Title: FUNDAMENTAL BEHAVIOR OF CFT BEAM-COLUMNS UNDER FIRE LOADING


1
FUNDAMENTAL BEHAVIOR OF CFT BEAM-COLUMNS UNDER
FIRE LOADING
  • Amit H. Varma, Sandgo Hong
  • Purdue University
  • 2005 ASCE Structures Congress
  • New York City, NY

2
INTRODUCTION
  • Significant research has been conducted on the
    fire resistance of composite CFT columns under
    standard fire loading.
  • Researchers at NRC-Canada (Lie, Kodur, Irwin,
    etc.), China (Lin-Hai Han), and Japan (Sakumoto
    using FR steel)
  • Focus on the behavior of columns subjected to
    constant axial loads, end conditions, and ASTM
    E119 fire time-temperature loading
  • The results provide fire resistance rating (FRR)
    values and have been used to develop standard
    fire resistant design
  • They do not provide knowledge of the fundamental
    force-deformation-temperature behavior of the CFT
    column or the critical failure segments
  • Limited research has been conducted on the
    fundamental force-deformation-temperature
    behavior of composite CFT beam-columns under
    combined axial and flexural loads and elevated
    temperatures from fire loading

3
MOTIVATION
  • Why is it relevant? Four reasons
  • The section force-deformation-temperature
    (P-M-f-T) represents the fundamental behavior of
    CFT beam-columns and it can be used to
    investigate the effects of various geometric,
    material, and insulation parameters on fire
    resistance.
  • These P-M-f-T responses can be used to calibrate
    beam-column finite element models used to conduct
    structural analysis under fire loading
  • The behavior and stability of moment resisting
    frames under fire loading depends on the strength
    interaction P-M-T curve for and the fire
    resistance of the connections
  • The stability of columns under fire loading also
    depends eventually on the P-M-f-T response of the
    critical failure segment at mid-span.

4
RESEARCH OBJECTIVES
  • The objectives of this research project are
  • To analytically and experimentally investigate
    the fundamental force-deformation-temperature
    (P-M-f-T) behavior of CFT beam-columns under
    elevated temperatures from fire loading.
  • To evaluate the effects of various material
    (concrete strength, steel yield stress),
    geometric (column size, width-to-thickness
    ratio), and insulation (thickness, thermal
    conductivity) on the fundamental P-M-f-T behavior
    of CFT beam-columns.
  • To develop (or calibrate) fiber-based finite
    element models for modeling CFT columns and
    beam-columns while investigating the fire
    behavior of CFT structures.

5
RESEARCH APPROACH
  • Development and validation of analytical approach
    for simulating the thermal and structural
    behavior of CFT members under structural loads
    and fire loading.
  • Preliminary analytical investigations of the
    fundamental P-M-f-T behavior of CFT beam-columns
    under elevated temperatures from fire loading.
    Evaluate the effects of geometric, material, and
    insulation parameters.
  • Experimental investigations to measure the
    fundamental P-M-f-T behavior of CFT beam-columns
    under combined axial and flexural loads and
    elevated temperatures from fire loading.
  • Analytical model calibration. The experimental
    results will be used to validate (or calibrate)
    the preliminary analytical models. The
    experimental results and calibrated models will
    be used to develop beam-column finite element
    models .

6
ANALYTICAL APPROACH
  • The analytical approach was developed and
    validated using existing experimental data for
    CFT columns tested under fire loading by
    researchers at NRC, China, and Japan.
  • Development and validation of the analytical
    approach was presented in detail at the 2004 ASCE
    Structures Congress
  • The approach consists of three sequentially
    coupled analysis steps, where the results from
    each step are required to continue the analysis
    in the subsequent step
  • Step I Fire dynamics analysis
  • Step II Nonlinear heat transfer analysis
  • Step III Nonlinear stress analysis

7
Step 1 - FIRE DYNAMICS ANALYSIS
  • Fire dynamics analysis is conducted to simulate
    the convection and radiation heat transfer from
    the fire source (or furnace walls) to the
    structural component by solving the simplified
    Navier-Stokes equations numerically.
  • It is conducted using the NIST-BFRL developed
    software FDS, and the results include the heat
    flux incident upon the surfaces of the component
    or the surface T-t curves.

8
Step 2 - NONLINEAR HEAT TRANSFER ANALYSIS
  • Nonlinear heat transfer analysis is conducted to
    simulate the heat transfer through the
    cross-section of the component and along its
    length (and the associated convection and
    radiation losses).
  • The surface heat flux or T-t curves from the fire
    dynamics analysis serve as thermal loading for
    conducting the heat transfer analysis.
  • The heat transfer analysis can be conducted using
    the FDM or FEM. It is assumed uncoupled from the
    stress analysis, which is adequate for structural
    materials.
  • We used FEM because it links more easily with
    step 3. The results from the heat transfer
    analysis include the T-t curves for the nodes of
    the FEM mesh and thermal contours.

