direct Digital Control Proportional Integral (
P. 1 )
  • P is corrective action proportional to the
    setpoint deviation.
  • I is an integral fine tuning loop, rate of
    correction is proportional to error.
  • Eliminates steady state error, providing superior
    comfort.

Set Point
5
Built-In TEST Mode ( P. 36 )
  • Tests UCP outputs
  • Initiated by applying a short across TEST
    terminals on unit LTB for 2 - 3 seconds and then
    removing.
  • The LED on the UCP will blink, indicating the
    unit is in the TEST mode.

TEST Terminals
6
On Board Diagnostics
  • Outputs provide operation status and problem
    diagnostic information.
  • Information is available at the rooftop unit, or
    in the zone (when using a Zone Sensor with remote
    panel capabilities).
  • Standard on Voyager Microcontrol units.

7
Low Ambient Start Timer (LAST)
  • Bypasses low pressure switch when a compressor
    starts.
  • Eliminates nuisance compressor lockouts under low
    ambient conditions.
  • Standard on Voyager Microcontrol units.

8
Anti Short Cycle Timer (ASCT)
  • No longer a field installed accessory.
  • Enhances compressor reliability.
  • Ensures proper oil return.
  • Provides a 3 minute minimum ON time and a 3
    minute minimum OFF time.
  • Standard on Voyager Microcontrol units.

9
Time Delay Relay (TDR)
  • No longer a field installed accessory.
  • Provides an incremental delay between compressor
    stages, keeps compressors from starting
    simultaneously.
  • Minimizes equipment current inrush.
  • Standard on Voyager Microcontrol units.

10
Fan Delay Relay (FDR)
  • Enhances equipment efficiency and reliability.
  • Provides custom fan timing sequences for the
    different kinds of equipment.
  • Standard on Voyager Microcontrol units.

11
Evaporator Defrost Control
  • Allows low ambient cooling to 0 F.
  • Compressor(s) are forced OFF for the 3 minute
    minimum OFF time after each 10 minutes of
    accumulated compressor run time (indoor fan
    continues to run).
  • Standard on Voyager Microcontrol units.

12
Integral Electric Heat Staging
  • Stages electric heat ON and OFF.
  • Eliminates the use of outdated sequencers.
  • Improves reliability.
  • Standard on Voyager Microcontrol units.

13
Intelligent Fallback
  • Built in default control provides adaptive
    operation.
  • Allows the equipment to operate in the event of
    certain component failure.
  • Emergency operation without a sensor.
  • Standard on Voyager Microcontrol units.

14
Emergency Stop Terminals
  • The Low Voltage Terminal Board (LTB) LTB-16 and
    LTB-17.
  • Provides a convenient point to disable the
    equipment completely, and immediately.
  • Standard on Voyager Microcontrol units.

15
Easy Sensor Installation
  • When using a Zone Sensor, control wiring may be
    run 5 times further than conventional
    electromechanical units, vitrually any wiring
    will do
  • 1 to 1, 2 to 2, 3 to 3 terminals
  • Standard on Voyager Microcontrol units.
  • Broad offering of sensors

16
Alternating Lead / Lag
  • Equalizes compressor wear run time on dual
    compressor models.
  • During part load operation compressors cycle
    alternately as circuit number one.
  • To enable, cut the wire at UCP J1-7.
  • Standard on Voyager Microcontrol units.

17
Demand Defrost (3-7.5 ton) WCs
  • Optimizes and lowers operating costs.
  • Defrosts only if needed, not based on time like
    most other systems.
  • Soft start (switchover valve delay)
  • Smart recovery (.1 deg / min)
  • Standard on Voyager Microcontrols units.

18
Remote Sensing
  • All standard Zone Sensor Modules have this
    capability.
  • Usually achieved using an expensive programmable
    thermostat and remote sensor on
    electro-mechanical equipment.
  • Accessory (requires use of remote sensor).

19
Space Temperature Averaging
  • All standard Zone Sensor Modules, with the
    exception of BAYSENS022A, have this capability.
  • Usually achieved using an expensive programmable
    thermostat and 4 remote sensors on
    electro-mechanical equipment.
  • Accessory (requires use of 4 remote sensors).

20
Supply Air Tempering
  • When in Heat mode and not actively heating, keeps
    discharge air temp within /- 10 F. of active
    heating set point.
  • Extremely effective when introducing any quantity
    of outside air.
  • Requires use of an ICS device, digital or
    programmable Zone Sensor, and economizer
    accessory.

21
Night Set Back Unoccupied
  • Sets cooling set point up 7 F., sets heating set
    point back 7 F., forces damper minimum position
    to zero, and fan operation to automatic.
  • Enabled by using a dual set point / auto change
    over Zone Sensor, and applying a short across
    terminals LTB-11 and LTB-12.
  • Requires timeclock or field supplied switch.

22
Built In Unoccupied Mode
  • Forces damper minimum position to zero, and fan
    operation to automatic.
  • Enabled by using a single set point / manual
    change over Zone Sensor, and applying a short
    across terminals LTB-11 and LTB-12.
  • Requires timeclock or field supplied switch.

23
Selectable Economizer Dry Bulb Change Over
  • Allows capability of field selecting dry bulb
    change over points.
  • Selectable points are 55, 60 or 65 F.
  • Standard with economizer accessory.
  • Enthalpy control available
  • Comparative enthalpy also available

24
Start Up Without A ZSM ( P. 37 )
  • Outdoor air sensor can be used temporarily to
    provide comfort.
  • Located in corner post, next to control box.
  • Connect to LTB-1 2.
  • CSP74, HSP71, auto change over, runs indoor fan
    continuous.

25
Wiring - ICS Device To TCI ( P. 5 )
  • Tracer / Tracker compatible
  • Shielded / twisted pair of conductors must be
    used.
  • 18 - gauge, maximum of 25 picofarads/ft.
  • Length - 5,000 feet or less.

Shielded / Twisted Pair