Power System Engineering - PowerPoint PPT Presentation

1 / 32
About This Presentation
Title:

Power System Engineering

Description:

Valley Forge, PA. Aims for Today. Chapter 5: Control of Voltage & Q. Parts 5.1-5.5, 5.7-5.9, 5.11 ... Voltage difference between two points in electric system ... – PowerPoint PPT presentation

Number of Views:314
Avg rating:3.0/5.0
Slides: 33
Provided by: jans2
Category:

less

Transcript and Presenter's Notes

Title: Power System Engineering


1
Power System Engineering
  • ECE 0909.408.01
  • ECE 0909.504.02 - Lecture 10
  • 17 April 2006
  • Dr. Peter Mark Jansson PP PE

2
Admin. Items
  • Leave 8.10 AM This Thursday
  • PJM Interconnection
  • Valley Forge, PA

3
Aims for Today
  • Chapter 5 Control of Voltage Q
  • Parts 5.1-5.5, 5.7-5.9, 5.11
  • Chapter 6 Load Flows
  • Parts 6.1, 6.2, 6.6
  • Chapter 8 System Stability
  • Parts 8.1, 8.4, 8.8

4
Voltage and Q
  • Voltage difference between two points in electric
    system and flow of reactive power was given
    previously as

5
Voltage drives Q
  • In most systems XgtgtR and reactive power is
    determined then by ?V

6
Power and Q Flow
  • See Board
  • Machine at A is in phase advance of B
  • V1 is greater than V2
  • Hence
  • Power and Reactive Power flow from A ? B

7
Power and Q Flow
  • Machine at A is still in phase advance of B
  • But now we adjust generator excitation so that V2
    is greater than V1
  • Now
  • Power flows from A ? B but Reactive Power flows
    from B ? A

8
Power and Q
  • Real Power flows are controlled by adjusting real
    power generated at any point in the system
    (leading to phase advance relationship) i.e.,
    steam flow to turbogenerator
  • Reactive Power (Q) flows are determined by
    excitation to the generator and resulting voltage
    relationship between points A B

9
Phasor Diagrams
  • Phasor diagrams show that reactive power flow
    will be determined y the scalar voltages
    maintained within the system
  • Hence Q flows from higher V to lower Vs

10
Voltage Instability
  • If reactive power support is insufficient for
    loads in a given part of the network voltage
    will fall
  • Conversely, if there is an excess of reactive
    power voltage will rise
  • Generating/Absorbing Q in system
  • Synchronous Generators make/absorb Q
  • Load Support capacitors change PF of load
  • Lines (O/H, cable) and Transformers

11
Synchronous Generator
  • Used to generate or absorb VARS
  • Typical 200 MW (85 PF) machine
  • Has 45MVAr capability at full load
  • Overexcited Machine (one with higher than normal
    rotor field excitation) generates vars (locally
    increasing voltage to export them)
  • Underexcited Machine absorbs vars
  • Main source of / - vars

12
Lines O/H
  • When fully Loaded
  • Lines absorb Reactive Power
  • For current I and Reactance X the vars absorbed
    are I2X per phase
  • When lightly Loaded
  • Lines can generate Reactive Power
  • Shunt capacitance of lines can dominate their
    electrical characteristics on low current flows

13
Lines Cables
  • Whether fully or Lightly Loaded
  • Always generate Reactive Power
  • Shunt capacitance of these lines always dominates
    their electrical characteristics
  • 275kV, 240 MVA cable
  • Generates 6.25-7.5 MVAr per km
  • 132kV 1.9 MVAr per km
  • 33kV 0.125 MVAr per km

14
Transformers
  • Whether fully or Lightly Loaded
  • Always absorb Reactive Power
  • Why?

15
Loads
  • Inherent in power system are loads of time
    varying power factor
  • Power factor of loads plays major role in
    determining required Q
  • Example Load at power factor of 0.95 implies
    that we have a demand for 0.33 kVAr for each kW
    of real power delivered