9
Step 3 NONLINEAR STRESS ANALYSIS
  • Nonlinear stress analysis is conducted to
    determine the structural response of the
    component under applied structural and thermal
    loads.
  • The nodal time-temperature (T-t) curves obtained
    from the heat transfer analysis of step 2 define
    the thermal loads for the nonlinear stress
    analysis
  • The stress analysis can be conducted using the
    finite element method while using identical
    meshes for both steps 2 and 3.
  • The results from the analysis include the
    complete structural response deflections,
    strains, stresses, load-displacement-temperature
    relationships.

10
Step 3 NONLINEAR STRESS ANALYSIS
  • For example, the behavior of CFT columns tested
    according to the ASTM E119 was investigated using
    the 3-step approach
  • The sequentially coupled heat transfer and
    structural analysis were conducted using the FEM
    and option in ABAQUS.
  • The analytical approach was validated for an
    assortment of CFT columns with different
    material, geometric, insulation parameters tested
    independently by researchers in Canada, China,
    and Japan

11
GENERAL FINDINGS
  • The analytical approach was developed and
    validated, but the behavior of CFT columns under
    fire loading were found to be very sensitive with
    respect to
  • Temperature dependent steel and concrete material
    structural properties, which are not measured or
    reported explicitly for most CFT specimens.
  • Column end conditions (rotational and axial
    restraint). End conditions obtained in the
    experiment may vary from those assumed in the
    analysis.
  • Variations in axial load level (P/Po). Axial load
    level can vary due to changes in axial load P due
    to restraint, or due to Po which depends on steel
    and concrete strength variation.
  • Relative motion (slip) between steel tube and
    concrete infill at ends. This slip occurs for
    some columns that were tested individually and
    the slip was allowed to occur. This may not be
    realistic.

12
PRELIMINARY ANALYTICAL INVESTIGATIONS
  • Preliminary investigations were conducted using
    the (developed and validated) analytical approach
    to determine the more fundamental
    force-deformation (P-M-f) behavior of CFT
    sections under elevated temperatures from fire
    loading.
  • These P-M-f-T responses and the effects of
    various material, geometric, and insulations
    parameters are the focus of the research for
    reasons explained earlier.
  • CFT parameters
  • Width b 200 or 300 mm.
  • Width-to-thickness ratio 32 or 48
  • Steel tube A500 Gr. B (300 MPa)
  • Concrete strength (fc35 MPa)
  • Axial load levels (P0, 20, 40)
  • Thermal insulation thickness (0, 7.5, 13 mm
    thick)

13
PRELIMINARY ANALYTICAL INVESTIGATIONS
  • The analytical investigations were conducted on a
    segment of the CFT beam-columns. The length of
    the segment was equal to the cross-section width
    b.
  • It represents the critical segment of CFT column
    or beam-column subjected to axial and flexural
    loads and elevated temperatures from fire
    loading.

Step 1 FDS analysis to simulate heat transfer
to the surface of the segment Step 2 Nonlinear
heat transfer analysis to simulate transfer
through section and along length Step 3
Nonlinear stress analysis for constant axial
load, monotonic flexural loading moment), and
nodal thermal loading (T-t) from step 2 Steps 2
and 3 conducted using the finite element method
and ABAQUS
14
MATERIAL PROPERTIES T Dependent
  • Temperature dependent thermal and structural
    material properties were used along with the 3D
    finite element models of the CFT failure segment.
  • These material properties were based on values
    generally reported in the literature (Lie and
    Irwin 1995 etc.).
  • T-Thermal properties are given in a table in the
    paper

100oC
Concrete s-e-T
Steel s-e-T
T100oC
300oC
T300oC
500oC
T500oC
700oC
T700oC
900oC
T900oC
15
Thermal response- CFT without insulation
16
Structural Response CFT without ins.
Step 3 P-M-f-T curves for CFT without insulation
17
Findings for CFTs Without Insulation
  • For CFTs without insulation
  • Fire loading results in quick heating of the
    steel tube (broiling) while the concrete infill
    remains relatively cooler. Significant portions
    remain at Tlt 100oC till much later
  • This relative heating causes rapid reduction in
    flexural stiffness and strength of the CFT
    section under fire loading effects
  • This reduction depends primarily on the rise in
    steel temperature, and is independent of axial
    load level, width, and other parameters
  • This by itself, may not be a cause of concern
    unless the demands placed on the CFT without
    insulation exceed the reduced stiffness and
    strength at elevated temperatures

18
Thermal response of CFT with insulation
  • Consider similar CFTs with some insulation.
    Assume commonly used insulation materials with
    properties given in the paper.
  • The presence of thermal insulation results in a
    slow increase in the steel surface temperature.