16
Voltage Control
  • METHOD 1 Injecting Reactive Power
  • Static Shunt Capacitors
  • Static Series Capacitors
  • Synchronous Compensators
  • Current Compensation by series injection

17
Static Shunt Capacitors
  • Lagging Power Factor correction
  • At source (factory, building, etc.)
  • Should be switched into circuit, parallel with
    primary busbar, as inductive loads require
    (ON/OFF)
  • Improving load power factor could alleviate
    entire reactive power problem on electrical system

18
Static Series Capacitors
  • Placed in series with line conductors
  • Best when
  • Total line reactance is high
  • Voltage drop is limiting factor
  • Can average voltage fluctuations in load
  • Must be protected from short circuit currents
  • Of little value if few load vars are needed

19
Synchronous Compensators
  • Synchronous motor operating without a mechanical
    load
  • Depending on excitation level it can absorb or
    generate reactive power
  • Cost of installation (OM) is high
  • Flexibility for all load conditions
  • Stored energy of rotating machine useful for
    riding through transient disturbances

20
Series Injection
  • Power Electronics
  • High-power, high-voltage semi-conductor
    controlled devices
  • Pulse turn-on, turn-off inverters
  • Can inject voltage in in series with a line of
    any phase angle
  • Sources transformers, battery pack, capacitor,
    etc.) external charging may be required

21
Voltage Control
  • MORE METHODS
  • Tap Changing Transformers
  • Combined Use of TCT and Q injection
  • Booster Transformer
  • Phase shift Transformer

22
Voltage Collapse
  • When loads are stable and mostly resistive
    collapse in voltage is unlikely as voltage
    decreases so does load
  • However, most system loads are inductive and the
    loss of voltage leads to unstable responses from
    induction devices (motors stall, etc.)

23
(No Transcript)
24
14 August 2003
  • https//reports.energy.gov/
  • U.S. Canada Power Systems Outage Task Force
    Causes of the August 14th Blackout

25
Reliable transmission
  • 7 principles
  • 1. Continuously balance generation / demand
  • 2. Balance reactive power to maintain voltage
  • 3. Monitor flows to not exceed thermal limits
  • 4. Keep system in stable condition
  • 5. Keep system in reliable condition (n-1)
  • 6. Plan, design and maintain to operate reliably
  • 7. Prepare for emergencies

26
Sequence unchanged
  • Assessment
  • Inadequate System Observation Loss of System
    Control and Data Acquisition
  • Outages due to inadequate tree trimming
  • Harding Chamberlain 345 kV 43.5 loaded
  • Hanna-Juniper 345kv 87.5 loaded
  • Star South 345kV 93.2 of emergency rating
  • Once this situation occurred FE needed to
    voluntarily reduce load so as not to impact
    remaining system, due to their unawareness of the
    n-1 contingency breach they did not take this
    critical action

27
Load Flows
  • The steady-state solution for a power system
    given conditions is referred to as the load flow
  • In most cases resistance of lines can be ignored
    with very limited impact on final solution
  • Comprehensive mathematical models enable the
    simulation of large systems

28
In order to simulate..
  • We need a floating busbar to feed required
    losses into the system
  • Load nodes specifying the complex power SP/-jQ
  • Generator nodes voltage magnitude and power

29
Load Flow Studies for
  • Flow of MW, MVAr in branches
  • Busbar voltages
  • Effects of changing circuitry
  • Effects of temporary loss of
  • Generators
  • Transmission lines
  • Transformers or other key devices

30
Load Flow Studies for
  • Effect of injecting VArs
  • Optimum system running conditions
  • Minimizing system losses
  • Optimum rating of and tap-range transformers
  • Improvements
  • Changing conductor size
  • Additional generation
  • Improving system voltage

31
Why? A load flow study
  • Check for unstable conditions
  • Minimum loading
  • Maximum loading
  • Economic studies
  • Optimize dispatch of units for economy
  • Determine benefits of new lines, etc.

32
Thursday AM
  • Please dont forget to attend
  • PJM Headquarters Visit 9-12
  • 8.10 AM This Thursday morning
Write a Comment
User Comments (0)
About PowerShow.com