19
Structural Response of CFT with Insulation
20
Findings for CFTs with Insulation
  • The insulation thickness becomes the most
    important parameter influencing P-M-f-T behavior
    and strength (P-M) under elevated temperatures
    from fire loading.
  • As expected, CFTs with b/t 48 have greater
    increase in moment capacity with increase in
    axial load (below the balance point). This
    continues to be true at elevated temperatures
    also.
  • The tube width (b) and width-to-thickness (b/t)
    ratio do not have significant influence on the
    P-M-f-T behavior of CFTs at elevated temperatures
    from fire loading

21
EXPERIMENTAL INVESTIGATIONS
  • Experimental investigations will focus on
    measuring the P-M-f-T response of CFT segments.
    Parameters included in the experimental studies
    are
  • Tube width (b) and b/t ratio
  • Concrete strength fc
  • Axial load level
  • Heating (surface temperature)
  • Insulation thickness and type
  • Experimental test matrix is currently being
    finalized using results of preliminary
    investigations

22
TEST SETUP
  • The test-setup will be similar to those used for
    measuring P-M-f response of beam-column specimens
    at ambient temperature
  • It will be a cantilever column with axial force
    and lateral load applied at the top (free) end
    and the bottom end clamped.
  • A custom-built portable furnace will be placed to
    surround the plastic hinge region. It will
    subject the surface to the selected T-t curve.
  • Thus, the specimen plastic hinge region will be
    subjected to P, M, and T.
  • The deformations of the plastic hinge region will
    be measured using close-range photogrammetry and
    digital image processing techniques.

23
FURNACE DESCRIPTION
  • The portable furnace consists of ceramic fiber
    radiant heaters. Four such panel heaters are
    assembled to form a box around the hinge region.
  • Heaters have wattage density of 2.5 kW/ft2. Can
    provide surface temperature approaching 1200oC.
    They use radiant heating which is efficient and
    economic

24
FURNACE T-t CONTROL
  • Radiant heaters are fully controllable. Specify
    control surface T-t curve and the heater will
    provide it.
  • For example, in the experiment below, we are
    controlling steel surface T-t curve under the
    insulation.
  • The insulation surface T-t curve can also be
    directly controlled. This experiment is in
    progress.

25
FURNACE T-t CONTROL
  • In this experiment we are directly controlling
    the steel surface T-t curve without insulation to
    follow the ASTM E119 gas T-t curve.

26
DEFORMATION MEASUREMENTS
  • The deformation (or movement) of any point on the
    specimen surface can be measured using
    close-range photogrammetry and digital image
    processing fundamentals.
  • For example, the thermal expansion was measured
    as shown below.

27
TEMPERATURE MEASUREMENTS
  • Thermocouples bonded to steel and embedded in
    concrete to measure temperatures

28
EXPERIMENTAL INVESTIGATIONS
  • Will be conducted this year. Results to be
    presented at next ASCE Structures Congress.
  • Acknowledgments
  • National Science Foundation - funding
  • Purdue University
  • Dr. Jim Bethel photogrammetry
  • Jarupat Srisa-Ard - student

29
  • THE END

30
MOTIVATION 2
  • Researchers around the world have developed
    finite element method based computer programs to
    conduct structural analysis under fire loading.
  • For example, researchers at Liege Univ. (SAFIR),
    Sheffield Univ. (FEMFAN), Univ. of Manchester,
    Nat. Univ. of Singapore (SINTEF)
  • Most of these programs use fiber-based or
    concentrated hinge based beam-column finite
    elements for modeling the behavior of columns and
    beam-columns under fire loading
  • These finite elements must be validated (or
    calibrated) using experimental data and realistic
    P-M-f-T behavior

31
MOTIVATION 3
  • Consider a 6-story structure with perimeter
    moment resisting frames for lateral stiffness and
    stability.
  • Design for dead, live, wind loads.
  • Satisfy building and interstory drift
    requirements.
  • Consider state when subjected to
    D0.5LWCompartment Fire load

32
MOTIVATION 4
  • The behavior and failure of columns under
    constant axial load and elevated temperatures
    from fire loading also depends on the section
    P-M-f-T response of the failure segment.

33
Step 1 - FIRE DYNAMICS ANALYSIS
  • During experiments, the furnace gas temperature
    was controlled to follow the ASTM E119 T-t curve.
    The temperatures of the CFT column surfaces were
    measured using thermocouples.
  • FDS model of the furnace, and the surface T-t
    curves for 200, 250, and 300 mm CFT columns that
    were tested shown below.

34
Step 2 - NONLINEAR HEAT TRANSFER ANALYSIS
  • For example, nonlinear heat transfer analyses of
    CFT columns tested by other researchers were
    conducted.
  • The surface T-t curves from step 1 were used as
    thermal loading
  • 3D finite element models were developed to
    conduct the heat transfer analysis and analyzed
    using ABAQUS.
  • The results were compared with experimental
    results.

35
Stress analysis results for CFT beam-column with
b/t32, P/Po 20, and insulation thickness6.5
mm (Curvature 12.5 x 10-5 1/mm)